12. DISPLAY

12.3. Bar Graph

12.3.1. Bar Graph Type

 Enter < Display / Bar graph / Bar graph type> submenu and set respective bar graph type.

Available bar graph types: none (no bar graph displayed), fast weighing, weighing threshold signalling, linear, workspace, control*.

*) – PGC and SQC working modes exclusively. The remaining bar graph types are not available for PGC and SQC working modes.

12.3.2. 'Fast Weighing' Bar Graph

Settings of Fast Weighing bar graph are to be found in < Display / Bar graph / Fast weighing> submenu:

MIN, MAX thresholds working mode

Stable – MIN, MAX thresholds signalling lights up when LO threshold gets exceeded, and when stable weighing result is obtained.

Unstable – MIN, MAX thresholds signalling lights up when LO threshold gets exceeded.

OK threshold working mode

Stable – OK threshold signalling lights up when LO threshold gets exceeded, and when stable weighing result is obtained.

Unstable – OK threshold signalling lights up when LO threshold gets exceeded.

MIN threshold signalling colour Enter to select colour for MIN threshold signalling; 18-colour palette.

OK threshold signalling colour Enter to select colour for OK threshold signalling; 18-colour palette.

MAX threshold signalling colour Enter to select colour for MAX threshold signalling; 18-colour palette.

Gradient Enter to enable/disable 'Gradient' fill effect.

Background colour Enter to select bar graph background colour;

18-colour palette.

Border colour Enter to select bar graph border colour;

18-colour palette.

Operation description:

 Bar graph consists of 8 red fields and 3 green fields.

 Green fields signal weighings comprised within MIN and MAX thresholds.

MIN = low limit of correct weighing LO.

MAX = high limit of correct weighing HI.

 If the weighing result value is greater than MIN value (but lower than 1/3 of MIN - MAX range), green square-shaped field and green triangle-shaped field on the left light up.

If the weighing result value is greater than 1/3 of MIN - MAX range and lower than 2/3 of MIN - MAX range, green square-shaped field lights up.

If the weighing result value is greater than 2/3 of MIN - MAX range and lower than MAX value, green square-shaped field and green triangle-shaped field on the right light up.

 If the weighing result value is lower than MIN value, red arrow-shaped fields on the left light up. The lower the value the more red fields on the left are lit up.

 If the weighing result value is greater than MAX value, red arrow-shaped fields on the right light up. The greater the value the more red fields on the right are lit up.

MIN value is on the left, on the border between red arrow-shaped field and green triangle-shaped field; MAX value is on the right, on the border between green triangle-shaped field and red arrow-shaped field.

12.3.3. 'Weighing Threshold Signalling' Bar Graph

Stable – MIN, MAX thresholds signalling lights up when LO threshold gets exceeded, and when stable weighing result is obtained. Unstable – MIN, MAX thresholds signalling lights up when LO threshold gets exceeded.

OK threshold working mode

Stable – OK threshold signalling lights up when LO threshold gets exceeded, and when stable weighing result is obtained. Unstable – OK threshold signalling lights up when LO threshold gets exceeded.

MIN threshold signalling

Gradient Enter to enable/disable 'Gradient' fill effect.

Background colour Enter to select bar graph background colour; 18-colour palette. load is lower than MIN value (Min threshold).

 Middle green field – the field lights up when the weight value of a measured load is comprised within tolerance low threshold and tolerance high threshold set for a given product (OK threshold).

 Right red field – the field lights up when the weight value of a measured load is greater than MAX value (Max threshold).

12.3.4. 'Linear' Bar Graph

Settings of <Linear> bar graph are to be found in < Display / Bar graph / Linear> submenu:

MIN threshold signalling colour Enter to select colour for MIN threshold signalling; 18-colour palette.

OK threshold signalling colour Enter to select colour for OK threshold signalling; 18-colour palette.

MAX threshold signalling colour Enter to select colour for MAX threshold signalling; 18-colour palette.

MIN, MAX range background colour

Enter to select MIN, MAX range background colour. 17-colour palette.

OK range background colour Enter to select OK range background colour.

18-colour palette.

Gradient Enter to enable/disable 'Gradient' fill effect.

Operation description:

Bar graph of this type provides you with a linear presentation of the weighing range.

Additionally it shows where Min and Max thresholds are (providing that they have been declared).

,

 Visualisation of mass value lower than MIN value:

 Visualisation of mass value higher than MIN value and lower than MAX value:

 Visualisation of mass value higher than MAX value:

12.3.5. 'Control' Bar Graph

<Control> bar graph is enabled in < PGC> working mode.

Operation description:

Bar graph signals:

 Qn nominal mass, declared for a selected product,

 MIN and MAX thresholds - providing that they have been declared,

 Qn-T mass values,

 Qn-2T mass values,

 Qn+T mass values,

 Qn+2T mass values,.

Where:

Qn - nominal mass T - T error

2T - double T error

 Visualisation of mass value lower than Qn-2T value:

 Visualisation of mass value higher than Qn-2T and lower than Qn-T value:

 Visualisation of mass value higher than Qn-T and lower than Qn+T value:

The field between Qn-T and Qn+T values gets zoomed automatically, magnifying glass icon is displayed.

 Visualisation of mass value higher than Qn+T and lower than Qn-2T value:

 Visualisation of mass value higher than Qn+2T value:

Operation: < SQC> working mode Bar graph signals:

 Qn nominal mass, declared for a selected product,

 Qn-T mass values,

 Qn-T2 mass values,

 Qn+T mass values,

 Qn+T2 mass values.

Where:

Qn - nominal mass T - T error

T2 - T2 error

 Visualisation of mass value lower than Qn-T2 value:

 Visualisation of mass value higher than Qn-T2 and lower than Qn-T value:

 Visualisation of mass value higher than Qn-T and lower than Qn+T value:

The field between Qn-T and Qn+T values gets zoomed automatically.

 Visualisation of mass value higher than Qn+T and lower than Qn+T2 value:

 Visualisation of mass value higher than Qn+2T value:

12.3.6. 'Workspace' Bar Graph

Settings of <Workspace> bar graph are to be found in < Display / Bar graph / Workspace> submenu:

MIN threshold signalling colour

Enter to select colour for MIN threshold signalling;

18-colour palette.

OK threshold signalling colour Enter to select colour for OK threshold signalling;

18-colour palette.

MAX threshold signalling colour

Enter to select colour for MAX threshold signalling; 18-colour palette.

Operation description:

Color-coded background of the workspace signals the MIN, MAX thresholds if they have been declared:

 Visualisation of mass value lower than MIN value:

 Visualisation of mass value higher than MIN value and lower than MAX value:

 Visualisation of mass value higher than MAX value: