Air Treatment
GEA MPower - Geko
Fan Coil Units | Data & Facts
Effective use of air distribution and capacity
Table of Contents
GEA MPower-Geko Fan Coil Unit2 PR-2009-0015-GB • Subject to modifications • Status 10/2009
Sizes ... 1.2
Fan Coil Unit Components ... 2
Unit Selection ... 3
Unit Description ... 4
Recirculating Air Unit Cooling and Heating ... 6
Accessories/Valves ... 7
Recirculating Air Unit Cooling and Heating ... 8
Accessories/Valves ... 9
Recirculating Air Unit Heating ... 10
Accessories/Valves ... 11
Recirculating Air Unit Heating ... 12
Accessories/Valves ... 13
Pressure Drop in Heat Exchanger, Warm and Chilled Water ... 14
Power and Current Consumption ... 15
Capacity Overview for Different Operating Points Size 1 ... 16
Overview of Acoustic Data for Different Operating Points, Size 1 ... 17
Capacity Overview for Different Operating Points Size 2 ... 18
Overview of Acoustic Data for Different Operating Points, Size 2 ... 19
Capacity Overview for Different Operating Points Size 3 ... 20
Overview of Acoustic Data for Different Operating Points, Size 3 ... 21
Capacity Overview for Different Operating Points Size 4 ... 22
Overview of Acoustic Data for Different Operating Points, Size 4 ... 23
Samples for Capacity Definition ... 24
Installation Samples ... 28
Dimensions of Basic Units ... 29
Dimensions of Accessories ... 31
Overview of Valves
Selection Tables... 33Valve Actuators ... 34
Valve Bodies ... 35
Shut-off Valves ... 36
Ball Traps ... 37
Control via Thermostat / Speed Switches / Control by Others ... 38
Control System GEA MATRIX ... 40
Product Type Code ... 51
Copyright noteDisclosing, copying, distributing or taking any action in reliance on the contents of this document is strictly prohibited without express prior consent. Violations entail liability for any damages or other liability arising. All rights in relation to patents, utility patents or design patents are reserved.
Sizes GEA MPower-Geko Fan Coil Unit
1) Sound level measured at unit casing, modular unit, capacity stage 1, filter class G2, without external pressure, without accessories. For other acoustic data refer to „Sample for capacity definition“, page 24 to page 27.
2) Capacity data apply for input parameters: WWP 70/50°C, tL1 = +20 °C; CWP 6/12 °C, tL1 = 27 °C, 46 % r.h. With other input parameters the following correction factors for approximate estimation of performance data should be applied.
Correction factors 3)
Size Width Air volume flow Sound power level 1)
[mm] [m3/h] [dB(A)] [kW]
1 2 3 4
Heating capacity QH Cooling capacity QK
•
•
975 515-1215 29-48 2.8-11,2
3.0-6,1
1275 685-1555 32-53 4.1-15,5
4.4-8,7
1575 810-2020 27-47 5.2-19,5
4.0-10,5
1775 1000-2460 30-51 6.2-23,4
6.1-12,7
For calculating performance data according EUROVENT classification - the following correction factors can be used:
Cooling (2-pipe system): 1,01 Cooling (4-pipe system): 0,92 Heating (2-pipe system): 0,70 Heating (4-pipe system): 1,22 Sound power4): +3 dB
Correction factors fK for cooling capacity QK
Correction factors fH for heating capacity QH (recirculating air tL1 = 20 °C)
Chilled water tempera-
ture
Air intake: tL1 [°C], ϕ1 [% r.h.]
Warm water tem-
perature
2-pipe system air intake: tL1 [°C]
4-pipe system Air air intake: tL1
[°C]
[°C] 32/40 30/40 27/46 26/50 24/50 [°C] +10 +15 +20 +10 +15 +20
6/12 1.40 1.19 1.00 0.97 0.76 90/70 1.84 1.71 1.57 1.86 1.73 1.59 7/13 1.39 1.17 0.98 0.96 0.75 80/60 1.56 1.43 1.29 1.57 1.43 1.30 8/12 1.37 1.15 0.97 0.94 0.73 70/55 1.37 1.24 1.10 1.38 1.24 1.11 8/14 1.20 1.00 0.81 0.78 0.57 70/50 1.28 1.14 1.00 1.28 1.14 1.00 10/15 1.08 0.88 0.71 0.67 0.49 60/50 1.19 1.05 0.91 1.19 1.06 0.92 12/16 0.96 0.77 0.60 0.56 0.44 60/40 0.99 0.85 0.70 0.98 0.84 0.70
12/18 0.82 0.66 0.50 0.44 – 50/40 0.90 0.77 0.63 0.91 0.77 0.63
14/18 0.77 0.65 0.49 0.44 0.34 40/30 0.62 0.48 0.34 0.62 0.48 0.33
3) All indicated correction factors are arithmetically calculated for different unit configurations and are to be used for only approximate estimation of performance data with other parameters. Exact data and other parameters can be obtained from our staff.
4) Maximum figure based on EUROVENT 0 tolerance standard
• •
Fan Coil Unit Components GEA MPower-Geko Fan Coil Unit
Fig. 1: Unit components (depending on unit model)
Pos. 1: Basic casing Pos. 2: Fixing bracket Pos. 3: Heat exchanger Pos. 4: Fan
Pos. 5: Condensate tray Pos. 6: Condensate pump
Pos. 7: Service panel Pos. 8: Filter cover Pos. 9: Filter element Pos. 10: Electric switch box Pos. 11: Contact protection
GEA participates in the EUROVENT certification programme.
The certified products are accordingly listed by the EUROVENT.
GEA MPower-Geko Fan Coil Unit Unit Selection
Unit Description 4
Recirculat- ing air
Cooling and
Heating
4-Pipe Chilled and Warm Water 6
Cooling or
Heating
2-Pipe Chilled or Warm Water 8
Heating
2-Pipe Warm Water 10
Cooling
2-Pipe Chilled Warm Water 12
Technical Data, Dimensions and Specification of
Accessories 14
Valves 33
GEA MATRIX Control System/Thermostat Switches 38
4 Rohrreihen Kühlen, 2-Leiter-System
5060701009080 200150 450400350300250 900800700600500 10001500 0,5 3,5 3,0 2,5 2,0 1,5 1,0 0,9 0,8 0,7 0,6 8,0 7,0 6,0 5,0 4,5 4,0 15 109,0 25 20
30 DruckverlustDp [kPa] 2000
654
7 1
2 3
Druckverluste im Wärmetauscher
GEA Top-Geko • ˜nderungen vorbehalten • Stand 08/00 (D) 25 Abb. 25.3
Wasservolumenstrom VW [l/h]
Unit Description GEA MPower-Geko Fan Coil Unit
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
Basic unit Basic units as modular and
compact models Heating/cooling/filtering/
with 2/4-pipe system. Ceiling mounting, single skin panel construction made of galvanized sheet steel with internal acoustic and thermal insulation (electrical and valve equipment depending on functions and requirements).
Basic unit + sound attenuator + intake plenum Compact basic unit with air
intake sound attenuator and air intake box, acoustic and thermal insulation of inner panels
Thermoelectric valves Modulating valves Valves
2 and 3-way valves with actuators for
2-point, 230/24 V~ 50/60 Hz 3-point, 230/24 V~ 50/60 Hz continuous 24 V~,
control signal 0-10 V
mounted and wired by factory
Electric equipment Electric equipment
Terminal box
Steel sheet electrical control box (depending on unit model, function and requirements)
MATRIX Control System
Speed and thermostat switches Control systems
according to unit model, valves, internal and external electronic components
GEA MPower-Geko Fan Coil Unit Unit Description
Fig. 7
Fig. 8
Fig. 9
Fig. 10
Heat exchanger for warm/chilled water (2-pipe system)
Heat exchanger for warm/chilled water (4-pipe system)
Copper pipes with drawn aluminium fins, supplied with ½"
connection, internal thread, air vent and drain screws
max. inlet temperature 90 °C max. operating pressure 16 bar
Centrifugal fan 230 V~ 50/60 Hz Centrifugal fan with low noise
maintenance-free sleeve bearings, high pressure stability, protection type IP00, insulation class B
Type and fan number depend on unit size and selection
Condensate pump (optional) Filter As an option, forming
condensate can be drained using a condensate pump. High operational safety through contact-free sensors.
Regenerative filter hose on clip-on frame, filter quality G2 (EN 779) or G3 (EN 779)
Fixing and connecting bracket Fixing and connecting bracket
provides different possibilities for ceiling mounting and connecting the unit and its add-on modules.
Recirculating Air Unit Heating and Cooling GEA MPower-Geko Fan Coil Unit 4-Pipe Chilled and Warm Water
Sizes 1 to 4
Design Speed stages Air flow rate**
Capacity stage 1 Capacity stage 2
Sound power air intake** Sound power air discharge** Sound power casing** Size
Cooling capacity Pressure drop Heating capacity Pressure drop Cooling capacity Pressure drop Heating capacity Pressure drop
QK ΔpK QH ΔpH QK ΔpK QH ΔpH
[m3/h] kW kPa kW kPa kW kPa kW kPa dB(A) dB(A) dB(A)
Modular (G)
1 515 3.1 17.9 2.8 2.0 3.0 7.1 3.7 4.3 40 41 29
1
Terminal box (select sheet steel electric switch box with GEA MATRIX)
2 685 3.7 25.6 3.3 2.6 3.6 10.0 4.3 5.7 44 46 34
3 915 4.4 34.9 3.8 3.4 4.3 13.9 5.1 7.5 52 54 41
4 1080 4.8 40.9 4.0 3.8 4.8 16.6 5.5 8.7 56 58 45
5 1215 5.0* 41.9 4.3 4.2 5.1 18.7 5.8 9.7 58 62 48
1 685 4.4 43.9 4.1 5.4 4.4 18.3 5.2 10.8 42 45 32
2
2 930 5.2* 53.7 4.8 7.1 5.4 26.5 6.3 15.1 50 53 40
3 1115 5.6* 53.7 5.3 8.5 6.0 32.5 6.9 17.8 54 58 44
4 1295 6.0* 53.6 5.7 9.6 6.6 38.6 7.5 20.8 58 62 48
5 1555 6.4* 53.6 6.2 11.2 7.3 46.9 8.1* 23.2 63 67 53 Speed combination
1 815 5.3 26.3 5.2 10.3 4.9 4.6 6.2 4.3 38 38 27
3
A 1-2-3
2 1150 6.7 40.3 6.3 14.5 6.3 7.2 7.7 6.4 44 45 33 B 2-3-4
3 1380 7.4* 47.5 6.9 17.2 7.1 9.0 8.5 7.8 48 49 37 C 3-4-5
4 1670 8.0* 47.5 7.7 20.6 8.0 11.0 9.4 9.3 52 54 42 E 1-3-5
5 2020 8.6* 47.4 8.2* 22.2 8.9 13.6 10.4 11.2 57 60 47 H 1-2-3-4-5
1 1000 6.4 40.1 6.2 15.6 6.1 7.3 7.5 6.5 40 43 30
4
2 1380 7.7* 51.5 7.4 21.2 7.6 10.8 9.0 9.2 47 50 37
3 1730 8.5* 51.4 8.2* 24.5 8.7 14.1 10.3 11.7 52 55 42
Sheet steel electric switch box with terminal strip or for integrated control
4 2065 9.1* 51.3 8.6* 24.5 9.7 17.0 11.2 13.7 57 60 47
5 2460 9.7* 51.3 9.2* 24.6 10.7 20.4 12.2 16.3 62 64 51
Compact (M)
1 515 3.1 17.9 2.8 2.0 3.0 7.1 3.7 4.3 40 41 29
1
2 680 3.7 25.3 3.2 2.6 3.6 10.0 4.3 5.7 44 46 34
3 905 4.4 34.5 3.7 3.3 4.3 14.0 5.0 7.4 52 54 41
4 1065 4.8 40.4 4.0 3.8 4.7 16.3 5.5 8.6 56 58 45
5 1190 5.0* 41.9 4.2 4.2 5.0 18.3 5.8 9.5 58 62 48
1 685 4.4 43.9 4.1 5.4 4.4 18.3 5.2 10.8 42 45 32
2
2 925 5.2* 53.7 4.8 7.1 5.4 26.4 6.3 15.0 50 53 40 Speed combination
3 1105 5.6* 53.7 5.3 8.4 6.0 32.7 6.9 17.7 54 58 44 K 1-2-3
4 1275 5.9* 53.6 5.6 9.4 6.5 37.7 7.4 20.4 58 62 48 L 2-3-4
5 1515 6.3* 53.6 6.1 11.0 7.2 45.5 8.0* 23.2 63 67 53 M 3-4-5
1 805 5.2 25.9 5.2 10.2 4.9 4.5 6.2 4.3 38 38 27
3
O 1-3-5
2 1135 6.6 39.6 6.2 14.3 6.2 7.0 7.6 6.3 44 45 33 R 1-2-3-4-5
3 1360 7.4* 47.6 6.9 17.0 7.0 8.8 8.4 7.6 48 49 37
4 1635 8.0* 47.5 7.6 20.2 8.0 11.0 9.4 9.3 52 54 42
5 1965 8.6* 47.4 8.1* 22.2 8.8 13.2 10.2 11.0 57 60 47
1 1000 6.4 40.1 6.2 15.6 6.1 7.2 7.5 6.5 40 43 30
4
2 1365 7.7* 51.5 7.3 20.9 7.5 10.7 9.0 9.1 47 50 37
3 1700 8.5* 51.4 8.2* 24.5 8.6 13.8 10.2 11.5 52 55 42
4 2015 9.0* 51.3 8.6* 24.5 9.6 16.8 11.1 13.4 57 60 47
5 2375 9.6* 51.3 9.0* 24.5 10.5 19.6 12.0 15.7 62 64 51
1 2
Capacity stage
Medium connection - front connection
side, facing discharge Ceiling left 3
right 4
Condensate line with drainage 0
with condensate pump *** 1
• • • •
G M • U W W .
Order code Data apply to basic units with filter class G2, without accessories and external pressure. Refer to table on page 24 for other operating points.
* Capacity at max. allowed medium flow rate
** Air flow rates and sound data for capacity stage 1
*** sheet steel electrical control box necessary
Filter G2 mat filter 2 G3 mat filter 3
Motor thermal contact
5-speed motor
Integrated
TC 0
External TC 1 WWP 70/50 °C
tL1 = +20 °C CWP 6/12 °C
tL1 = +27 °C ϕ1 = 46 % r.h.
GEA MPower-Geko Fan Coil Unit Accessories/Valves Recirculating Air Unit Heating and Cooling 4-Pipe Chilled and Warm Water, Sizes 1 to 4 Accessories
Spare filter hoses
Filter class G2 8 2 3
Filter class G3 8 3 3
Box with round connector
Air intake 0 4 1 Air dis-
charge** 0 4 2 Cover cap for round connector DN200 (irrespective of size) *
Air intake 7 1 1
Air discharge 7 1 2
Contact protection Air intake 5 1 1
Flexible dis- charge connector
Air intake 1 1 1
Air discharge** 1 1 2
Sound attenua- tion module
Air intake 2 1 1
Air discharge** 2 1 2
Suspension rail (irrespective of size) *
950 mm 6 1 3
1550 mm 6 2 3
2150 mm 6 3 3
** Only for basic units in modular configuration
Sizes 1 to 4
* 0, if irrespective of size
Z G M • A
Order code
MATRIX 500 MATRIX 2000 MATRIX 3000/4000 Terminal box
Actuator Operating voltage/circuit
• • • • 2-point open/
close
230 V AC2) T
• • • 24 V AC1), 2) Q
• •
3-point open/
stop/
close
230 V AC R
24 V AC1) N
230 V AC + 2 contacts C
• continu-ous 0/2 ... 10 V = 24 V AC1) S
V G M • •
Order code
Cooling circuit Heating circuit 1) 24 V-transformer to be provided by
others
2) kvs-values for open/close actuators (T,Q) only kvs 1,6 and 4,0 possible
Connection/shut-off
Inlet/outlet with external thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/outlet + shut-off valve with external
thread 4
Inlet + ball trap/outlet + shut-off valve with solder
fitting 5
Medium connection
left L
right R
kvs-values Cooling/Heating
0.25 ≡ 03
0.40 ≡ 04
0.63 ≡ 06
1.00 ≡ 10
1,602) ≡ 16
2.50 ≡ 25
4,002) ≡ 40
Heating circuit
Cooling circuit
2 3
Valves
Recirculating Air Unit Heating or Cooling GEA MPower-Geko Fan Coil Unit 2-Pipe Chilled or Warm Water
Sizes 1 to 4
Design Speed stages Air flow rate**
Capacity stage 1 Capacity stage 2
Sound power air intake** Sound power air discharge** Sound power casing** Size
Cooling capacity Pressure drop Heating capacity Pressure drop Cooling capacity Pressure drop Heating capacity Pressure drop
QK ΔpK QH ΔpH QK ΔpK QH ΔpH
[m3/h] kW kPa kW kPa kW kPa kW kPa dB(A) dB(A) dB(A)
Modular (G)
1 515 3.0 7.1 5.5 2.0 3.4 5.2 5.9 1.3 40 41 29
1
Terminal box (select sheet steel electric switch box with GEA MATRIX)
2 685 3.6 10.1 6.7 2.9 4.2 7.6 7.4 2.1 44 46 34
3 915 4.4 14.1 8.2 4.2 5.1 11.1 9.3 3.1 52 54 41
4 1080 4.8 16.9 9.2 5.2 5.6 13.2 10.4 3.9 56 58 45
5 1215 5.2 19.2 10.0 6.1 6.1 15.2 11.2 4.5 58 62 48
1 685 4.4 18.3 7.6 4.7 4.9 13.2 8.2 3.2 42 45 32
2
2 930 5.4 26.7 9.6 7.2 6.1 19.9 10.4 5.0 50 53 40
3 1115 6.0 32.8 10.9 9.1 7.0 25.3 12.0 6.4 54 58 44
4 1295 6.6 38.9 12.0 10.9 7.7 30.2 13.5 8.0 58 62 48
5 1555 7.3* 46.7 13.6 13.7 8.7 37.5 15.5 10.2 63 67 53 Speed combination
1 815 5.0 4.6 8.8 1.3 5.4 3.2 9.5 0.8 38 38 27
3
A 1-2-3
2 1150 6.3 7.2 11.6 2.1 7.1 5.3 12.8 1.5 44 45 33 B 2-3-4
3 1380 7.2 9.1 13.2 2.6 8.2 6.8 14.7 1.9 48 49 37 C 3-4-5
4 1670 8.0 11.2 15.1 3.4 9.4 8.8 17.1 2.5 52 54 42 E 1-3-5
5 2020 9.0 13.8 17.2 4.3 10.5 10.8 19.5 3.2 57 60 47 H 1-2-3-4-5
1 1000 6.1 7.3 10.8 1.9 6.7 5.1 11.8 1.3 40 43 30
4
2 1380 7.6 10.9 13.8 3.1 8.7 8.2 15.3 2.2 47 50 37
3 1730 8.8 14.3 16.2 4.1 10.1 10.9 18.1 3.0 52 55 42
Sheet steel electric switch box with terminal strip or for integrated control
4 2065 9.7 17.2 18.3 5.2 11.4 13.6 20.7 3.8 57 60 47
5 2460 10.8 20.8 20.7 6.5 12.7 16.4 23.4 4.8 62 64 51
Compact (M)
1 515 3.0 7.1 5.5 2.0 3.4 5.2 5.9 1.3 40 41 29
1
2 680 3.6 10.0 6.7 2.9 4.2 7.6 7.4 2.1 44 46 34
3 905 4.3 13.9 8.1 4.2 5.1 10.9 9.2 3.1 52 54 41
4 1065 4.8 16.6 9.0 5.1 5.6 13.0 10.3 3.8 56 58 45
5 1190 5.1 18.7 9.8 5.9 6.0 14.8 11.1 4.4 58 62 48
1 685 4.4 18.3 7.6 4.7 4.9 13.2 8.2 3.2 42 45 32
2
2 925 5.4 26.5 9.6 7.1 6.2 20.1 10.4 4.9 50 53 40 Speed combination
3 1105 6.0 32.5 10.8 9.0 6.9 25.0 12.0 6.4 54 58 44 K 1-2-3
4 1275 6.6 38.2 11.9 10.7 7.6 29.5 13.3 7.8 58 62 48 L 2-3-4
5 1515 7.3 46.4 13.4 13.3 8.5 36.3 15.2 9.9 63 67 53 M 3-4-5
1 805 4.9 4.5 8.8 1.2 5.4 3.1 9.4 0.8 38 38 27
3
O 1-3-5
2 1135 6.3 7.1 11.5 2.0 7.0 5.2 12.6 1.4 44 45 33 R 1-2-3-4-5
3 1360 7.1 8.9 13.1 2.6 8.1 6.7 14.5 1.8 48 49 37
4 1635 8.0 11.1 14.9 3.3 9.2 8.6 16.9 2.4 52 54 42
5 1965 8.9 13.4 16.8 4.1 10.3 10.5 19.1 3.1 57 60 47
1 1000 6.1 7.3 10.8 1.9 6.7 5.2 11.6 1.3 40 43 30
4
2 1365 7.5 10.7 13.7 3.0 8.6 8.1 15.1 2.1 47 50 37
3 1700 8.7 14.0 16.0 4.0 10.0 10.6 17.9 2.9 52 55 42
4 2015 9.7 17.1 18.0 5.0 11.3 13.2 20.4 3.7 57 60 47
5 2375 10.6 20.1 20.1 6.1 12.4 15.7 22.8 4.5 62 64 51
1 2
Capacity stage
Medium connection - front connection
side, facing discharge Ceiling left 3
right 4
Condensate line with drainage 0
with condensate pump *** 1
• • • •
G M . U W C .
Order code Data apply to basic units with filter class G2, without accessories and external pressure. Refer to table on page 24 for other operating points.
* Capacity at max. allowed medium flow rate
** Air flow rates and sound data for capacity stage 1
*** Sheet steel electrical control box necessary
Filter G2 mat filter 2 G3 mat filter 3
Motor thermal contact
5-speed motor
Integrated
TC 0
External TC 1 WWP 70/50 °C
tL1 = +20 °C CWP 6/12 °C
tL1 = +27 °C ϕ1 = 46 % r.h.
GEA MPower-Geko Fan Coil Unit Accessories/Valves Recirculating Air Unit Heating or Cooling 2-Pipe Chilled or Warm Water, sizes 1 to 4 Accessories
Spare filter hoses
Filter class G2 8 2 3
Filter class G3 8 3 3
Box with round connector
Air intake 0 4 1 Air dis-
charge** 0 4 2 Cover cap for round connector DN200 (irrespective of size) *
Air intake 7 1 1
Air discharge 7 1 2
Contact protection Air intake 5 1 1
Flexible dis- charge connector
Air intake 1 1 1
Air discharge** 1 1 2
Sound attenua- tion module
Air intake 2 1 1
Air discharge** 2 1 2
Suspension rail (irrespective of size) *
950 mm 6 1 3
1550 mm 6 2 3
2150 mm 6 3 3
** Only for basic units in modular configuration
Sizes 1 to 4
* 0, if irrespective of size
Z G M • A
Order code
Valves
MATRIX 500 MATRIX 2000 MATRIX 3000/4000 Terminal box
Actuator Operating voltage/circuit
• • • • 2-point open/
close
230 V AC2) T
• • • 24 V AC1), 2) Q
〈 • •
3-point open/
stop/
close
230 V AC R
24 V AC1) N
230 V AC + 2 contacts C
• continu-ous 0/2 ... 10 V = 24 V AC1) S
V G M 〈 3 〈
Order code
Cooling/heating circuit 1) 24 V-transformer to be provided by
others
2) kvs-values for open/close actuators (T,Q) only kvs 1,6 and 4 possible
Connection/shut-off
Inlet/outlet with external thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/outlet + shut-off valve with external
thread 4
Inlet + ball trap/outlet + shut-off valve with solder
fitting 5
Medium connection
left L
right R
kvs-values Cooling/Heating
0.25 ≡ 03
0.40 ≡ 04
0.63 ≡ 06
1.00 ≡ 10
1,602) ≡ 16
2,50 ≡ 25
4.002) ≡ 40
Cooling/
heating cir- cuit
3
Recirculating Air Unit Heating GEA MPower-Geko Fan Coil Unit 2-Pipe Warm Water
Sizes 1 to 4
Design Speed stages Air flow rate**
Capacity stage 1 Capacity stage 2
Sound power air intake** Sound power air discharge** Sound power casing** Size
Cooling capacity Pressure drop Heating capacity Pressure drop Cooling capacity Pressure drop Heating capacity Pressure drop
QK ΔpK QH ΔpH QK ΔpK QH ΔpH
[m3/h] kW kPa kW kPa kW kPa kW kPa dB(A) dB(A) dB(A)
Modular (G)
1 515 – – 5.5 2.0 – – 5.9 1.3 40 41 29
1
Terminal box (select sheet steel electric switch box with GEA MATRIX)
2 685 – – 6.7 2.9 – – 7.4 2.1 44 46 34
3 915 – – 8.2 4.2 – – 9.3 3.1 52 54 41
4 1080 – – 9.2 5.2 – – 10.4 3.9 56 58 45
5 1215 – – 10.0 6.1 – – 11.2 4.5 58 62 48
1 685 – – 7.6 4.7 – – 8.2 3.2 42 45 32
2
2 930 – – 9.6 7.2 – – 10.4 5.0 50 53 40
3 1115 – – 10.9 9.1 – – 12.0 6.4 54 58 44
4 1295 – – 12.0 10.9 – – 13.5 8.0 58 62 48
5 1555 – – 13.6 13.7 – – 15.5 10.2 63 67 53 Speed combination
1 815 – – 8.8 1.3 – – 9.5 0.8 38 38 27
3
A 1-2-3
2 1150 – – 11.6 2.1 – – 12.8 1.5 44 45 33 B 2-3-4
3 1380 – – 13.2 2.6 – – 14.7 1.9 48 49 37 C 3-4-5
4 1670 – – 15.1 3.4 – – 17.1 2.5 52 54 42 E 1-3-5
5 2020 – – 17.2 4.3 – – 19.5 3.2 57 60 47 H 1-2-3-4-5
1 1000 – – 10.8 1.9 – – 11.8 1.3 40 43 30
4
2 1380 – – 13.8 3.1 – – 15.3 2.2 47 50 37
3 1730 – – 16.2 4.1 – – 18.1 3.0 52 55 42
Sheet steel electric switch box with terminal strip or for integrated control
4 2065 – – 18.3 5.2 – – 20.7 3.8 57 60 47
5 2460 – – 20.7 6.5 – – 23.4 4.8 62 64 51
Compact (M)
1 515 – – 5.5 2.0 – – 5.9 1.3 40 41 29
1
2 680 – – 6.7 2.9 – – 7.4 2.1 44 46 34
3 905 – – 8.1 4.2 – – 9.2 3.1 52 54 41
4 1065 – – 9.0 5.1 – – 10.3 3.8 56 58 45
5 1190 – – 9.8 5.9 – – 11.1 4.4 58 62 48
1 685 – – 7.6 4.7 – – 8.2 3.2 42 45 32
2
2 925 – – 9.6 7.1 – – 10.4 4.9 50 53 40 Speed combination
3 1105 – – 10.8 9.0 – – 12.0 6.4 54 58 44 K 1-2-3
4 1275 – – 11.9 10.7 – – 13.3 7.8 58 62 48 L 2-3-4
5 1515 – – 13.4 13.3 – – 15.2 9.9 63 67 53 M 3-4-5
1 805 – – 8.8 1.2 – – 9.4 0.8 38 38 27
3
O 1-3-5
2 1135 – – 11.5 2.0 – – 12.6 1.4 44 45 33 R 1-2-3-4-5
3 1360 – – 13.1 2.6 – – 14.5 1.8 48 49 37
4 1635 – – 14.9 3.3 – – 16.9 2.4 52 54 42
5 1965 – – 16.8 4.1 – – 19.1 3.1 57 60 47
1 1000 – – 10.8 1.9 – – 11.6 1.3 40 43 30
4
2 1365 – – 13.7 3.0 – – 15.1 2.1 47 50 37
3 1700 – – 16.0 4.0 – – 17.9 2.9 52 55 42
4 2015 – – 18.0 5.0 – – 20.4 3.7 57 60 47
5 2375 – – 20.1 6.1 – – 22.8 4.5 62 64 51
1 2
Capacity stage
Medium connection - front connection side, facing discharge Ceiling
left 3
right 4
• • • •
G M . U O W . 0
Order code Data apply to basic units with filter class G2, without accessories and external pressure. Refer to table on page 24 for other operating points.
* Capacity at max. allowed medium flow rate
** Air flow rates and sound data for capacity stage 1
Filter G2 mat filter 2 G3 mat filter 3
Motor thermal contact
5-speed motor
Integrated
TC 0
External TC 1 WWP 70/50 °C
tL1 = +20 °C