34 Basic application
4.1 Basic speed or torque control
This section shows the essential requirements for a very basic speed or torque control application.
Note that the arrangement of the contactor shown here allows continuous phase sensing on EL1/2/3.
VERY IMPORTANT see 4.2 Main Contactor operation, 4.3 Main contactor wiring options, 14 Installation.
1 0V
13 0V
2 3 4 5 6 7 8 9 10 11 12UIP2 UIP3 UIP4 UIP5 UIP6 UIP7 UIP8 AOP1 AOP2 AOP3
0V DIP1 DIP2 DIP3 DIP4
14 15 16 17 18 19 20 21 22 23 24DIO1 DIO2 3ODI DIO4 DOP1 DOP2 DOP3
25 26 27 28 29 30 31 32 33 34 35 36TACH +10 -10 IARM MTH RUN JOG START CSTOP +24V 0V 41 42 43 44 45 46 5152 53
RA+ NC RA- CON1 EARTH N LNC CON2
A+ A- L1 L2 L3
EL1 EL2 EL3 F- F+TERMINALS 1 -12 FUNCTION TERMINALS 13 -24 FUNCTION 110V
AC IPFAN B1 B2
Terminals shown on the top edge are located on the lower level power board. (B1/B2 on top edge of 185/225/265 models)
Symbolic connection block.
Terminals 1 - 36 are located on the bottom edge of the upper control board arranged as 3 blocks of 12.
Terminals 2 -12, 14 - 24, and 31 are programmable.
Their default function is shown here.
Speed ref/Current ref Ramped Speed Setpoint Lower Current Clamp Main/Upper Current Clamp Motorised Pot Preset Motorised Pot Increase Motorised Pot decrease Speed Feedback
0V Terminal Total Speed Reference Total Current Demand
Speed Reference 0V Terminal Zero reference interlock Jog Speed Select Ramp Hold Current Clamp Select
Spare input Spare input Feedback encoder Feedback encoder Zero Speed Ramping flag Drive Healthy
contactor coil supply 110V AC
3 phase motor blower circuit
breaker main
semi-conductor fuses
main contactor main
contactor coil
Isolator
armature field
linereactor
auxiliary semi-conductor fuses
L3
L2
L1
10K speed pot cw
acw
emergency stop relay start
jog T+ run
thermistor
UIP9
AC Control Supply Inputs (110 -240V)
Protective clean earth.
Control supply dirty earth
47 48
LAT1 LAT2
Substantial chassis earth Use DC semiconductor
fuse for regen applications
WARNING. Do not allow coil supply to be externally interrupted.
Retro- fit relay logic is often the main culprit.
WARNING The phase order of EL1/2/3 must be the same as L1/2/3
For Torque control enter Torque ref into T6. (0 - 10V).
For speed control link T6 to +10V on T27.