• Nie Znaleziono Wyników

FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-116-13-NURE

N/A
N/A
Protected

Academic year: 2021

Share "FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-116-13-NURE"

Copied!
9
0
0

Pełen tekst

(1)

FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-116-13-NURE

Cable bearing system and fireboxes BAKS with cables business Tele-Fonika Kable sp. z o.o. S.K.A. at raised access floor

This is an electronic version of a classification report which was made as a copy of classification report officially issued in a paper form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e.

FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor.

FIRES 004/S2-20/12/2012-E-el

(2)

FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION IN ACCORDANCE WITH DIN 4102-12: 1998-11

FIRES-JR-116-13-NURE

Name of the product: Cable bearing system and fireboxes BAKS with cables business Tele-Fonika Kable sp. z o.o. S.K.A. at raised access floor

Sponsor: BAKS Kazimierz Sielski, ul. Jagodne 5, 05 - 480 Karczew, Poland producer of cable bearing system

Tele-Fonika Kable sp. z o.o. S.K.A., ul. Wielicka 114, 30-630 Kraków, Poland producer of cables

TIM-EX Sp. z o.o. S.K.A., ul. Rydygiera 8, 01-793 Warszawa, Poland supplier of floor

Prepared by: FIRES, s.r.o.

Approved Body No. SK01 Osloboditeľov 282

059 35 Batizovce Slovak Republic Task No.: PR-13-0427 Date of issue: 25. 10. 2013

Reports: 7

Copy No.: 2

Distribution list:

Copy No. 1 FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic (electronic version)

Copy No. 2 BAKS Kazimierz Sielski, ul. Jagodne 5, 05 - 480 Karczew, Poland (electronic version)

Copy No. 3 Tele-Fonika Kable sp. z o.o. S.K.A., ul. Wielicka 114, 30-630 Kraków, Poland (electronic version)

Copy No. 4 TIM-EX Sp. z o.o. S.K.A., ul. Rydygiera 8, 01-793 Warszawa, Poland (electronic version)

Copy No. 5 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland

Copy No. 6 Tele-Fonika Kable sp. z o.o. S.K.A., ul. Wielicka 114, 30-630 Kraków, Poland Copy No. 7 TIM-EX Sp. z o.o. S.K.A., ul. Rydygiera 8, 01-793 Warszawa, Poland

This expert judgement report consists of 8 pages and may only be used or reproduced in its entirety.

(3)

FIRES-JR-116-13-NURE

FIRES 149/S-27/10/2009-E Page: 2/8

1. INTRODUCTION

This expert judgement report with classification defines the function in fire classification assigned to element „ Cable bearing system and fireboxes BAKS with cables business Tele-Fonika Kable sp. z o.o.

S.K.A. at raised access floor” in accordance with the classes given in DIN 4102-12: 1998-11.

This test was carried out according to standard STN 92 0205: 2012 and meets requirements of DIN 4102-12: 1998-11. Basic deviation in process and carrying out of test between these standards is in measuring and in control of temperature in the test furnace. According to STN 92 0205: 2012, plate thermometers according to EN 1363-1 are used. According to DIN 4102-12: 1998-11, common thermocouples of construction which was used for this measurement till issue of EN 1363-1 are used.

Measurement by plate thermometers acc. to EN 1363-1 can be considered as stricter method of temperature control in test furnace in compare with thermocouples used till issue of EN 1363-1. Therefore, it is possible to use results of test according to STN 92 025: 2012 for classification of tested cables according to DIN 4102-12: 1998-11, but not conversely.

This expert judgement report defines field of application which is outside the field of direct application according test standard or outside the field of extended application according to relevant extended application standard. This expert judgement expresses the opinion of the FIRES and is based on the experience or internal rules of FIRES.

2. DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL

The product, Cable bearing system and fireboxes BAKS with cables business Tele-Fonika Kable sp. z o.o.

S.K.A. at raised access floor, is defined as a cable bearing system for power and communication halogen free cables with circuit integrity maintenance.

2.2 PRODUCT DESCRIPTION

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable single clips KSA and fireboxes PMO3B with accessories, power and communication halogen free cables of Tele-Fonika Kable sp. z o.o. S.K.A. company and components of raised access floor supplied by company TIM-EX Sp. z o.o. S.K.A..

Cable trays

Cable trays type KGJ/KGOJ…H60 are made from steel sheet thickness 0,9 mm. Trays are jointed together by screws type SGN M6x12. Trays are used as bearing system for the cables.

Cable mesh trays

Cable trays type KDS/KDSO…H60 are made from steel wire ∅ 4,5 mm. Mesh trays are jointed together by junctions type USS/USSO. Mesh trays are used as bearing system for the cables.

Cable ladders

Cable ladders type DUP/DUOP…H60 are made from steel sheet thickness 1,5 mm and spacing of transoms is 300 mm. Cable ladders are jointed together by two junctions (LDCH60N) on both sides an screws (SGN M8x14). Cable ladders are used as bearing system for the cables.

Consoles

Consoles type WPCW/WPCO are made from steel sheet thickness 2,0 mm and 6,0 mm.

Consoles are used to gripping brackets.

Brackets

Brackets type WMC/WMCO are made from steel sheet thickness 2,5 mm and 5 mm.

Brackets type WWS/WWSO are made from steel sheet thickness 2,0 mm.

Brackets type WFL/WFLO are made from steel sheet thickness 2,0 mm.

Brackets are used to gripping trays or ladders to ceiling or to wall.

(4)

Supports

Supports type CWP/CWOP are made from steel sheet thickness 1,5 mm.

Supports are used to gripping trays or ladders.

Fireboxes

Fireboxes PMO3B are made of steel sheets with thickness 1,0 mm and bottom part 1,25 mm and includes current-limiting fuse. Fireboxes can be used for cross connection of cable – number of cables and conductors according to type. It can be used inside the buildings on the ceiling or wall.

Cable clips

Clips KSA are made from steel sheet thickness 1,2 mm. Clips are used to gripping cables to ceiling or to wall.

Raised access floor

Raised access floor is made of steel pedestals S235JRH/P235TR2 (∅ 33,7 mm, thickness 6,3 mm) and (∅ 24,0 mm, thickness 2,0 mm) (manufacturer: PPHU Urszula Pacek, Poland) glued to aerated concreted blocks by glue Helmipur SH 300 (manufacturer: Forbo Helmitin GmbH) and fixed by screws in spacing of 600 mm. Pedestals (∅ 24,0 mm, thickness 2,0 mm) are fixed together by horizontal supports (CWP/CWOP40H40/07) and hangers (OBR25, ∅25 mm). Pedestals are joined to each other by steel traverses (40 x 40 x 2) mm. Traverses are fixed to pedestals by steel screws (M8x30). Panels EHB 36/600 (manufacturer: Knauf Integral KG AM, Germany) with dimensions (600 x 600 x 36) mm. Plenum height is 1000 mm.

Cables Power cables:

(N)HXH-J FE/180/E90 4x1,5RE 0,6/1 kV (16x) (N)HXH-O FE180/E90 4x50RM 0,6/1 kV (16x) (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV (17x) (N)HXCH-O FE180/E90 4x16RE/16 0,6/1 kV (1x) (N)HXCH-O FE180/E90 4x50RM/25 0,6/1 kV (16x) Communication cables:

JE-H(St)H Bd 2x2x0,8 FE180/E90 (17x)

The length of cables was 4,5 m and 3,2 m from that was exposed to fire.

More detailed information about construction of specimen is shown in the drawings which form an integral part of test report. Drawings were delivered by sponsor.

3. TEST REPORTS AND EXTENDED APPLICATION REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS AND EXTENDED APPLICATION REPORTS

No. Name of laboratory Name of sponsors Test report No. Date of the test Test method [1] FIRES, s.r.o.,

Batizovce, SR

BAKS Kazimierz Sielski Karczew,Poland

FIRES-FR-

183-13-AUNE 24. 10. 2013

STN 92 0205 ZP-27/2008 DIN 4102-12

(5)

FIRES-JR-116-13-NURE

FIRES 149/S-27/10/2009-E Page: 4/8

3.2 TEST RESULTS

No./

Test method

Specimen

No. Cables Track

No.

Time to first failure / interruption of conductor

[1]

STN 92 0205 ZP-27/2008 DIN 4102-12

1 2 cables (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV

12 83 minutes

2 2 cables (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption 3 cable (N)HXCH-O FE180/E90 4x16RE/16 0,6/1 kV +

fireboxes PMO3B

13

90 minutes no failure / interruption 4 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV +

fireboxes PMO3B 90 minutes no failure / interruption

5 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV

11 84 minutes

6 2 cables (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 7 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV

10 72 minutes

8 2 cables (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 9 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV

8 90 minutes no failure / interruption 10 2 cables (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 11 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV

6 83 minutes

12 2 cables (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 13 2 cables (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV

9 70 minutes

14 2 cables (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption 15 2 cables (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV

7 90 minutes no failure / interruption 16 2 cables (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption 17 2 cables (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV

5 83 minutes

18 2 cables (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption 19 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV

4

82 minutes 20 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV 75 minutes 21 cable (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV 40 minutes 22 cable (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV 29 minutes

23 cable (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 24 cable (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 88 minutes

25 cable (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 89 minutes

26 cable (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption 27 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV

3

90 minutes no failure / interruption 28 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV 90 minutes no failure / interruption 29 cable (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV 90 minutes no failure / interruption 30 cable (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV 40 minutes

31 cable (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 32 cable (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 33 cable (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption 34 cable (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption 35 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV

2

84 minutes 36 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV 58 minutes 37 cable (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV 55 minutes 38 cable (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV 57 minutes

39 cable (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 40 cable (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 41 cable (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption 42 cable (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption

(6)

No./

Test method

Specimen

No. Cables Track

No.

Time to first failure / interruption of conductor

[1]

STN 92 0205 ZP-27/2008 DIN 4102-12

43 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV

1

90 minutes no failure / interruption 44 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 0,6/1 kV 75 minutes

45 cable (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV 71 minutes 46 cable (N)HXH-J FE180/E90 4x1,5RE 0,6/1 kV 48 minutes

47 cable (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 48 cable (N)HXCH-O FE180/E90 4x50RE/25 0,6/1 kV 90 minutes no failure / interruption 49 cable (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption 50 cable (N)HXH-O FE180/E90 4x50RM 0,6/1 kV 90 minutes no failure / interruption 52 cable JE-H(St)H Bd 2x2x0,8 FE180/E90

12 90 minutes no failure / interruption 53 cable JE-H(St)H Bd 2x2x0,8 FE180/E90 90 minutes no failure / interruption 54 cable JE-H(St)H Bd 2x2x0,8 FE180/E90 +

fireboxes PMO3B 13 90 minutes no failure / interruption

55 cable JE-H(St)H Bd 2x2x0,8 FE180/E90

11 90 minutes no failure / interruption 56 cable JE-H(St)H Bd 2x2x0,8 FE180/E90 90 minutes no failure / interruption 57 cable JE-H(St)H Bd 2x2x0,8 FE180/E90

9 90 minutes no failure / interruption 58 cable JE-H(St)H Bd 2x2x0,8 FE180/E90 90 minutes no failure / interruption 59 cable JE-H(St)H Bd 2x2x0,8 FE180/E90

7 90 minutes no failure / interruption 60 cable JE-H(St)H Bd 2x2x0,8 FE180/E90 90 minutes no failure / interruption 61 cable JE-H(St)H Bd 2x2x0,8 FE180/E90

5 90 minutes no failure / interruption 62 cable JE-H(St)H Bd 2x2x0,8 FE180/E90 90 minutes no failure / interruption 63 cable JE-H(St)H Bd 2x2x0,8 FE180/E90

4 90 minutes no failure / interruption 64 cable JE-H(St)H Bd 2x2x0,8 FE180/E90 90 minutes no failure / interruption 65 cable JE-H(St)H Bd 2x2x0,8 FE180/E90

3 90 minutes no failure / interruption 66 cable JE-H(St)H Bd 2x2x0,8 FE180/E90 90 minutes no failure / interruption 67 cable JE-H(St)H Bd 2x2x0,8 FE180/E90

1 90 minutes no failure / interruption 68 cable JE-H(St)H Bd 2x2x0,8 FE180/E90 90 minutes no failure / interruption

The fire test was discontinued in 94th minute at the request of test sponsor.

Specimens S1 – S50 were tested by three-phase voltage supply 3 x 230/400V with bulbs 240V / 60 W.

Specimens S52 – S68 were tested by one-phase voltage supply 1 x 110V with LED diodes 3V /0,03W.

Circuit breakers with rating 3 A were used.

(7)

FIRES-JR-116-13-NURE

FIRES 149/S-27/10/2009-E Page: 6/8

4. CLASSIFICATION AND FIELD OF APPLICATION 4.1 REFERENCE OF CLASSIFICATION

This classification has been carried out in accordance with clause 11 of ZP-27/2008 PAVUS.

4.2 CLASSIFICATION ACCORDING TO ZP-27/2008

The product, Cable bearing system and fireboxes BAKS with cables business Tele-Fonika Kable sp. z o.o.

S.K.A. at raised access floor is classified according to the following combinations of performance parameters and classes as appropriate.

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Cable trays KGJ/KGOJ400H60/B-400.

Consoles combined of brackets WWS/WWSO400 fixed to supports CWP/CWOP40H40/1

and threaded rods PG M12.

Consoles fixed to wall.

Loading 15kg.m-1. Consoles in spacing of 1500 mm.

Track No. 1.

E 90 n x ≥1,5 mm2 n ≥ 2 E 30

(N)HXH-J FE180/E90 4x1,5 RE E 30

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 90 n x ≥1,5 mm2

n ≥ 2 E 60

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM Cable trays KGJ/KGOJ400H60/B-400.

Consoles combined of brackets WMC/WMCO400 fixed to supports

CWP/CWOP40H40/1 and threaded rods PG M12.

Consoles fixed to wall.

Loading 15kg.m-1. Consoles in spacing of 1500 mm.

Track No. 2.

E 90 n x ≥1,5 mm2 n ≥ 2 E 30

(N)HXH-J FE180/E90 4x1,5 RE E 30

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 90 n x ≥1,5 mm2

n ≥ 2 E 30

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 30

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Cable ladders DUD/DUOD400H60/B-400.

Consoles combined of brackets WWS/WWSO400 fixed to supports CWP/CWOP40H40/1

and threaded rods PG M12.

Consoles fixed to wall.

Loading 20kg.m-1. Consoles in spacing of 1500 mm.

Track No. 3.

E 90 n x ≥1,5 mm2 n ≥ 2 E 30

(N)HXH-J FE180/E90 4x1,5 RE E 30

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 90 n x ≥1,5 mm2

n ≥ 2 E 90

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 90

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Cable ladders DUD/DUOD400H60/B-400.

Consoles combined of brackets WMC/WMCO400 fixed to supports

CWP/CWOP40H40/1 and threaded rods PG M12.

Consoles fixed to wall.

Loading 20kg.m-1. Consoles in spacing of 1500 mm.

Track No. 4.

E 60

Without classification

(N)HXH-J FE180/E90 4x1,5 RE Without

classification

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 60 n x ≥1,5 mm2

n ≥ 2 E 60

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(8)

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Cable trays KGJ/KGOJ400H60/B-400 fixed to horizontal supports CWP/CWOP40H40/07. Supports

fixed to pedestals (∅34) mm of raised floor by hangers OBR35.

Loading 20kg.m-1. Supports in spacing of 1200 mm.

Tracks No. 5 and 6.

E 90 n x ≥1,5 mm2 n ≥ 2 E 60

(N)HXH-J FE180/E90 4x1,5 RE E 60

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 90 n x ≥1,5 mm2

n ≥ 2 E 60

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Cable ladders DUD/DUOD400H60/B-400 fixed to horizontal supports CWP/CWOP40H40/07. Supports

fixed to pedestals (34) mm of raised floor by hangers OBR35.

Loading 20kg.m-1. Supports in spacing of 1200 mm.

Tracks No. 7 and 8.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

(N)HXH-J FE180/E90 4x1,5 RE E 90

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 90 n x ≥1,5 mm2

n ≥ 2 E 90

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 90

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Cable mesh trays KDS/KDSO 400H60/B-400 fixed to horizontal supports CWP/CWOP40H40/07. Supports

fixed to pedestals (∅34) mm of raised floor by hangers OBR35.

Loading 20kg.m-1. Supports in spacing of 1200 mm.

Tracks No. 9 and 10.

E 90 n x ≥1,5 mm2 n ≥ 2 E 60

(N)HXH-J FE180/E90 4x1,5 RE E 60

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 90 n x ≥1,5 mm2

n ≥ 2 E 60

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 Cable trays KGJ/KGOJ 400H60/B-400.

Consoles combined of horizontal support CWP/CWOP40H40/2 and

two threaded rods PG M10.

Loading 20kg.m-1. Consoles in spacing of 1500 mm.

Track No. 11.

E 90 n x ≥1,5 mm2 n ≥ 2 E 60

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM Cable trays KGJ/KGOJ 400H60/B-400.

Brackets WFL/WFLO400 fixed to wall by threaded rods PG M8 and at the end by threaded rods

PG M8 to ceiling.

Loading 20kg.m-1. Brackets in spacing of 1500 mm.

Track No. 12.

E 90

n x ≥1,5 mm2 n ≥ 2 E 60

(N)HXH-J FE180/E90 4x1,5 RE E 60

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x16RE/16 Track is made of fireboxes (BAKS PMO3B – tested without

current-limiting fuse) fixed to ceiling. Cables connected to fireboxes are fixed to ceiling by

cable clips KSA in spacing of 300 mm.

Track No. 13.

E 90 n x ≥1,5 - 16 mm2 n ≥ 2 E 90

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 90

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(9)

FIRES-JR-116-13-NURE

FIRES 149/S-27/10/2009-E Page: 8/8

4.3 FIELD OF APPLICATION

This classification is valid for the following end use applications:

§ throughout the period during which circuit integrity is to be maintained, neighbouring building components shall not have a negative effect on circuit integrity;

§ although testing is only carried out on cables arranged horizontally, test results also apply to cables arranged either diagonally or vertically (e.g. risers), as long as the cable system is supported in transitional areas (i.e. where it switches from a horizontal to a vertical arrangement) in such a manner that the cables will not slip or kink at corners;

§ test results of function in fire test of cables tested at standard supporting construction are also applicable for tested standard supporting construction of other producers;

§ test results of function in fire test of cables tested at standard supporting construction are also applicable for cables of other producers tested at standard supporting construction;

§ maximal length of increasing routing shall be 3500 mm with consistent horizontal placing of cable with minimal length of 300 mm (apart from cable bending) and with maximal spacing of clips of 300 mm, eventually the cables are stabilized by cable transmissions at floor or ceiling with particular fire resistance;

§ for vertical systems, the test results obtained for cables mounted singly on the ceiling using single clips apply. Brackets of proven suitability may also be used, as long as their spacing is equal to that of the single clips tested;

§ results of testing single cables on the ceiling apply also to cables mounted horizontally on walls;

§ results of testing bunched cables on a ladder or tray also apply to support construction attached to a wall. However, such constructions required proof of suitability by means of a test certificate or other document issued by an accredited testing laboratory.

5. LIMITATIONS

Load-bearing construction elements for fixing of cable systems must be proved for at least the same fire resistance compare to classified function in fire of cable system.

This classification document does not represent type approval or certification of the product.

The classification is valid until 25. 10. 2018 provided that the product, field of application and standards and regulations are not changed.

Approved: Signed:

Ing. Štefan Rástocký Bc. Dávid Šubert

leader of the testing laboratory technician of the testing laboratory

Cytaty

Powiązane dokumenty

Product comprised from cable bearing systems BAKS with accessories – cable trays, cable ladders, basket cable trays, ceiling ledges SDOC with clips UKO1, clips UEF, UDF

1-L1 no failure / interruption 2-L2 no failure / interruption 3-L3 no failure / interruption 4-PEN no failure / interruption 5-L1 no failure / interruption 6-L2 no failure

Test specimen comprised from cable bearing system BAKS Kazimierz Sielski company – cable trays, cable mesh trays, cable clips and fireboxes with accessories

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable hangers with accessories and power and communication halogen

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clamps and hangers with accessories (consoles, brackets,

The element, Cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clips and hangers with accessories (consoles, brackets, supports, etc.) and power

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clips and hangers with accessories (consoles, brackets,

Product comprise of cable bearing system BAKS – cable trays, cable mesh trays, cable clips KSA and UDF and fireboxes PMO 1 and PMO2 with accessories and