Anna LIS

Czestochowa University of Technology

THE ASSESSMENT OF EFFECT OF SELECTED ELEMENTS ON THE HEAT LOSSES

The paper presents the results of investigations on building’s heat losses.

The heat balance conditions in selected buildings were observed. The factors which influence on heat losses in analysed buildings were identified. The changes of value of these quantities on the influence of individual factors were estimated. Figures illustrate the formation of values related to heat losses in given buildings depending on the selected factors. Regression equations correlations and coefficients were determined.

Keywords: heat losses, heat balance conditions, heat consumption for heating build- ings, single-family buildings

INTRODUCTION

Heat losses in a building result from heat penetration through external and inter- nal partitions as well as from heating up the air exchanged in the ventilation process.

Heat lost on penetration has been up till now the highest value in the annual loss account [1, 2]. With low thermal insulation of partitions it amounted to 80%. The observed and predicted increase of thermal insulation of external coating of build- ings causes high dependence of heat losses on the ventilation needs. Heat lost on ventilation with air-tight enclosures amounts to 70÷80% [3]. Wind is a significant factor intensifying losses. At the speed of 3 m/s heat losses increase by 2%, and with 6 m/s exceed by 25% the value of losses as compared to the windless weather.

The shape and location of a building has a considerable influence on the whirl and wind velocity. The shape of the building determines as well its energy properties.

Precipitation causing dampness of partitions and deterioration of their thermal insu- lation increases heat losses [4].

1. THE RESULT’S OF INVESTIGATION

Research was conducted in a dozen or so single-family one- or two-storey buildings, built in traditional technology. Two buildings had a complete basement, but only one basement was heated. One building had a partial basement. The build- ings were situated with minimal glazing facing north and maximal - south.

(2)

It was determined: window’s surface Po, wall’s surface Ps, heating surface Pu, cooling partition’s surface A, heating cubic capacity V, shape’s coefficient A/V, glazing’s surface Po/Ps, window's surface/heating surface Po/Pu, window's surface/

/heating cubic capacity Po/V, air change’s quantity to ventilation and person quantity. Selected statistical indexes of parameters which characterized research buildings and quantity of people which used these buildings are presented in Tables 1 and 2. ( x ) is arithmetic mean, (H) is harmonic mean and (s) is standard deviation.

Table 1. Air change’s quantity to ventilation and person quantity Statistical

Indexes Air change’s quantity to ventilation Person quantity

x 1.1 5.9

s 0.4 1.4

Table 2. Parameters of research buildings Statistical

Indexes

Po Ps V Po/Ps Po/V A/V

m2 m2 m3 % m–1

x 39.6 199.3 581.9 20.2 6.9

H 0.9

s 11.3 57.8 110.1 3.7 1.8 0.1

2. THE ANALYSIS OF HEAT LOSSES

The heat losses in research buildings was determined. The results are shown in Table 3. (H) is harmonic mean and (s) is standard deviation.

Table 3. Heat losses in research buildings Statistical

Indexes

Heat losses

[kWh/year] [GJ/year]

H 34 646.3 124.8

s 7555.1 24.1

Figures 1-6 illustrate the formation of values related to heat losses in given buildings depending on the selected factors. Regression equations correlations and coefficients were determined. Only dependencies for the factors for which correla- tion coefficients remained at the level 0.5÷1 were presented. For the rest of factors, correlation coefficients were below 0.3.

(3)

y = -0.0002x2 + 0.4096x - 35.761 r = 0.8419

80 100 120 140 160 180

400 500 600 700 800

Cooling partition's surface A, m2

Heat losses, GJ/year

Fig. 1. The cooling partition’s surface influence on heat losses

y = -0.0011x2 + 1.5176x - 369.98 r = 0.9032

80 100 120 140 160 180

400 500 600 700 800 900

Heating cubic capacity V, m3

Heat losses, GJ/year

Fig. 2. The heating cubic capacity influence on heat losses

y = 97.159x2 - 131.05x + 165.95 r = 0.5329

80 100 120 140 160 180

0,70 0,80 0,90 1,00 1,10

Shape's coefficient A/V, m-1

Heat losses, GJ/year

Fig. 3. The shape’s coefficient influence on heat losses

(4)

y = -29.204x2 + 128.05x + 30.612 r = 0.8679

80 100 120 140 160 180

0,5 0,7 0,9 1,1 1,3 1,5

Air change's quantity to ventilation

Heat losses, GJ/year

Fig. 4. The air change's quantity to ventilation influence on heat losses

y = -0.0004x2 + 0.4126x + 61.999 r = 0.7352

80 100 120 140 160 180

120 160 200 240 280 320

Wall surface Ps, m2

Heat losses, GJ/year

Fig. 5. The wall surface Ps influence on heat losses

y = -0.0967x2 + 9.6117x - 88.398 r = 0.8703

80 100 120 140 160 180

20 30 40 50 60 70

Window's surface Po, m2

Heat losses, GJ/year

Fig. 6. The window’s surface Po influence on heat losses

(5)

SUMMARY AND CONCLUSION

The amount of heat lost through partitions mainly depends on their surface area, heat-insulating properties and the temperature difference. For the sake of energy management a bigger density of the building’s solid is advantageous, however a shape factor has a direct and more significant influence on heat consumption than exclusively on its losses. A more significant relation was obtained for the analysis of the influence of the surface of cooling partitions. Increasing in a certain bracket the insulation thickness influences to a small extent the percentage increase of capi- tal spending, however after having reached a certain value further increase of insu- lation thickness does not result in the noticeable economic effects, but it becomes a source of construction problems. Analysing the heat losses it is more beneficial to use only the window surface, and not the elevation glazing. In the first case a clear correlation was noticed, while the changes in elevation glazing influenced the changes in heat losses only in 7%. Excessive size of transparent surface area is to a larger extent a source of increased heat losses than the factor generating con- siderable gains. In summer, however, it causes the overheating of rooms and the loss of thermal comfort. Keeping the required parameter values of microclimate, and especially of temperature, also influences the heat losses. Lowering the temperature from 20°C to 18°C causes the heat drop by about 8.5%.

REFERENCES

[1] Košičanová D., Sedláková A., Energy precautions in buildings in dependence on energy consumption of buildings, [in:] Budownictwo o zoptymalizowanym potencjale energetycznym, ed. T. Bobko, J. Rajczyk, Wyd. Politechniki Czestochowskiej, Częstochowa 2010, 146-150.

[2] Perez-Lombard L., Ortiz J., Pout Ch., A review on buildings energy consumption information, Energy and Buildings 2008, 40, 394-398.

[3] Wolski L., Kamiński A., Efektywność energetyczna - dążenie do zmniejszenia zużycia energii, Ciepłownictwo, Ogrzewnictwo, Wentylacja 2009, 6, 15-19.

[4] Lis A., Ocena poziomu zużycia ciepła w budynkach, Czasopismo Techniczne 2009, 5, 157-165.

OCENA WPŁYWU WYBRANYCH PARAMETRÓW NA STRATY CIEPŁA

W pracy przedstawiono rezultaty badań dotyczących strat ciepła z budynków.

Analizowano bilans cieplny wybranych budynków mieszkalnych jednorodzinnych.

Określono parametry wpływające na straty ciepła z budynków. Oszacowano wpływ wybranych parametrów na zmiany wartości strat ciepła.

Słowa kluczowe: bilans cieplny budynków, straty ciepła, zużycie ciepła do ogrzewa- nia budynków, budynki mieszkalne jednorodzinne

Cytaty

Powiązane dokumenty

Heat exchanger with double jacket from copper can be installed to the downpipe for utilization of heat from waste water.. The inner jacket is pipe from plain copper tube that

W Polsce coraz częstszą, choć wciąż mało popularną, metodą ogrzewania domu jednorodzinnego jest pozyskiwanie ciepła z ziemi, powietrza,... wody za pomocą

The annual average heat loss with groundwater present is by 45% greater in the case without any thermal insulation (variant I), 60% greater with vertical foundation

Na podstawie wykresu uporz¹dkowanego temperatur dla lokalizacji odbiorcy ciep³a oraz tabeli regulacyjnej parametrów dostarczanego ciep³a rozwa¿ono dwa warianty uciep³ownienia

The building’s heating in the above- -mentioned technologies using an active thermal insulation is realised through a combination of passive solar energy use within the roof

Większe zaniepokojenie daje się dostrzec pod koniec analizowanego okresu, gdy czasopisma antysemickie zauważyły wzrost popularności idei neosłowiańskich wśród pol­ skich

24 J.. Dla sprawy udało się pozy­ skać przychylność Ministra Kultury i Sztuki, który zainicjował nawet Zjazd A r­ chitektów i Artystów Rzeźbiarzy w Gdańsku. Jako model

This paper introduces a zero-dimensional single zone model considering detailed chemical kinetics in order to study on the operational and combustion characteristics of a natural