• Nie Znaleziono Wyników

FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-103-13-NURE

N/A
N/A
Protected

Academic year: 2021

Share "FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-103-13-NURE"

Copied!
11
0
0

Pełen tekst

(1)

FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-103-13-NURE

Cable bearing system and fireboxes BAKS with anchors HILTI and with cables business TECHNOKABEL S.A.

This is an electronic version of a classification report which was made as a copy of classification report officially issued in a paper form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e.

FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor.

FIRES 004/S2-20/12/2012-E-el

(2)

FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION IN ACCORDANCE WITH DIN 4102-12: 1998-11

FIRES-JR-103-13-NURE

FIRES 149/S-27/10/2009-E FIRES, s.r.o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk Notified Body No. 1396, Approved Body No. SK01, Member of EGOLF

Name of the product: Cable bearing system and fireboxes BAKS with anchors HILTI and with cables business TECHNOKABEL S.A.

Sponsor: BAKS Kazimierz Sielski, ul. Jagodne 5, 05 - 480 Karczew, Poland producer of cable bearing system

TECHNOKABEL S.A., Nasielska 55, 04 - 343 Warszawa, Poland producer of cables

Hilti Sp. z o.o., ul. Puławska 491, 02 – 844 Warszawa, Poland producer of anchors

Prepared by: FIRES, s.r.o.

Approved Body No. SK01 Osloboditeľov 282

059 35 Batizovce Slovak Republic Task No.: PR-13-0373 Date of issue: 26. 09. 2013

Reports: 7

Copy No.: 2

Distribution list:

Copy No. 1 FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic (electronic version)

Copy No. 2 BAKS Kazimierz Sielski, ul. Jagodne 5, 05 - 480 Karczew, Poland (electronic version)

Copy No. 3 TECHNOKABEL S.A., Nasielska 55, 04 - 343 Warszawa, Poland (electronic version)

Copy No. 4 Hilti Sp. z o.o., ul. Puławska 491, 02 – 844 Warszawa, Poland (electronic version) Copy No. 5 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland

Copy No. 6 TECHNOKABEL S.A., Nasielska 55, 04 - 343 Warszawa, Poland Copy No. 7 Hilti Sp. z o.o., ul. Puławska 491, 02 – 844 Warszawa, Poland

This expert judgement report consists of 10 pages and may only be used or reproduced in its entirety.

(3)

1. INTRODUCTION

This expert judgement report with classification defines the function in fire classification assigned to element „Cable bearing system and fireboxes BAKS with anchors HILTI and with cables business TECHNOKABEL S.A.” in accordance with the classes given in DIN 4102-12: 1998-11.

This test was carried out according to standard STN 92 0205: 2012 and meets requirements of DIN 4102-12: 1998-11. Basic deviation in process and carrying out of test between these standards is in measuring and in control of temperature in the test furnace. According to STN 92 0205: 2012, plate thermometers according to EN 1363-1 are used. According to DIN 4102-12: 1998-11, common thermocouples of construction which was used for this measurement till issue of EN 1363-1 are used.

Measurement by plate thermometers acc. to EN 1363-1 can be considered as stricter method of temperature control in test furnace in compare with thermocouples used till issue of EN 1363-1. Therefore, it is possible to use results of test according to STN 92 025: 2012 for classification of tested cables according to DIN 4102-12: 1998-11, but not conversely.

This expert judgement report defines field of application which is outside the field of direct application according test standard or outside the field of extended application according to relevant extended application standard. This expert judgement expresses the opinion of the FIRES and is based on the experience or internal rules of FIRES.

2. DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL

The product, Cable bearing system and fireboxes BAKS with anchors HILTI and with cables business TECHNOKABEL S.A., is defined as a cable bearing system for power and communication halogen free cables with circuit integrity maintenance.

2.2 PRODUCT DESCRIPTION

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays and fireboxes PMO 3 and PMO3B with accessories and anchors HILTI and power and communication halogen free cables of TECHNOKABEL S.A. company.

Cable trays

Cable trays type KCP/KCOP…H60 are made from steel sheet thickness 1,5 mm. Trays are jointed together by two junctions type LPP/LPOPH60N (from steel sheet thickness 1,5 mm) and by sheet type BL/BLO…N (from steel sheet thickness 1,0 mm) with screws type SGN M6x12.

Cable trays type KGJ/KGOJ…H60 are made from steel sheet thickness 0,9 mm. Trays are jointed together by screws type SGN M6x12.

Cable trays type KFJ…H60 are made from steel sheet thickness 0,9 mm. Trays are jointed together by integrated connectors and screws type SGN M6x12.

Trays are used as bearing system for the cables.

Cable mesh trays

Cable mesh trays type KDSZ…H60 are made from steel wire ∅ 4,5 mm. Mesh trays are jointed together by integrated connectors.

Cable mesh trays type KGS…H60 are made from steel wire ∅ 4,0 mm. Mesh trays are jointed together by junctions type USS/USSO.

Mesh trays are used as bearing system for the cables.

Cable ladders

Cable ladders type DUP/DUOP…H60 are made from steel sheet thickness 1,5 mm and spacing of transoms is 300 mm. Cable ladders are jointed together by two junctions (LDCH60N) on both sides an screws (SGN M8x14).

(4)

FIRES-JR-103-13-NURE

FIRES 149/S-27/10/2009-E Page: 3/10

Cable ladders type DGOP…H60 are made from steel sheet thickness 1,5 mm and spacing of transoms is 150 mm. Ladders are jointed together by two junction type LDC/LDOCH60N (from steel sheet thickness 1,5 mm) with screws type SGN M8x14.

Cable ladders are used as bearing system for the cables.

Consoles

Consoles type WPCW/WPCO are made from steel sheet thickness 2,0 mm and 6,0 mm.

Consoles are used to gripping brackets.

Brackets

Brackets type WMC/WMCO are made from steel sheet thickness 2,5 mm and 5 mm.

Brackets type WFML are made from steel sheet thickness 2,0 mm.

Brackets are used to gripping trays or ladders to ceiling or to wall.

Supports

Supports type CWP/CWOP are made from steel sheet thickness 1,5 mm.

Supports are used to gripping trays or ladders to the ceiling with threaded bar.

Fireboxes

Fireboxes PMO3 are made of steel sheets with thickness 1,0 mm and bottom part 1,25 mm. Fireboxes can be used for cross connection of cable – number of cables and conductors according to type. It can be used inside the buildings on the ceiling or wall.

Cables Power cables:

(N)HXH-J FE180 PH30/E30 4x1,5 RE (4x) (N)HXH-J FE180 PH30/E30 4x50 RM (4x) (N)HXH-J FE180 PH90/E90 4x1,5 RE (18x) (N)HXH-J FE180 PH90/E90 4x50 RM (18x) NHXH-J FE180 PH90/E90 4x1,5 RE (15x) NHXH-J FE180 PH90/E90 5x16 RM (1x) NHXH-J FE180 PH90/E90 4x50 RM (14x) NHXCH FE180 PH30/E30 4x1,5/1,5 RE (4x) NHXCH FE180 PH30/E30 4x50/25 RE (4x) NHXCH FE180 PH90/E90 4x1,5/1,5 RE (2x) NHXCH FE180 PH90/E90 4x50/25 RE (2x) NHXHRHX-J FE180 PH90/E90 4x1,5 RE (2x) NHXHRHX-J FE180 PH90/E90 4x50 RM (2x) Communication cables:

HTKSH PH90 1x2x0,8 mm (20x)

HTKSHekw PH90 1x2x0,8 mm (8x)

HDGs fe180 PH90/E30-E90 2x1 mm2 (19x)

The length of cables was 5,5 m and 4,0 m from that was exposed to fire.

More detailed information about construction of specimen is shown in the drawings which form an integral part of test report. Drawings were delivered by sponsor.

3. TEST REPORTS AND EXTENDED APPLICATION REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS AND EXTENDED APPLICATION REPORTS

No. Name of laboratory Name of sponsors Test report No. Date of the test Test method [1] FIRES, s.r.o.,

Batizovce, SR

BAKS Kazimierz Sielski Karczew,Poland

FIRES-FR-

160-13-AUNE 26. 09. 2013

STN 92 0205 ZP-27/2008 DIN 4102-12

(5)

3.2 TEST RESULTS

No./

Test method

Specimen

No. Cables Track

No.

Time to first failure / interruption of conductor

[1]

STN 92 0205 ZP-27/2008

DIN 4102- 12

1 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM

11

90 minutes no failure / interruption 2 2 cables (N)HXH-J FE180 PH30/E30 4x50 RM 90 minutes no failure / interruption 3 2 cables (N)HXH-J FE180 PH90/E90 4x1,5 RE 90 minutes no failure / interruption 4 2 cables (N)HXH-J FE180 PH30/E30 4x1,5 RE 90 minutes no failure / interruption 5 2 cables (N)HXH-J FE180 PH90/E90 4x1,5 RE

10

90 minutes no failure / interruption 6 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 81 minutes

7 2 cables NHXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 8 2 cables NHXH-J FE180 PH90/E90 4x1,5 RE 31 minutes

9 2 cables (N)HXH-J FE180 PH90/E90 4x1,5 RE

9

90 minutes no failure / interruption 10 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 11 2 cables NHXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 12 2 cables NHXH-J FE180 PH90/E90 4x1,5 RE 90 minutes no failure / interruption 13 cable NHXH-J FE180 PH90/E90 4x1,5 RE +

fireboxes PMO3

15

87 minutes

14 cable NHXH-J FE180 PH90/E90 5x16 RM +

fireboxes PMO3 79 minutes

15 2 cables NHXH-J FE180 PH90/E90 4x1,5 RE

14 90 minutes no failure / interruption 16 2 cables NHXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 17 2 cables (N)HXH-J FE180 PH90/E90 4x1,5 RE

8

90 minutes no failure / interruption 18 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 54 minutes

19 2 cables (N)HXH-J FE180 PH30/E30 4x50 RM 17 minutes

20 2 cables (N)HXH-J FE180 PH30/E30 4x1,5 RE 90 minutes no failure / interruption 21 2 cables NHXH-J FE180 PH90/E90 4x1,5 RE

7 90 minutes no failure / interruption 22 2 cables NHXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 23 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM

13a 90 minutes no failure / interruption 24 2 cables (N)HXH-J FE180 PH90/E90 4x1,5 RE 90 minutes no failure / interruption 25 2 cables (N)HXH-J FE180 PH90/E90 4x1,5 RE

13 90 minutes no failure / interruption 26 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 27 2 cables NHXCH FE180 PH30/E30 4x50/25 RM

12a 87 minutes

28 2 cables NHXCH FE180 PH90/E90 4x50/25 RM 90 minutes no failure / interruption 29 2 cables (N)HXH-J FE180 PH90/E90 4x1,5 RE

6

90 minutes no failure / interruption 30 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 31 2 cables NHXHRHX-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 32 2 cables NHXHRHX-J FE180 PH90/E90 4x1,5 RE 90 minutes no failure / interruption 33 2 cables NHXH-J FE180 PH90/E90 4x1,5 RE

4 90 minutes no failure / interruption 34 2 cables NHXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 35 2 cables NHXH-J FE180 PH90/E90 4x1,5 RE

3 90 minutes no failure / interruption 36 2 cables NHXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 37 2 cables (N)HXH-J FE180 PH90/E90 4x1,5 RE

2

80 minutes

38 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 39 2 cables NHXCH FE180 PH30/E30 4x50/25 RM 79 minutes

40 2 cables NHXCH FE180 PH30/E30 4x1,5/1,5 RE 87 minutes 41 2 cables (N)HXH-J FE180 PH90/E90 4x1,5 RE

1

90 minutes no failure / interruption 42 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 43 2 cables NHXH-J FE180 PH90/E90 4x50 RM 90 minutes no failure / interruption 44 2 cables NHXH-J FE180 PH90/E90 4x1,5 RE 90 minutes no failure / interruption

(6)

FIRES-JR-103-13-NURE

FIRES 149/S-27/10/2009-E Page: 5/10

No./

Test method

Specimen

No. Cables Track

No.

Time to first failure / interruption of conductor

[1]

STN 92 0205 ZP-27/2008

DIN 4102- 12

45 2 cables NHXCH FE180 PH90/E90 4x1,5/1,5 RE

12a 90 minutes no failure / interruption 46 2 cables NHXCH FE180 PH30/E30 4x1,5/1,5 RE 90 minutes no failure / interruption 52 2 cables HTKSH PH90 1x2x0,8 mm

11 74 minutes

53 2 cables HDGs FE180 PH90/E30-E90 2x1 mm2 90 minutes no failure / interruption 54 2 cables HDGs FE180 PH90/E30-E90 2x1 mm2

10 90 minutes no failure / interruption

55 2 cables HTKSH PH90 1x2x0,8 mm 76 minutes

56 2 cables HDGs FE180 PH90/E30-E90 2x1 mm2

9 90 minutes no failure / interruption 57 2 cables HTKSH PH90 1x2x0,8 mm 90 minutes no failure / interruption 58 cable HDGs FE180 PH90/E30-E90 2x1 mm2

+ fireboxes PMO3B 15 90 minutes no failure / interruption 59 2 cables HTKSH PH90 1x2x0,8 mm 14 87 minutes

60 2 cables HTKSH PH90 1x2x0,8 mm 8 57 minutes

61 2 cables HDGs FE180 PH90/E30-E90 2x1 mm2 7 90 minutes no failure / interruption 62 2 cables HDGs FE180 PH90/E30-E90 2x1 mm2

6

90 minutes no failure / interruption

63 2 cables HTKSHekw PH90 1x2x0,8 mm 71 minutes

64 2 cables HTKSH PH90 1x2x0,8 mm 69 minutes

65 2 cables HDGs FE180 PH90/E30-E90 2x1 mm2

5

90 minutes no failure / interruption 66 2 cables HTKSHekw PH90 1x2x0,8 mm 90 minutes no failure / interruption

67 2 cables HTKSH PH90 1x2x0,8 mm 46 minutes

68 2 cables HTKSH PH90 1x2x0,8 mm 2 30 minutes

69 2 cables HDGs FE180 PH90/E30-E90 2x1 mm2 1 90 minutes no failure / interruption 70 2 cables HDGs FE180 PH90/E30-E90 2x1 mm2

12a

90 minutes no failure / interruption 71 2 cables HTKSHekw PH90 1x2x0,8 mm 90 minutes no failure / interruption 72 2 cables HTKSH PH90 1x2x0,8 mm 90 minutes no failure / interruption 73 2 cables HDGs FE180 PH90/E30-E90 2x1 mm2

12

90 minutes no failure / interruption 74 2 cables HTKSHekw PH90 1x2x0,8 mm 90 minutes no failure / interruption 75 2 cables HTKSH PH90 1x2x0,8 mm 90 minutes no failure / interruption

The fire test was discontinued in 94th minute at the request of test sponsor.

Specimens S1 – S46 were tested by three-phase voltage supply 3 x 230/400V with bulbs 240V / 60 W.

Specimens S52 – S75 were tested by one-phase voltage supply 1 x 110V with LED diodes 3V /0,03W.

Circuit breakers with rating 3 A were used.

(7)

4. CLASSIFICATION AND FIELD OF APPLICATION 4.1 REFERENCE OF CLASSIFICATION

This classification has been carried out in accordance with clause 3.2 of DIN 4102 – 12:1998-11.

4.2 CLASSIFICATION ACCORDING TO DIN 4102-12: 1998-11

The product, Cable bearing system and fireboxes BAKS with anchors HILTI and with cables business TECHNOKABEL S.A. is classified according to the following combinations of performance parameters and classes as appropriate.

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

NHXH-J FE180 PH90/E90

NHXH-J FE180 PH90/E90 4x1,5 RE Cable trays

KGJ/KGOJ400H60/B-400 covered by cover PKL400 with connectors

ZPNH60. Consoles combined of horizontal support CWP/CWOP40H40/05 and

threaded rods PG M10 fixed to ceiling by anchors HKD M10x30 HILTI.

Loading 15kg.m-1. Consoles in spacing of 1500 mm.

Track No. 1.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

NHXH-J FE180 PH90/E90 4x50 RM E 90

(N)HXH-J FE180 PH90/E90

(N)HXH-J FE180 PH90/E90 4x1,5 RE E 90 n x ≥1,5 mm2

n ≥ 2 E 90

(N)HXH-J FE180 PH90/E90 4x50 RM E 90

HDGs FE180 PH90/E30-E90

HDGs FE180 PH90/E30-E90 2x1 mm2 E 90

n x ≥ 1,0 mm2 n ≥ 2 E 90 (N)HXH-J

FE180 PH90/E90

(N)HXH-J FE180 PH90/E90 4x1,5 RE

Cable ladders DUP/DUOP400H60/B-400.

Consoles combined of horizontal support CWP/CWOP40H40/05

and threaded rods PG M10 fixed to ceiling by anchors HKD M10x30 HILTI.

Loading 20kg.m-1. Consoles in spacing of 1500 mm.

Track No. 2.

E 60 n x ≥1,5 mm2 n ≥ 2 E 60

(N)HXH-J FE180 PH90/E90 4x50 RM E 90

NHXCH FE180 PH30/E30

NHXCH FE180 PH30/E30 4x1,5/1,5 RE E 60 n x ≥1,5 mm2

n ≥ 2 E 60

NHXCH FE180 PH30/E30 4x50/25 RM E 60

HTKSH

PH90 HTKSH PH90 1x2x0,8 mm E 30

n x 2 x ≥ 0,8 mm n ≥ 1 E 30

NHXH-J FE180 PH90/E90

NHXH-J FE180 PH90/E90 4x1,5 RE

Cable ladders DUP/DUOP200H60/B-200.

Horizontal supports CWP/CWOP40H40/05 fixed to steel profile (100 x 100 x 3) under

the ceiling by threaded rods PG M10 and horizontal supports.

Loading 10kg.m-1. Consoles in spacing of 1500 mm.

Track No. 3.

E 90

n x ≥1,5 mm2 n ≥ 2 E 90

NHXH-J FE180 PH90/E90 4x50 RM E 90

NHXH-J FE180 PH90/E90

NHXH-J FE180 PH90/E90 4x1,5 RE

Cable trays KGJ/KGOJ200H60/B-200.

Horizontal supports CWP/CWOP40H40/05 fixed to steel profile (100 x 100 x 3) under

the ceiling by threaded rods PG M10 and horizontal supports.

Loading 10kg.m-1. Consoles in spacing of 1500 mm.

Track No. 4.

E 90

n x ≥1,5 mm2 n ≥ 2 E 90

NHXH-J FE180 PH90/E90 4x50 RM E 90

HTKSH

PH90 HTKSH PH90 1x2x0,8 mm

Cable trays KGJ/KGOJ400H60/B-400.

Horizontal supports CWP/CWOP40H40/05 fixed to steel profile (100 x 100 x 3) under

the ceiling by threaded rods PG M10 and horizontal supports.

Loading 10kg.m-1. Consoles in spacing of 1500 mm.

Track No. 5.

E 30

n x 2 x ≥ 0,8 mm n ≥ 1 E 30 HTKSHekw

PH90 HTKSHekw PH90 1x2x0,8 mm E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGs

FE180 PH90/E30-E90

HDGs FE180 PH90/E30-E90 2x1 mm2 E 90

n x ≥ 1,0 mm2 n ≥ 2 E 90

(8)

FIRES-JR-103-13-NURE

FIRES 149/S-27/10/2009-E Page: 7/10

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

(N)HXH-J FE180 PH90/E90

(N)HXH-J FE180 PH90/E90 4x1,5 RE

Cable ladders DUP/DUOP400H60/B-400 covered by cover PDDJ with

connectors ZAP2.

Horizontal supports CWP/CWOP40H40/05 fixed to steel profile (100 x 100 x 3) under

the ceiling by threaded rods PG M10 and horizontal supports.

Loading 10kg.m-1. Consoles in spacing of 1500 mm.

Track No. 6.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

(N)HXH-J FE180 PH90/E90 4x50 RM E 90

NHXHRHX-J FE180 PH90/E90

NHXHRHX-J FE180 PH90/E90 4x1.5 RE E 90 n x ≥1,5 mm2

n ≥ 2 E 90

NHXHRHX-J FE180 PH90/E90 4x50 RM E 90

HTKSH

PH90 HTKSH PH90 1x2x0,8 mm E 60

n x 2 x ≥ 0,8 mm n ≥ 1 E 60 HTKSHekw

PH90 HTKSHekw PH90 1x2x0,8 mm E 60

n x 2 x ≥ 0,8 mm n ≥ 1 E 60 HDGs

FE180 PH90/E30-E90

HDGs FE180 PH90/E30-E90 2x1 mm2 E 90

n x ≥ 1,0 mm2 n ≥ 2 E 90 NHXH-J

FE180 PH90/E90

NHXH-J FE180 PH90/E90 4x1,5 RE Cable trays KFJ300H60/B-300. Brackets WFML400 and threaded rods

PG M8 fixed to ceiling by anchors HUS-I6 and

HUS-A6 HILTI.

Loading 10kg.m-1. Consoles in spacing of 1500 mm.

Track No. 7.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

NHXH-J FE180 PH90/E90 4x50 RM E 90

HDGs FE180 PH90/E30-E90

HDGs FE180 PH90/E30-E90 2x1 mm2 E 90

n x ≥ 1,0 mm2 n ≥ 2 E 90

(N)HXH-J FE180 PH90/E90

(N)HXH-J FE180 PH90/E90 4x1,5 RE

Cable mesh trays KDSZ400H60/B-400. Brackets

WFML400 and threaded rods PG M8 fixed to ceiling by

anchors HUS-I6 and HUS-A6 HILTI.

Loading 20kg.m-1. Consoles in spacing of 1500 mm.

Track No. 8.

E 90 n x ≥1,5 mm2 n ≥ 2 E 30

(N)HXH-J FE180 PH90/E90 4x50 RM E 30

(N)HXH-J FE180 PH30/E30

(N)HXH-J FE180 PH30/E30 4x1,5 RE E 90

Without classification

(N)HXH-J FE180 PH30/E30 4x50 RM Without

classification HTKSH

PH90 HTKSH PH90 1x2x0,8 mm E 30

n x 2 x ≥ 0,8 mm n ≥ 1 E 30 NHXH-J

FE180 PH90/E90

NHXH-J FE180 PH90/E90 4x1,5 RE

Cable trays KCP/KCOP400H60/B-400.

Consoles WPCW/WPCO1000 with brackets WMC/WMCO400

and threaded rods PG M10 through the holders UPW/UPWO fixed to ceiling by anchors HUS-I6

and HUS-A6 HILTI Loading 10 kg/m.

Consoles in spacing of 1200 mm.

Track No. 9.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

NHXH-J FE180 PH90/E90 4x50 RM E 90

(N)HXH-J FE180 PH90/E90

(N)HXH-J FE180 PH90/E90 4x1,5 RE E 90 n x ≥1,5 mm2

n ≥ 2 E 90

(N)HXH-J FE180 PH90/E90 4x50 RM E 90

HTKSH

PH90 HTKSH PH90 1x2x0,8 mm E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGs

FE180 PH90/E30-E90

HDGs FE180 PH90/E30-E90 2x1 mm2 E 90

n x ≥ 1,0 mm2 n ≥ 2 E 90

(9)

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

NHXH-J FE180 PH90/E90

NHXH-J FE180 PH90/E90 4x1,5 RE

Cable ladders DGOP400H60/B-400.

Consoles WPCW/WPCO1000 with brackets WMC/WMCO400 and threaded rods PG M10 through the holders UPW/UPWO fixed to ceiling by anchors HUS-I6

and HUS-A6 HILTI Loading 20 kg/m.

Consoles in spacing of 1200 mm.

Track No. 10.

E 30 n x ≥1,5 mm2 n ≥ 2 E 30

NHXH-J FE180 PH90/E90 4x50 RM E 90

(N)HXH-J FE180 PH90/E90

(N)HXH-J FE180 PH90/E90 4x1,5 RE E 90 n x ≥1,5 mm2

n ≥ 2 E 60

(N)HXH-J FE180 PH90/E90 4x50 RM E 60

HTKSH

PH90 HTKSH PH90 1x2x0,8 mm E 60

n x 2 x ≥ 0,8 mm n ≥ 1 E 60 HDGs

FE180 PH90/E30-E90

HDGs FE180 PH90/E30-E90 2x1 mm2 E 90

n x ≥ 1,0 mm2 n ≥ 2 E 90 (N)HXH-J

FE180 PH90/E90

(N)HXH-J FE180 PH90/E90 4x1,5 RE

Track is made of single cable clips UDF fixed to steel sheet 0,7 mm

thick placed on side wall of furnace. Clips fixed by screws

S-MD03PZ 4,8x16 HILTI in spacing of 600 mm.

Track No. 11.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

(N)HXH-J FE180 PH90/E90 4x50 RM E 90

(N)HXH-J FE180 PH30/E30

(N)HXH-J FE180 PH30/E30 4x1,5 RE E 90 n x ≥1,5 mm2

n ≥ 2 E 90

(N)HXH-J FE180 PH30/E30 4x50 RM E 90

HTKSH

PH90 HTKSH PH90 1x2x0,8 mm E 60

n x 2 x ≥ 0,8 mm n ≥ 1 E 60 HDGs

FE180 PH90/E30-E90

HDGs FE180 PH90/E30-E90 2x1 mm2 E 90

n x ≥ 1,0 mm2 n ≥ 2 E 90 HTKSH

PH90 HTKSH PH90 1x2x0,8 mm

Track is made of double cable clips X-DFB MX HILTI fixed to ceiling in spacing of 300 mm.

Track No. 12.

E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSHekw

PH90 HTKSHekw PH90 1x2x0,8 mm E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGs

FE180 PH90/E30-E90

HDGs FE180 PH90/E30-E90 2x1 mm2 E 90

n x ≥ 1,0 mm2 n ≥ 2 E 90 NHXCH

FE180 PH90/E90

NHXCH FE180 PH90/E90 4x1,5/1,5 RE

Track is made of single cable clips X-FB MX HILTI fixed to ceiling in

spacing of 300 mm.

Track No. 12a.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

NHXCH FE180 PH90/E90 4x50/25 RM E 90

NHXCH FE180 PH30/E30

NHXCH FE180 PH30/E30 4x1,5/1,5 RE E 90 n x ≥1,5 mm2

n ≥ 2 E 60

NHXCH FE180 PH30/E30 4x50/25 RM E 60

HTKSH

PH90 HTKSH PH90 1x2x0,8 mm E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSHekw

PH90 HTKSHekw PH90 1x2x0,8 mm E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGs

FE180 PH90/E30-E90

HDGs FE180 PH90/E30-E90 2x1 mm2 E 90

n x ≥ 1,0 mm2 n ≥ 2 E 90

(10)

FIRES-JR-103-13-NURE

FIRES 149/S-27/10/2009-E Page: 9/10

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

(N)HXH-J FE180 PH90/E90

(N)HXH-J FE180 PH90/E90 4x1,5 RE Track is made of single cable clips X-FB MX HILTI fixed to ceiling in

spacing of 600 mm.

Track No. 13.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

(N)HXH-J FE180 PH90/E90 4x50 RM E 90

(N)HXH-J FE180 PH90/E90

(N)HXH-J FE180 PH90/E90 4x1,5 RE Track is made of double cable clips X-DFB MX HILTI fixed to ceiling in spacing of 600 mm.

Track No. 13a.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

(N)HXH-J FE180 PH90/E90 4x50 RM E 90

NHXH-J FE180 PH90/E90

NHXH-J FE180 PH90/E90 4x50 RM

Cable mesh trays KGS100H60/B-100 fixed to ceiling

by holders WKS/WKSO60 and anchors HUS-P6 HILTI.

Loading 5kg.m-1. Fixing in spacing of 1500 mm.

Track tested without bending.

Track No. 14.

E 90

n x ≥1,5 - 50 mm2 n ≥ 2 E 90

NHXH-J FE180 PH90/E90 4x1,5 RE

Cable mesh trays KGS60H60/B-60 fixed to ceiling by

holders WKS/WKSO60 and anchors HUS-P6 HILTI.

Loading 0,6kg.m-1. Fixing in spacing of 1500 mm.

Track tested without bending.

Track No. 14.

E 90

HTKSH

PH90 HTKSH PH90 1x2x0,8 mm E 60

n x 2 x ≥ 0,8 mm n ≥ 1 E 60

NHXH-J FE180 PH90/E90

(N)HXH-J FE180 PH90/E90 4x1,5 RE +

fireboxes PMO3 Track is made of fireboxes type PMO3 fixed to ceiling by anchors HUS-P6 HILTI. Cables are fixed to

ceiling by single cable clips X-FB MX HILTI in spacing of 600 mm.

Track No. 15.

E 60 n x ≥1,5 - 16 mm2 n ≥ 2 E 60 (N)HXH-J FE180 PH90/E90 5x16 RM +

fireboxes PMO3 E 60

HDGs FE180 PH90/E30-E90

HDGs FE180 PH90/E30-E90 2x1 mm2 +

fireboxes PMO3 E 90

n x ≥ 1,0 mm2 n ≥ 2 E 90

4.3 FIELD OF APPLICATION

This classification is valid for the following end use applications:

§ throughout the period during which circuit integrity is to be maintained, neighbouring building components shall not have a negative effect on circuit integrity;

§ although testing is only carried out on cables arranged horizontally, test results also apply to cables arranged either diagonally or vertically (e.g. risers), as long as the cable system is supported in transitional areas (i.e. where it switches from a horizontal to a vertical arrangement) in such a manner that the cables will not slip or kink at corners;

§ test results of function in fire test of cables tested at standard supporting construction are also applicable for tested standard supporting construction of other producers;

§ test results of function in fire test of cables tested at standard supporting construction are also applicable for cables of other producers tested at standard supporting construction;

§ maximal length of increasing routing shall be 3500 mm with consistent horizontal placing of cable with minimal length of 300 mm (apart from cable bending) and with maximal spacing of clips of 300 mm, eventually the cables are stabilized by cable transmissions at floor or ceiling with particular fire resistance;

§ for vertical systems, the test results obtained for cables mounted singly on the ceiling using single clips apply. Brackets of proven suitability may also be used, as long as their spacing is equal to that of the single clips tested;

§ results of testing single cables on the ceiling apply also to cables mounted horizontally on walls;

§ results of testing bunched cables on a ladder or tray also apply to support construction attached to a wall. However, such constructions required proof of suitability by means of a test certificate or other document issued by an accredited testing laboratory.

(11)

5. LIMITATIONS

Load-bearing construction elements for fixing of cable systems must be proved for at least the same fire resistance compare to classified function in fire of cable system.

This classification document does not represent type approval or certification of the product.

The classification is valid until 26. 09. 2018 provided that the product, field of application and standards and regulations are not changed.

Approved: Signed:

Ing. Štefan Rástocký Bc. Dávid Šubert

leader of the testing laboratory technician of the testing laboratory

Cytaty

Powiązane dokumenty

§ test results of cables bunched on the ladder or in the tray are also applicable to supporting constructions fixed in the wall, while this construction was tested at the

The element, Power and communications cables TECHNOKABEL, type – NHXH, NHXCH, HTKSHekw and JE-H(St)H at cable bearing system BAKS - cable trays KCOP, cable

The element, Power and communications cables TECHNOKABEL, type – NHXH, NHXCH, HTKSH and HTKSHekw at cable bearing system BAKS - cable trays KCOP, cable ladders

The element, Power and communications cables TECHNOKABEL, type – NHXH, NHXCH, HTKSH, HTKSHekw and JE-H(St)H at cable bearing system BAKS - cable trays KCOD and

The element comprise of cable bearing system BAKS – cable trays KCOP, cable ladders DGOP, ceiling ledges SDOC with clips UKO1 and UKO2, clips UDF and UEF, cable holders

The element comprise of cable bearing system BAKS – cable trays KCOP, cable ladders DGOP, ceiling ledges SDOC with clips UKO1 and UKO2, clips UDF and UEF, and accessories

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable single clips KSA and fireboxes PMO3B with accessories, power

Product comprise of fireboxes of company W2 with accessories and cable bearing system BAKS Kazimierz Sielski company – cable trays, ladders, mesh trays with