Air Treatment

GEA MPower - Geko

Fan Coil Units | Data & Facts

Effective use of air distribution and capacity

(2)

Table of Contents

GEA MPower-Geko Fan Coil Unit

2 PR-2009-0015-GB • Subject to modifications • Status 10/2009

Sizes ... 1.2

Fan Coil Unit Components ... 2

Unit Selection ... 3

Unit Description ... 4

Recirculating Air Unit Cooling and Heating ... 6

Accessories/Valves ... 7

Recirculating Air Unit Cooling and Heating ... 8

Accessories/Valves ... 9

Recirculating Air Unit Heating ... 10

Accessories/Valves ... 11

Recirculating Air Unit Heating ... 12

Accessories/Valves ... 13

Pressure Drop in Heat Exchanger, Warm and Chilled Water ... 14

Power and Current Consumption ... 15

Capacity Overview for Different Operating Points Size 1 ... 16

Overview of Acoustic Data for Different Operating Points, Size 1 ... 17

Capacity Overview for Different Operating Points Size 2 ... 18

Overview of Acoustic Data for Different Operating Points, Size 2 ... 19

Capacity Overview for Different Operating Points Size 3 ... 20

Overview of Acoustic Data for Different Operating Points, Size 3 ... 21

Capacity Overview for Different Operating Points Size 4 ... 22

Overview of Acoustic Data for Different Operating Points, Size 4 ... 23

Samples for Capacity Definition ... 24

Installation Samples ... 28

Dimensions of Basic Units ... 29

Dimensions of Accessories ... 31

Overview of Valves

Selection Tables... 33

Valve Actuators ... 34

Valve Bodies ... 35

Shut-off Valves ... 36

Ball Traps ... 37

Control via Thermostat / Speed Switches / Control by Others ... 38

Control System GEA MATRIX ... 40

Product Type Code ... 51

Copyright note

Disclosing, copying, distributing or taking any action in reliance on the contents of this document is strictly prohibited without express prior consent. Violations entail liability for any damages or other liability arising. All rights in relation to patents, utility patents or design patents are reserved.

(3)

Sizes GEA MPower-Geko Fan Coil Unit

1) Sound level measured at unit casing, modular unit, capacity stage 1, filter class G2, without external pressure, without accessories. For other acoustic data refer to „Sample for capacity definition“, page 24 to page 27.

2) Capacity data apply for input parameters: WWP 70/50°C, tL1 = +20 °C; CWP 6/12 °C, tL1 = 27 °C, 46 % r.h. With other input parameters the following correction factors for approximate estimation of performance data should be applied.

Correction factors 3)

Size Width Air volume flow Sound power level 1)

[mm] [m3/h] [dB(A)] [kW]

1 2 3 4

Heating capacity QH Cooling capacity QK

975 515-1215 29-48 2.8-11,2

3.0-6,1

1275 685-1555 32-53 4.1-15,5

4.4-8,7

1575 810-2020 27-47 5.2-19,5

4.0-10,5

1775 1000-2460 30-51 6.2-23,4

6.1-12,7

For calculating performance data according EUROVENT classification - the following correction factors can be used:

Cooling (2-pipe system): 1,01 Cooling (4-pipe system): 0,92 Heating (2-pipe system): 0,70 Heating (4-pipe system): 1,22 Sound power4): +3 dB

Correction factors fK for cooling capacity QK

Correction factors fH for heating capacity QH (recirculating air tL1 = 20 °C)

Chilled water tempera-

ture

Air intake: tL1 [°C], ϕ1 [% r.h.]

Warm water tem-

perature

2-pipe system air intake: tL1 [°C]

4-pipe system Air air intake: tL1

[°C]

[°C] 32/40 30/40 27/46 26/50 24/50 [°C] +10 +15 +20 +10 +15 +20

6/12 1.40 1.19 1.00 0.97 0.76 90/70 1.84 1.71 1.57 1.86 1.73 1.59 7/13 1.39 1.17 0.98 0.96 0.75 80/60 1.56 1.43 1.29 1.57 1.43 1.30 8/12 1.37 1.15 0.97 0.94 0.73 70/55 1.37 1.24 1.10 1.38 1.24 1.11 8/14 1.20 1.00 0.81 0.78 0.57 70/50 1.28 1.14 1.00 1.28 1.14 1.00 10/15 1.08 0.88 0.71 0.67 0.49 60/50 1.19 1.05 0.91 1.19 1.06 0.92 12/16 0.96 0.77 0.60 0.56 0.44 60/40 0.99 0.85 0.70 0.98 0.84 0.70

12/18 0.82 0.66 0.50 0.44 50/40 0.90 0.77 0.63 0.91 0.77 0.63

14/18 0.77 0.65 0.49 0.44 0.34 40/30 0.62 0.48 0.34 0.62 0.48 0.33

3) All indicated correction factors are arithmetically calculated for different unit configurations and are to be used for only approximate estimation of performance data with other parameters. Exact data and other parameters can be obtained from our staff.

4) Maximum figure based on EUROVENT 0 tolerance standard

(4)

Fan Coil Unit Components GEA MPower-Geko Fan Coil Unit

Fig. 1: Unit components (depending on unit model)

Pos. 1: Basic casing Pos. 2: Fixing bracket Pos. 3: Heat exchanger Pos. 4: Fan

Pos. 5: Condensate tray Pos. 6: Condensate pump

Pos. 7: Service panel Pos. 8: Filter cover Pos. 9: Filter element Pos. 10: Electric switch box Pos. 11: Contact protection

GEA participates in the EUROVENT certification programme.

The certified products are accordingly listed by the EUROVENT.

(5)

GEA MPower-Geko Fan Coil Unit Unit Selection

Unit Description 4

Recirculat- ing air

Cooling and

Heating

4-Pipe Chilled and Warm Water 6

Cooling or

Heating

2-Pipe Chilled or Warm Water 8

Heating

2-Pipe Warm Water 10

Cooling

2-Pipe Chilled Warm Water 12

Technical Data, Dimensions and Specification of

Accessories 14

Valves 33

GEA MATRIX Control System/Thermostat Switches 38

4 Rohrreihen Kühlen, 2-Leiter-System

5060701009080 200150 450400350300250 900800700600500 10001500 0,5 3,5 3,0 2,5 2,0 1,5 1,0 0,9 0,8 0,7 0,6 8,0 7,0 6,0 5,0 4,5 4,0 15 109,0 25 20

30 DruckverlustDp [kPa] 2000

654

7 1

2 3

Druckverluste im Wärmetauscher

GEA Top-Geko • ˜nderungen vorbehalten • Stand 08/00 (D) 25 Abb. 25.3

Wasservolumenstrom VW [l/h]

(6)

Unit Description GEA MPower-Geko Fan Coil Unit

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

Basic unit Basic units as modular and

compact models Heating/cooling/filtering/

with 2/4-pipe system. Ceiling mounting, single skin panel construction made of galvanized sheet steel with internal acoustic and thermal insulation (electrical and valve equipment depending on functions and requirements).

Basic unit + sound attenuator + intake plenum Compact basic unit with air

intake sound attenuator and air intake box, acoustic and thermal insulation of inner panels

Thermoelectric valves Modulating valves Valves

2 and 3-way valves with actuators for

2-point, 230/24 V~ 50/60 Hz 3-point, 230/24 V~ 50/60 Hz continuous 24 V~,

control signal 0-10 V

mounted and wired by factory

Electric equipment Electric equipment

Terminal box

Steel sheet electrical control box (depending on unit model, function and requirements)

MATRIX Control System

Speed and thermostat switches Control systems

according to unit model, valves, internal and external electronic components

(7)

GEA MPower-Geko Fan Coil Unit Unit Description

Fig. 7

Fig. 8

Fig. 9

Fig. 10

Heat exchanger for warm/chilled water (2-pipe system)

Heat exchanger for warm/chilled water (4-pipe system)

Copper pipes with drawn aluminium fins, supplied with ½"

connection, internal thread, air vent and drain screws

max. inlet temperature 90 °C max. operating pressure 16 bar

Centrifugal fan 230 V~ 50/60 Hz Centrifugal fan with low noise

maintenance-free sleeve bearings, high pressure stability, protection type IP00, insulation class B

Type and fan number depend on unit size and selection

Condensate pump (optional) Filter As an option, forming

condensate can be drained using a condensate pump. High operational safety through contact-free sensors.

Regenerative filter hose on clip-on frame, filter quality G2 (EN 779) or G3 (EN 779)

Fixing and connecting bracket Fixing and connecting bracket

provides different possibilities for ceiling mounting and connecting the unit and its add-on modules.

(8)

Recirculating Air Unit Heating and Cooling GEA MPower-Geko Fan Coil Unit 4-Pipe Chilled and Warm Water

Sizes 1 to 4

Design Speed stages Air flow rate**

Capacity stage 1 Capacity stage 2

Sound power air intake** Sound power air discharge** Sound power casing** Size

Cooling capacity Pressure drop Heating capacity Pressure drop Cooling capacity Pressure drop Heating capacity Pressure drop

QK ΔpK QH ΔpH QK ΔpK QH ΔpH

[m3/h] kW kPa kW kPa kW kPa kW kPa dB(A) dB(A) dB(A)

Modular (G)

1 515 3.1 17.9 2.8 2.0 3.0 7.1 3.7 4.3 40 41 29

1

Terminal box (select sheet steel electric switch box with GEA MATRIX)

2 685 3.7 25.6 3.3 2.6 3.6 10.0 4.3 5.7 44 46 34

3 915 4.4 34.9 3.8 3.4 4.3 13.9 5.1 7.5 52 54 41

4 1080 4.8 40.9 4.0 3.8 4.8 16.6 5.5 8.7 56 58 45

5 1215 5.0* 41.9 4.3 4.2 5.1 18.7 5.8 9.7 58 62 48

1 685 4.4 43.9 4.1 5.4 4.4 18.3 5.2 10.8 42 45 32

2

2 930 5.2* 53.7 4.8 7.1 5.4 26.5 6.3 15.1 50 53 40

3 1115 5.6* 53.7 5.3 8.5 6.0 32.5 6.9 17.8 54 58 44

4 1295 6.0* 53.6 5.7 9.6 6.6 38.6 7.5 20.8 58 62 48

5 1555 6.4* 53.6 6.2 11.2 7.3 46.9 8.1* 23.2 63 67 53 Speed combination

1 815 5.3 26.3 5.2 10.3 4.9 4.6 6.2 4.3 38 38 27

3

A 1-2-3

2 1150 6.7 40.3 6.3 14.5 6.3 7.2 7.7 6.4 44 45 33 B 2-3-4

3 1380 7.4* 47.5 6.9 17.2 7.1 9.0 8.5 7.8 48 49 37 C 3-4-5

4 1670 8.0* 47.5 7.7 20.6 8.0 11.0 9.4 9.3 52 54 42 E 1-3-5

5 2020 8.6* 47.4 8.2* 22.2 8.9 13.6 10.4 11.2 57 60 47 H 1-2-3-4-5

1 1000 6.4 40.1 6.2 15.6 6.1 7.3 7.5 6.5 40 43 30

4

2 1380 7.7* 51.5 7.4 21.2 7.6 10.8 9.0 9.2 47 50 37

3 1730 8.5* 51.4 8.2* 24.5 8.7 14.1 10.3 11.7 52 55 42

Sheet steel electric switch box with terminal strip or for integrated control

4 2065 9.1* 51.3 8.6* 24.5 9.7 17.0 11.2 13.7 57 60 47

5 2460 9.7* 51.3 9.2* 24.6 10.7 20.4 12.2 16.3 62 64 51

Compact (M)

1 515 3.1 17.9 2.8 2.0 3.0 7.1 3.7 4.3 40 41 29

1

2 680 3.7 25.3 3.2 2.6 3.6 10.0 4.3 5.7 44 46 34

3 905 4.4 34.5 3.7 3.3 4.3 14.0 5.0 7.4 52 54 41

4 1065 4.8 40.4 4.0 3.8 4.7 16.3 5.5 8.6 56 58 45

5 1190 5.0* 41.9 4.2 4.2 5.0 18.3 5.8 9.5 58 62 48

1 685 4.4 43.9 4.1 5.4 4.4 18.3 5.2 10.8 42 45 32

2

2 925 5.2* 53.7 4.8 7.1 5.4 26.4 6.3 15.0 50 53 40 Speed combination

3 1105 5.6* 53.7 5.3 8.4 6.0 32.7 6.9 17.7 54 58 44 K 1-2-3

4 1275 5.9* 53.6 5.6 9.4 6.5 37.7 7.4 20.4 58 62 48 L 2-3-4

5 1515 6.3* 53.6 6.1 11.0 7.2 45.5 8.0* 23.2 63 67 53 M 3-4-5

1 805 5.2 25.9 5.2 10.2 4.9 4.5 6.2 4.3 38 38 27

3

O 1-3-5

2 1135 6.6 39.6 6.2 14.3 6.2 7.0 7.6 6.3 44 45 33 R 1-2-3-4-5

3 1360 7.4* 47.6 6.9 17.0 7.0 8.8 8.4 7.6 48 49 37

4 1635 8.0* 47.5 7.6 20.2 8.0 11.0 9.4 9.3 52 54 42

5 1965 8.6* 47.4 8.1* 22.2 8.8 13.2 10.2 11.0 57 60 47

1 1000 6.4 40.1 6.2 15.6 6.1 7.2 7.5 6.5 40 43 30

4

2 1365 7.7* 51.5 7.3 20.9 7.5 10.7 9.0 9.1 47 50 37

3 1700 8.5* 51.4 8.2* 24.5 8.6 13.8 10.2 11.5 52 55 42

4 2015 9.0* 51.3 8.6* 24.5 9.6 16.8 11.1 13.4 57 60 47

5 2375 9.6* 51.3 9.0* 24.5 10.5 19.6 12.0 15.7 62 64 51

1 2

Capacity stage

Medium connection - front connection

side, facing discharge Ceiling left 3

right 4

Condensate line with drainage 0

with condensate pump *** 1

G M • U W W .

Order code Data apply to basic units with filter class G2, without accessories and external pressure. Refer to table on page 24 for other operating points.

* Capacity at max. allowed medium flow rate

** Air flow rates and sound data for capacity stage 1

*** sheet steel electrical control box necessary

Filter G2 mat filter 2 G3 mat filter 3

Motor thermal contact

5-speed motor

Integrated

TC 0

External TC 1 WWP 70/50 °C

tL1 = +20 °C CWP 6/12 °C

tL1 = +27 °C ϕ1 = 46 % r.h.

(9)

GEA MPower-Geko Fan Coil Unit Accessories/Valves Recirculating Air Unit Heating and Cooling 4-Pipe Chilled and Warm Water, Sizes 1 to 4 Accessories

Spare filter hoses

Filter class G2 8 2 3

Filter class G3 8 3 3

Box with round connector

Air intake 0 4 1 Air dis-

charge** 0 4 2 Cover cap for round connector DN200 (irrespective of size) *

Air intake 7 1 1

Air discharge 7 1 2

Contact protection Air intake 5 1 1

Flexible dis- charge connector

Air intake 1 1 1

Air discharge** 1 1 2

Sound attenua- tion module

Air intake 2 1 1

Air discharge** 2 1 2

Suspension rail (irrespective of size) *

950 mm 6 1 3

1550 mm 6 2 3

2150 mm 6 3 3

** Only for basic units in modular configuration

Sizes 1 to 4

* 0, if irrespective of size

Z G M A

Order code

MATRIX 500 MATRIX 2000 MATRIX 3000/4000 Terminal box

Actuator Operating voltage/circuit

2-point open/

close

230 V AC2) T

24 V AC1), 2) Q

3-point open/

stop/

close

230 V AC R

24 V AC1) N

230 V AC + 2 contacts C

continu-ous 0/2 ... 10 V = 24 V AC1) S

V G M

Order code

Cooling circuit Heating circuit 1) 24 V-transformer to be provided by

others

2) kvs-values for open/close actuators (T,Q) only kvs 1,6 and 4,0 possible

Connection/shut-off

Inlet/outlet with external thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/outlet + shut-off valve with external

thread 4

Inlet + ball trap/outlet + shut-off valve with solder

fitting 5

Medium connection

left L

right R

kvs-values Cooling/Heating

0.25 03

0.40 04

0.63 06

1.00 10

1,602) 16

2.50 25

4,002) 40

Heating circuit

Cooling circuit

2 3

Valves

(10)

Recirculating Air Unit Heating or Cooling GEA MPower-Geko Fan Coil Unit 2-Pipe Chilled or Warm Water

Sizes 1 to 4

Design Speed stages Air flow rate**

Capacity stage 1 Capacity stage 2

Sound power air intake** Sound power air discharge** Sound power casing** Size

Cooling capacity Pressure drop Heating capacity Pressure drop Cooling capacity Pressure drop Heating capacity Pressure drop

QK ΔpK QH ΔpH QK ΔpK QH ΔpH

[m3/h] kW kPa kW kPa kW kPa kW kPa dB(A) dB(A) dB(A)

Modular (G)

1 515 3.0 7.1 5.5 2.0 3.4 5.2 5.9 1.3 40 41 29

1

Terminal box (select sheet steel electric switch box with GEA MATRIX)

2 685 3.6 10.1 6.7 2.9 4.2 7.6 7.4 2.1 44 46 34

3 915 4.4 14.1 8.2 4.2 5.1 11.1 9.3 3.1 52 54 41

4 1080 4.8 16.9 9.2 5.2 5.6 13.2 10.4 3.9 56 58 45

5 1215 5.2 19.2 10.0 6.1 6.1 15.2 11.2 4.5 58 62 48

1 685 4.4 18.3 7.6 4.7 4.9 13.2 8.2 3.2 42 45 32

2

2 930 5.4 26.7 9.6 7.2 6.1 19.9 10.4 5.0 50 53 40

3 1115 6.0 32.8 10.9 9.1 7.0 25.3 12.0 6.4 54 58 44

4 1295 6.6 38.9 12.0 10.9 7.7 30.2 13.5 8.0 58 62 48

5 1555 7.3* 46.7 13.6 13.7 8.7 37.5 15.5 10.2 63 67 53 Speed combination

1 815 5.0 4.6 8.8 1.3 5.4 3.2 9.5 0.8 38 38 27

3

A 1-2-3

2 1150 6.3 7.2 11.6 2.1 7.1 5.3 12.8 1.5 44 45 33 B 2-3-4

3 1380 7.2 9.1 13.2 2.6 8.2 6.8 14.7 1.9 48 49 37 C 3-4-5

4 1670 8.0 11.2 15.1 3.4 9.4 8.8 17.1 2.5 52 54 42 E 1-3-5

5 2020 9.0 13.8 17.2 4.3 10.5 10.8 19.5 3.2 57 60 47 H 1-2-3-4-5

1 1000 6.1 7.3 10.8 1.9 6.7 5.1 11.8 1.3 40 43 30

4

2 1380 7.6 10.9 13.8 3.1 8.7 8.2 15.3 2.2 47 50 37

3 1730 8.8 14.3 16.2 4.1 10.1 10.9 18.1 3.0 52 55 42

Sheet steel electric switch box with terminal strip or for integrated control

4 2065 9.7 17.2 18.3 5.2 11.4 13.6 20.7 3.8 57 60 47

5 2460 10.8 20.8 20.7 6.5 12.7 16.4 23.4 4.8 62 64 51

Compact (M)

1 515 3.0 7.1 5.5 2.0 3.4 5.2 5.9 1.3 40 41 29

1

2 680 3.6 10.0 6.7 2.9 4.2 7.6 7.4 2.1 44 46 34

3 905 4.3 13.9 8.1 4.2 5.1 10.9 9.2 3.1 52 54 41

4 1065 4.8 16.6 9.0 5.1 5.6 13.0 10.3 3.8 56 58 45

5 1190 5.1 18.7 9.8 5.9 6.0 14.8 11.1 4.4 58 62 48

1 685 4.4 18.3 7.6 4.7 4.9 13.2 8.2 3.2 42 45 32

2

2 925 5.4 26.5 9.6 7.1 6.2 20.1 10.4 4.9 50 53 40 Speed combination

3 1105 6.0 32.5 10.8 9.0 6.9 25.0 12.0 6.4 54 58 44 K 1-2-3

4 1275 6.6 38.2 11.9 10.7 7.6 29.5 13.3 7.8 58 62 48 L 2-3-4

5 1515 7.3 46.4 13.4 13.3 8.5 36.3 15.2 9.9 63 67 53 M 3-4-5

1 805 4.9 4.5 8.8 1.2 5.4 3.1 9.4 0.8 38 38 27

3

O 1-3-5

2 1135 6.3 7.1 11.5 2.0 7.0 5.2 12.6 1.4 44 45 33 R 1-2-3-4-5

3 1360 7.1 8.9 13.1 2.6 8.1 6.7 14.5 1.8 48 49 37

4 1635 8.0 11.1 14.9 3.3 9.2 8.6 16.9 2.4 52 54 42

5 1965 8.9 13.4 16.8 4.1 10.3 10.5 19.1 3.1 57 60 47

1 1000 6.1 7.3 10.8 1.9 6.7 5.2 11.6 1.3 40 43 30

4

2 1365 7.5 10.7 13.7 3.0 8.6 8.1 15.1 2.1 47 50 37

3 1700 8.7 14.0 16.0 4.0 10.0 10.6 17.9 2.9 52 55 42

4 2015 9.7 17.1 18.0 5.0 11.3 13.2 20.4 3.7 57 60 47

5 2375 10.6 20.1 20.1 6.1 12.4 15.7 22.8 4.5 62 64 51

1 2

Capacity stage

Medium connection - front connection

side, facing discharge Ceiling left 3

right 4

Condensate line with drainage 0

with condensate pump *** 1

G M . U W C .

Order code Data apply to basic units with filter class G2, without accessories and external pressure. Refer to table on page 24 for other operating points.

* Capacity at max. allowed medium flow rate

** Air flow rates and sound data for capacity stage 1

*** Sheet steel electrical control box necessary

Filter G2 mat filter 2 G3 mat filter 3

Motor thermal contact

5-speed motor

Integrated

TC 0

External TC 1 WWP 70/50 °C

tL1 = +20 °C CWP 6/12 °C

tL1 = +27 °C ϕ1 = 46 % r.h.

(11)

GEA MPower-Geko Fan Coil Unit Accessories/Valves Recirculating Air Unit Heating or Cooling 2-Pipe Chilled or Warm Water, sizes 1 to 4 Accessories

Spare filter hoses

Filter class G2 8 2 3

Filter class G3 8 3 3

Box with round connector

Air intake 0 4 1 Air dis-

charge** 0 4 2 Cover cap for round connector DN200 (irrespective of size) *

Air intake 7 1 1

Air discharge 7 1 2

Contact protection Air intake 5 1 1

Flexible dis- charge connector

Air intake 1 1 1

Air discharge** 1 1 2

Sound attenua- tion module

Air intake 2 1 1

Air discharge** 2 1 2

Suspension rail (irrespective of size) *

950 mm 6 1 3

1550 mm 6 2 3

2150 mm 6 3 3

** Only for basic units in modular configuration

Sizes 1 to 4

* 0, if irrespective of size

Z G M A

Order code

Valves

MATRIX 500 MATRIX 2000 MATRIX 3000/4000 Terminal box

Actuator Operating voltage/circuit

2-point open/

close

230 V AC2) T

24 V AC1), 2) Q

3-point open/

stop/

close

230 V AC R

24 V AC1) N

230 V AC + 2 contacts C

continu-ous 0/2 ... 10 V = 24 V AC1) S

V G M 3

Order code

Cooling/heating circuit 1) 24 V-transformer to be provided by

others

2) kvs-values for open/close actuators (T,Q) only kvs 1,6 and 4 possible

Connection/shut-off

Inlet/outlet with external thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/outlet + shut-off valve with external

thread 4

Inlet + ball trap/outlet + shut-off valve with solder

fitting 5

Medium connection

left L

right R

kvs-values Cooling/Heating

0.25 03

0.40 04

0.63 06

1.00 10

1,602) 16

2,50 25

4.002) 40

Cooling/

heating cir- cuit

3

(12)

Recirculating Air Unit Heating GEA MPower-Geko Fan Coil Unit 2-Pipe Warm Water

Sizes 1 to 4

Design Speed stages Air flow rate**

Capacity stage 1 Capacity stage 2

Sound power air intake** Sound power air discharge** Sound power casing** Size

Cooling capacity Pressure drop Heating capacity Pressure drop Cooling capacity Pressure drop Heating capacity Pressure drop

QK ΔpK QH ΔpH QK ΔpK QH ΔpH

[m3/h] kW kPa kW kPa kW kPa kW kPa dB(A) dB(A) dB(A)

Modular (G)

1 515 5.5 2.0 5.9 1.3 40 41 29

1

Terminal box (select sheet steel electric switch box with GEA MATRIX)

2 685 6.7 2.9 7.4 2.1 44 46 34

3 915 8.2 4.2 9.3 3.1 52 54 41

4 1080 9.2 5.2 10.4 3.9 56 58 45

5 1215 10.0 6.1 11.2 4.5 58 62 48

1 685 7.6 4.7 8.2 3.2 42 45 32

2

2 930 9.6 7.2 10.4 5.0 50 53 40

3 1115 10.9 9.1 12.0 6.4 54 58 44

4 1295 12.0 10.9 13.5 8.0 58 62 48

5 1555 13.6 13.7 15.5 10.2 63 67 53 Speed combination

1 815 8.8 1.3 9.5 0.8 38 38 27

3

A 1-2-3

2 1150 11.6 2.1 12.8 1.5 44 45 33 B 2-3-4

3 1380 13.2 2.6 14.7 1.9 48 49 37 C 3-4-5

4 1670 15.1 3.4 17.1 2.5 52 54 42 E 1-3-5

5 2020 17.2 4.3 19.5 3.2 57 60 47 H 1-2-3-4-5

1 1000 10.8 1.9 11.8 1.3 40 43 30

4

2 1380 13.8 3.1 15.3 2.2 47 50 37

3 1730 16.2 4.1 18.1 3.0 52 55 42

Sheet steel electric switch box with terminal strip or for integrated control

4 2065 18.3 5.2 20.7 3.8 57 60 47

5 2460 20.7 6.5 23.4 4.8 62 64 51

Compact (M)

1 515 5.5 2.0 5.9 1.3 40 41 29

1

2 680 6.7 2.9 7.4 2.1 44 46 34

3 905 8.1 4.2 9.2 3.1 52 54 41

4 1065 9.0 5.1 10.3 3.8 56 58 45

5 1190 9.8 5.9 11.1 4.4 58 62 48

1 685 7.6 4.7 8.2 3.2 42 45 32

2

2 925 9.6 7.1 10.4 4.9 50 53 40 Speed combination

3 1105 10.8 9.0 12.0 6.4 54 58 44 K 1-2-3

4 1275 11.9 10.7 13.3 7.8 58 62 48 L 2-3-4

5 1515 13.4 13.3 15.2 9.9 63 67 53 M 3-4-5

1 805 8.8 1.2 9.4 0.8 38 38 27

3

O 1-3-5

2 1135 11.5 2.0 12.6 1.4 44 45 33 R 1-2-3-4-5

3 1360 13.1 2.6 14.5 1.8 48 49 37

4 1635 14.9 3.3 16.9 2.4 52 54 42

5 1965 16.8 4.1 19.1 3.1 57 60 47

1 1000 10.8 1.9 11.6 1.3 40 43 30

4

2 1365 13.7 3.0 15.1 2.1 47 50 37

3 1700 16.0 4.0 17.9 2.9 52 55 42

4 2015 18.0 5.0 20.4 3.7 57 60 47

5 2375 20.1 6.1 22.8 4.5 62 64 51

1 2

Capacity stage

Medium connection - front connection side, facing discharge Ceiling

left 3

right 4

G M . U O W . 0

Order code Data apply to basic units with filter class G2, without accessories and external pressure. Refer to table on page 24 for other operating points.

* Capacity at max. allowed medium flow rate

** Air flow rates and sound data for capacity stage 1

Filter G2 mat filter 2 G3 mat filter 3

Motor thermal contact

5-speed motor

Integrated

TC 0

External TC 1 WWP 70/50 °C

tL1 = +20 °C

Cytaty

Powiązane dokumenty

Studies of the wear processes of dies for aluminum profile extrusion. with prototyped nitrided

Zwracam także uwagę na to, że język suahili, jako język funkcyjny i język komunikacji ponadetnicznej w całej Afryce Wschodniej, charakteryzuje się wysokim stopniem przyswojenia

Plik pobrany ze strony https://www.Testy.EgzaminZawodowy.info.. Wi cej materia ów na

powieściowej stru k tu ry utworów autora Opowieści o braciach Turgieniew uzasadnia epicki charakter narracji, bieg zdarzeń fabularnych i historycznych, losy i

Due to the specificity of the hydraulic system forcing the serial flow though plate heat exchanger (space heating) and coils in the do- mestic hot water tank, it can be noticed

Assume a is increasing (the proof is similar provided a is decreasing)... The proof is

Nie bez racji historycy praw a tra k tu ją konflikt Kościoła z rządem w owym czasie jako casus zderzenia się nowego ze starym : ustroju o sil­ nej,

Due to the reasonable predictability of system load, intra-day calculations for unit commitment may be necessary only when unexpected, significant changes occur in generation