FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-007-14-NURE

Cable bearing system BAKS with cables business Tele-Fonika Kable sp. z o.o. S.K.A.

This is an electronic version of a classification report which was made as a copy of classification report officially issued in a paper form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e.

FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor.

FIRES 004/S2-20/12/2012-E-el

(2)

FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION IN ACCORDANCE WITH DIN 4102-12: 1998-11

FIRES-JR-007-14-NURE

Name of the product: Cable bearing system BAKS with cables business Tele-Fonika Kable sp. z o.o. S.K.A.

Sponsor: BAKS Kazimierz Sielski, ul. Jagodne 5, 05 - 480 Karczew, Poland producer of cable bearing system

Tele-Fonika Kable sp. z o.o. S.K.A., ul. Wielicka 114, 30-630 Kraków, Poland producer of cables

Prepared by: FIRES, s.r.o.

Approved Body No. SK01 Osloboditeľov 282

059 35 Batizovce Slovak Republic Task No.: PR-13-0525 Date of issue: 14. 03. 2014

Reports: 5

Copy No.: 2

Distribution list:

Copy No. 1 FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic (electronic version)

Copy No. 2 BAKS Kazimierz Sielski, ul. Jagodne 5, 05 - 480 Karczew, Poland (electronic version)

Copy No. 3 Tele-Fonika Kable sp. z o.o. S.K.A., ul. Wielicka 114, 30-630 Kraków, Poland (electronic version)

Copy No. 4 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland

Copy No. 5 Tele-Fonika Kable sp. z o.o. S.K.A., ul. Wielicka 114, 30-630 Kraków, Poland

This expert judgement report consists of 9 pages and may only be used or reproduced in its entirety.

(3)

FIRES-JR-007-14-NURE

FIRES 149/S-27/10/2009-E Page: 2

1. INTRODUCTION

This expert judgement report with classification defines the function in fire classification assigned to element „Cable bearing system BAKS with cables business Tele-Fonika Kable sp. z o.o. S.K.A.” in accordance with the classes given in DIN 4102-12: 1998-11.

This test was carried out according to standard STN 92 0205: 2012 and meets requirements of DIN 4102-12: 1998-11. Basic deviation in process and carrying out of test between these standards is in measuring and in control of temperature in the test furnace. According to STN 92 0205: 2012, plate thermometers according to EN 1363-1 are used. According to DIN 4102-12: 1998-11, common thermocouples of construction which was used for this measurement till issue of EN 1363-1 are used.

Measurement by plate thermometers acc. to EN 1363-1 can be considered as stricter method of temperature control in test furnace in compare with thermocouples used till issue of EN 1363-1. Therefore, it is possible to use results of test according to STN 92 025: 2012 for classification of tested cables according to DIN 4102-12: 1998-11, but not conversely.

This expert judgement report defines field of application which is outside the field of direct application according test standard or outside the field of extended application according to relevant extended application standard. This expert judgement expresses the opinion of the FIRES and is based on the experience or internal rules of FIRES.

2. DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL

The product, Cable bearing system BAKS with cables business Tele-Fonika Kable sp. z o.o. S.K.A., is defined as a cable bearing system for power and communication halogen free cables with circuit integrity maintenance.

2.2 PRODUCT DESCRIPTION

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable hangers with accessories and power and communication halogen free cables of Tele-Fonika Kable sp. z o.o. S.K.A. company.

Cable trays

Cable trays type KGJ/KGOJ…H60 are made from steel sheet thickness 0,9 mm. Trays are jointed together by screws type SGN M6x12. Trays are used as bearing system for the cables.

Cable trays type KBJ/KGOJ…H60 (trays without perforation) are made from steel sheet thickness 0,9 mm.

Trays are jointed together by screws type SGN M6x12. Trays are used as bearing system for the cables.

Cable trays type KCJ/KGOJ…H60 are made from steel sheet thickness 0,9 mm. Trays are jointed together by screws type SGN M6x12. Trays are used as bearing system for the cables.

Cable ladders

Cable ladders type DUP/DUOP…H60 are made from steel sheet thickness 1,5 mm and spacing of transoms is 300 mm. Cable ladders are jointed together by two junctions (LDCH60N) on both sides an screws (SGN M8x14). Cable ladders are used as bearing system for the cables.

Cable ladders type DUD/DUOD…H60 are made from steel sheet thickness 1,2 mm and spacing of transoms is 300 mm. Cable ladders are jointed together by two junctions (LDCH60N) on both sides an screws (SGN M8x14). Cable ladders are used as bearing system for the cables.

Consoles

Consoles type WPCW/WPCO are made from steel sheet thickness 2,0 mm and 6,0 mm.

Consoles are used to gripping brackets.

(4)

Brackets

Brackets type WMC/WMCO are made from steel sheet thickness 2,5 mm and 5 mm.

Brackets type WWS/WWSO are made from steel sheet thickness 2,0 mm.

Brackets type WFL/WFLO are made from steel sheet thickness 2,0 mm.

Brackets are used to gripping trays or ladders to ceiling or to wall.

Supports

Supports type CWP/CWOP are made from steel sheet thickness 1,5 mm.

Supports are used to gripping trays or ladders.

Wall channels

Wall channels type KS…H68/2 are made from steel sheet thickness 1,0 mm. Channels are jointed together by junctions (LKSH68) and (SU). Wall channel is covered by steel sheet (PKS).

Wall channels are used as bearing system for the cables.

Cable hangers

Supports type OZ/OZO are made from steel sheet thickness 1,5 mm.

Supports type OZS/OZSO are made from steel sheet thickness 0,7 mm.

Supports type OZM/OZMO are made from steel sheet thickness 0,7 mm.

Cable hangers are used to gripping cables to ceiling or wall.

Cables Power cables:

(N)HXH-J FE180/E90 4x1,5RE (26x)

(N)HXH-O FE180/E90 4x50RM (18x)

(N)HXCH-O FE180/E90 4x1,5RE/1,5 (22x) (N)HXCH-O FE180/E90 4x50RM/25 (14x) Communication cables:

HTKSH FE180 PH90 1x2x1.0 mm (20x)

HLGsekwf 2x1 mm2 (10x)

JE-H(St)H…Bd FE180/E90 2x2x0,8 (18x)

The length of cables was 5,5 m and 4,0 m from that was exposed to fire.

More detailed information about construction of specimen is shown in the drawings which form an integral part of test report. Drawings were delivered by sponsor.

3. TEST REPORTS AND EXTENDED APPLICATION REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS AND EXTENDED APPLICATION REPORTS

No. Name of laboratory Name of sponsors Test report No. Date of the test Test method [1] FIRES, s.r.o.,

Batizovce, SR

BAKS Kazimierz Sielski Karczew,Poland

FIRES-FR-

016-14-AUNE 30. 01. 2014

STN 92 0205 ZP-27/2008 DIN 4102-12

(5)

FIRES-JR-007-14-NURE

FIRES 149/S-27/10/2009-E Page: 4

3.2 TEST RESULTS No./

Test method

Specimen

No. Cables Track

No.

Time to first failure / interruption of conductor

[1]

STN 92 0205 ZP-27/2008 DIN 4102-12

1 2 cables (N)HXCH-O FE180/E90 4x50RM/25

13

90 minutes no failure / interruption 2 2 cables (N)HXH-O FE180/E90 4x50RM 90 minutes no failure / interruption 3 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5 65 minutes

4 2 cables (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption 5 2 cables (N)HXH-O FE180/E90 4x50RM

12 34 minutes

6 2 cables (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption 7 2 cables (N)HXCH-O FE180/E90 4x50RM/25

11 90 minutes no failure / interruption 8 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5 73 minutes

9 2 cables (N)HXH-O FE180/E90 4x50RM

10 90 minutes no failure / interruption 10 2 cables (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption 11 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5

9 90 minutes no failure / interruption 12 2 cables (N)HXCH-O FE180/E90 4x50RM/25 90 minutes no failure / interruption 13 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5

8 81 minutes

14 2 cables (N)HXCH-O FE180/E90 4x50RM/25 90 minutes no failure / interruption 15 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5

16 80 minutes 16 2 cables (N)HXH-J FE180/E90 4x1,5RE 85 minutes 17 2 cables (N)HXH-J FE180/E90 4x1,5RE

7 80 minutes 18 2 cables (N)HXH-O FE180/E90 4x50RM 28 minutes 19 2 cables (N)HXH-J FE180/E90 4x1,5RE

6 32 minutes

20 2 cables (N)HXH-O FE180/E90 4x50RM 90 minutes no failure / interruption 21 2 cables (N)HXH-J FE180/E90 4x1,5RE

5 58 minutes

22 2 cables (N)HXH-O FE180/E90 4x50RM 90 minutes no failure / interruption 23 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5

15 90 minutes no failure / interruption 24 2 cables (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption 25 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5

4

75 minutes

26 2 cables (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption 27 2 cables (N)HXH-O FE180/E90 4x50RM 90 minutes no failure / interruption 28 2 cables (N)HXCH-O FE180/E90 4x50RM/25 90 minutes no failure / interruption 29 2 cables (N)HXCH-O FE180/E90 4x1,5RE/1,5

3

82 minutes 30 2 cables (N)HXH-J FE180/E90 4x1,5RE 81 minutes

31 2 cables (N)HXCH-O FE180/E90 4x50RM/25 90 minutes no failure / interruption 32 2 cables (N)HXH-O FE180/E90 4x50RM 90 minutes no failure / interruption 33 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5

2

90 minutes no failure / interruption 34 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 90 minutes no failure / interruption 35 cable (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption 36 cable (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption 37 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5

1

90 minutes no failure / interruption 38 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 90 minutes no failure / interruption 39 cable (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption 40 cable (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption

(6)

No./

Test method

Specimen

No. Cables Track

No.

Time to first failure / interruption of conductor

[1]

STN 92 0205 ZP-27/2008 DIN 4102-12

41 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5

14

90 minutes no failure / interruption 42 cable (N)HXCH-O FE180/E90 4x1,5RE/1,5 90 minutes no failure / interruption 43 cable (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption 44 cable (N)HXH-J FE180/E90 4x1,5RE 90 minutes no failure / interruption 45 cable (N)HXCH-O FE180/E90 4x50RM/25 90 minutes no failure / interruption 46 cable (N)HXCH-O FE180/E90 4x50RM/25 90 minutes no failure / interruption 47 cable (N)HXH-O FE180/E90 4x50RM 90 minutes no failure / interruption 48 cable (N)HXH-O FE180/E90 4x50RM 90 minutes no failure / interruption 52 2 cables JE-H(St)H…Bd FE180/E90 2x2x0,8

13

64 minutes

53 2 cables HLGsekwf 2x1 mm2 68 minutes

54 2 cables HTKSH FE180 PH90 1x2x1.0 mm 90 minutes no failure / interruption 55 2 cables JE-H(St)H…Bd FE180/E90 2x2x0,8 12 90 minutes no failure / interruption 56 2 cables HTKSH FE180 PH90 1x2x1.0 mm

11 65 minutes

57 2 cables HLGsekwf 2x1 mm2 31 minutes

58 2 cables HTKSH FE180 PH90 1x2x1.0 mm 10 58 minutes

59 2 cables HTKSH FE180 PH90 1x2x1.0 mm 9 90 minutes no failure / interruption 60 2 cables HTKSH FE180 PH90 1x2x1.0 mm 8 58 minutes

61 2 cables HTKSH FE180 PH90 1x2x1.0 mm

16 90 minutes no failure / interruption 62 2 cables JE-H(St)H…Bd FE180/E90 2x2x0,8 90 minutes no failure / interruption 63 2 cables JE-H(St)H…Bd FE180/E90 2x2x0,8 7 90 minutes no failure / interruption 64 2 cables JE-H(St)H…Bd FE180/E90 2x2x0,8 5 64 minutes

65 2 cables HTKSH FE180 PH90 1x2x1.0 mm

15 90 minutes no failure / interruption 66 2 cables JE-H(St)H…Bd FE180/E90 2x2x0,8 90 minutes no failure / interruption 67 2 cables HTKSH FE180 PH90 1x2x1.0 mm

14

80 minutes

68 2 cables HLGsekwf 2x1 mm2 33 minutes

69 2 cables JE-H(St)H…Bd FE180/E90 2x2x0,8 90 minutes no failure / interruption 70 2 cables HLGsekwf 2x1 mm2

4 39 minutes 71 2 cables HTKSH FE180 PH90 1x2x1.0 mm 63 minutes

72 2 cables JE-H(St)H…Bd FE180/E90 2x2x0,8 3 90 minutes no failure / interruption 73 2 cables HTKSH FE180 PH90 1x2x1.0 mm 2 90 minutes no failure / interruption 74 2 cables HLGsekwf 2x1 mm2

1 76 minutes

75 2 cables JE-H(St)H…Bd FE180/E90 2x2x0,8 90 minutes no failure / interruption

The fire test was discontinued in 96th minute at the request of test sponsor.

Specimens S1 – S48 were tested by three-phase voltage supply 3 x 230/400V with bulbs 240V / 60 W.

Specimens S52 – S75 were tested by one-phase voltage supply 1 x 110V with LED diodes 3V /0,03W.

Circuit breakers with rating 3 A were used.

(7)

FIRES-JR-007-14-NURE

FIRES 149/S-27/10/2009-E Page: 6

4. CLASSIFICATION AND FIELD OF APPLICATION 4.1 REFERENCE OF CLASSIFICATION

This classification has been carried out in accordance with clause 3.2 of DIN 4102 – 12:1998-11.

4.2 CLASSIFICATION ACCORDING TO DIN 4102-12: 1998-11

The product, Cable bearing system and fireboxes BAKS with cables business Tele-Fonika Kable sp. z o.o.

S.K.A. at raised access floor is classified according to the following combinations of performance parameters and classes as appropriate.

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

(N)HXH

FE180/E90 (N)HXH-J FE180/E90 4x1,5 RE Cable trays KGJ/KGOJ400H60/B-400.

Consoles combined of brackets WWS/WWSO400 fixed to supports CWP/CWOP40H40/1

and threaded rods PG M12.

Consoles fixed to wall.

Loading 15kg.m-1. Consoles in spacing of 1500 mm.

Track No. 1.

E 90 Without

classification (N)HXCH

FE180/E90 (N)HXCH-O FE180/E90 4x1,5RE/1,5 E 90 Without

classification JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

HLGsekwf HLGsekwf 2x1 mm2 E 60

n x ≥ 1,0 mm2 n ≥ 2 E 60 (N)HXH

FE180/E90 (N)HXH-J FE180/E90 4x1,5 RE

Cable trays KGJ/KGOJ400H60/B-400.

Consoles combined of brackets WMC/WMCO400 fixed to supports

CWP/CWOP40H40/1 and threaded rods PG M12.

Consoles fixed to wall.

Loading 15kg.m-1. Consoles in spacing of 1500 mm.

Track No. 2.

E 90 Without

classification (N)HXCH

FE180/E90 (N)HXCH-O FE180/E90 4x1,5RE/1,5 E 90 Without

classification HTKSH

FE180 E90

HTKSH FE180 PH90 1x2x1.0 mm E 90

n x 2 x ≥ 1,0 mm n ≥ 1 E 90

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Cable ladders DUD/DUOD400H60/B-400.

Consoles combined of brackets WWS/WWSO400 fixed to supports CWP/CWOP40H40/1

and threaded rods PG M12.

Consoles fixed to wall.

Loading 20kg.m-1. Consoles in spacing of 1500 mm.

Track No. 3.

E 90 n x ≥1,5 mm2 n ≥ 2 E 60

(N)HXH-J FE180/E90 4x1,5 RE E 60

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 90 n x ≥1,5 mm2

n ≥ 2 E 60

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Cable ladders DUD/DUOD400H60/B-400.

Consoles combined of brackets WMC/WMCO400 fixed to supports

CWP/CWOP40H40/1 and threaded rods PG M12.

Consoles fixed to wall.

Loading 20kg.m-1. Consoles in spacing of 1500 mm.

Track No. 4.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

(N)HXH-J FE180/E90 4x1,5 RE E 90

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 90 n x ≥1,5 mm2

n ≥ 2 E 60

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60

HTKSH FE180

E90

HTKSH FE180 PH90 1x2x1.0 mm E 60

n x 2 x ≥ 1,0 mm n ≥ 1 E 60

HLGsekwf HLGsekwf 2x1 mm2 E 30

n x ≥ 1,0 mm2 n ≥ 2 E 30

(8)

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM Cable trays KBJ400H60/B-400 + cover PKJ400 with clips ZPD H60.

Consoles WPCW/WPCO1000 with brackets WFL/WFLO400 and

threaded rods PG M10.

Loading 15kg.m-1. Consoles in spacing of 1500 mm.

Track No. 5.

E 90 n x ≥1,5 mm2 n ≥ 2 E 30

(N)HXH-J FE180/E90 4x1,5 RE E 30

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 60

n x 2 x ≥ 0,8 mm n ≥ 2 E 60

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Cable trays KCJ/KCOJ400H60/B-400.

Consoles WPCW/WPCO1000 with brackets WFL/WFLO400 and

threaded rods PG M10.

Loading 15kg.m-1. Consoles in spacing of 1500 mm.

Track No. 6.

E 90

n x ≥1,5 mm2 n ≥ 2 E 30

(N)HXH-J FE180/E90 4x1,5 RE E 30

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM Cable ladders DUP/DUOP400H60/B-400.

Consoles WPCW/WPCO1000 with brackets WFL/WFLO400 and

threaded rods PG M10.

Loading 25kg.m-1. Consoles in spacing of 1500 mm.

Track No. 7.

Without

classification Without classification

(N)HXH-J FE180/E90 4x1,5 RE E 60

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 Cable trays KBJ400H60/B-400 + cover PKJ400 with clips ZPD H60.

Consoles combined of horizontal supports CWP/CWOP40H40/2 and two threaded rods PG M10

fixed to ceiling.

Loading 15kg.m-1. Consoles in spacing of 1500 mm.

Track No. 8.

E 90 n x ≥1,5 mm2 n ≥ 2 E 60

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60

HTKSH FE180

E90

HTKSH FE180 PH90 1x2x1.0 mm E 30

n x 2 x ≥ 1,0 mm n ≥ 1 E 30

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 Cable trays KCJ/KCOJ400H60/B-400.

Consoles combined of horizontal supports CWP/CWOP40H40/2 and two threaded rods PG M10

fixed to ceiling.

Loading 15kg.m-1. Consoles in spacing of 1500 mm.

Track No. 9.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 90

HTKSH FE180

E90

HTKSH FE180 PH90 1x2x1.0 mm E 90

n x 2 x ≥ 1,0 mm n ≥ 1 E 90

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM Cable ladders DUP/DUOP400H60/B-400.

Consoles combined of horizontal supports CWP/CWOP40H40/2 and two threaded rods PG M10

fixed to ceiling.

Loading 20kg.m-1. Consoles in spacing of 1500 mm.

Track No. 10.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

(N)HXH-J FE180/E90 4x1,5 RE E 90

HTKSH FE180

E90

HTKSH FE180 PH90 1x2x1.0 mm E 30

n x 2 x ≥ 1,0 mm n ≥ 1 E 30

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25

Cable ladders DUP/DUOP400H60/B-400.

Consoles WPCW/WPCO500.

Ladders fixed to consoles by hangers UTM/UTMO.

Loading 20kg.m-1. Consoles in spacing of 1500 mm.

Track No. 11.

E 90 n x ≥1,5 mm2 n ≥ 2 E 60

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60

HTKSH FE180

E90

HTKSH FE180 PH90 1x2x1.0 mm E 60

n x 2 x ≥ 1,0 mm n ≥ 1 E 60

HLGsekwf HLGsekwf 2x1 mm2 E 30

n x ≥ 1,0 mm2 n ≥ 2 E 30

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM Cable ladders DUP/DUOP400H60/B-400.

Consoles WPCW/WPCO500.

Ladders fixed to consoles by

E 30 n x ≥1,5 mm2 n ≥ 2 E 30

(N)HXH-J FE180/E90 4x1,5 RE E 90

(9)

FIRES-JR-007-14-NURE

FIRES 149/S-27/10/2009-E Page: 8

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Wall channels KS 130H68/2 fixed to side wall by expansion screws (MKR6x32) in spacing of 800 mm.

Track No. 13.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

(N)HXH-J FE180/E90 4x1,5 RE E 90

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 90 n x ≥1,5 mm2

n ≥ 2 E 60

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 60

n x 2 x ≥ 0,8 mm n ≥ 2 E 60 HTKSH

FE180 E90

HTKSH FE180 PH90 1x2x1.0 mm E 90

n x 2 x ≥ 1,0 mm n ≥ 1 E 90

HLGsekwf HLGsekwf 2x1 mm2 E 60

n x ≥ 1,0 mm2 n ≥ 2 E 60

(N)HXH FE180/E90

(N)HXH-O FE180/E90 4x50 RM

Cable hangers OZ/OZO fixed to ceiling in spacing of 600 mm.

Track No. 14.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

(N)HXH-J FE180/E90 4x1,5 RE E 90

(N)HXCH FE180/E90

(N)HXCH-O FE180/E90 4x50RM/25 E 90 n x ≥1,5 mm2

n ≥ 2 E 90

(N)HXCH-O FE180/E90 4x1,5RE/1,5 E 90

JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90 HTKSH

FE180 E90

HTKSH FE180 PH90 1x2x1.0 mm E 60

n x 2 x ≥ 1,0 mm n ≥ 1 E 60

HLGsekwf HLGsekwf 2x1 mm2 E 30

n x ≥ 1,0 mm2 n ≥ 2 E 30 (N)HXH

FE180/E90 (N)HXH-J FE180/E90 4x1,5 RE

Cable hangers OZS/OZSO fixed to ceiling in spacing of 600 mm.

Track No. 15.

E 90 Without

classification (N)HXCH

FE180/E90 (N)HXCH-O FE180/E90 4x1,5RE/1,5 E 90 Without

classification JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90 HTKSH

FE180 E90

HTKSH FE180 PH90 1x2x1.0 mm E 90

n x 2 x ≥ 1,0 mm n ≥ 1 E 90 (N)HXH

FE180/E90 (N)HXH-J FE180/E90 4x1,5 RE

Cable hangers OZM/OZMO fixed to ceiling in spacing of 600 mm.

Track No. 16.

E 60 Without

classification (N)HXCH

FE180/E90 (N)HXCH-O FE180/E90 4x1,5RE/1,5 E 60 Without

classification JE-H(St)H Bd

FE180/E90 JE-H(St)H Bd 2x2x0,8 FE180/E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 2 E 90 HTKSH

FE180 E90

HTKSH FE180 PH90 1x2x1.0 mm E 90

n x 2 x ≥ 1,0 mm n ≥ 1 E 90

(10)

4.3 FIELD OF APPLICATION

This classification is valid for the following end use applications:

§ throughout the period during which circuit integrity is to be maintained, neighbouring building components shall not have a negative effect on circuit integrity;

§ although testing is only carried out on cables arranged horizontally, test results also apply to cables arranged either diagonally or vertically (e.g. risers), as long as the cable system is supported in transitional areas (i.e. where it switches from a horizontal to a vertical arrangement) in such a manner that the cables will not slip or kink at corners;

§ test results of function in fire test of cables tested at standard supporting construction are also applicable for tested standard supporting construction of other producers;

§ test results of function in fire test of cables tested at standard supporting construction are also applicable for cables of other producers tested at standard supporting construction;

§ maximal length of increasing routing shall be 3500 mm with consistent horizontal placing of cable with minimal length of 300 mm (apart from cable bending) and with maximal spacing of clips of 300 mm, eventually the cables are stabilized by cable transmissions at floor or ceiling with particular fire resistance;

§ for vertical systems, the test results obtained for cables mounted singly on the ceiling using single clips apply. Brackets of proven suitability may also be used, as long as their spacing is equal to that of the single clips tested;

§ results of testing single cables on the ceiling apply also to cables mounted horizontally on walls;

§ results of testing bunched cables on a ladder or tray also apply to support construction attached to a wall. However, such constructions required proof of suitability by means of a test certificate or other document issued by an accredited testing laboratory.

5. LIMITATIONS

Load-bearing construction elements for fixing of cable systems must be proved for at least the same fire resistance compare to classified function in fire of cable system.

This classification document does not represent type approval or certification of the product.

The classification is valid until 14. 03. 2019 provided that the product, field of application and standards and regulations are not changed.

Approved: Signed:

Ing. Štefan Rástocký Bc. Dávid Šubert

leader of the testing laboratory technician of the testing laboratory

Cytaty

Powiązane dokumenty

Consoles combined of assembling profile CWP40H22/05 and threaded rods PG M8 fixed to.. ceiling by anchors HKD

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clips and hangers with accessories (consoles, brackets,

Product comprise of cable bearing system of company BAKS Kazimierz Sielski – cable trays, mesh trays, ladders, cable clamps with accessories (consoles, brackets, supports,

The element, Cable bearing system BAKS – cable trays, cable ladders, cable clips and clamps with accessories (consoles, brackets, supports, hangers, etc.) and

The element comprise of cable bearing system BAKS – cable trays KCOP, cable ladders DGOP, ceiling ledges SDOP with clips UKO1 and clips UDF with accessories (consoles, booms,

§ test results of function in fire test of cables at nonstandard supporting construction are valid only for tested construction with particular tested cable

The element comprise of cable bearing system BAKS – cable trays KCOP, cable mesh trays KDSO, cable ladders DGOP, DUOP, cable clips UDF, UEF, 1015 and accessories (consoles

§ test results of function in fire test of cables at nonstandard supporting construction are valid only for tested construction with particular tested cable