FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-084-15-NURE
Cable bearing system BAKS with cables business TECHNOKABEL S.A.
This is an electronic version of a classification report which was made as a copy of classification report officially issued in a paper form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e.
FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor.
FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION IN ACCORDANCE WITH DIN 4102-12: 1998-11
FIRES-JR-084-15-NURE
FIRES 149/S-10/08/2015-E FIRES, s.r.o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk
Name of the product: Cable bearing system BAKS
with cables business TECHNOKABEL S.A.
Sponsor: BAKS Kazimierz Sielski ul. Jagodne 5
05-480 Karczew Poland
Prepared by: FIRES, s.r.o.
Approved Body No. SK01 Osloboditeľov 282
059 35 Batizovce Slovak Republic
Task No.: PR-15-0333 Date of issue: 10. 09. 2015
Reports: 5
Copy No.: 2
Distribution list:
Copy No. 1 FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic (electronic version)
Copy No. 2 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland (electronic version)
Copy No. 3 TECHNOKABEL S.A., Nasielska 55, 04-343 Warszawa, Poland (electronic version)
Copy No. 4 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland
Copy No. 5 TECHNOKABEL S.A., Nasielska 55, 04-343 Warszawa, Poland
This expert judgement report with classification may only be used or reproduced in its entirety.
1. INTRODUCTION
This expert judgement report with classification defines the function in fire classification assigned to element Cable bearing system BAKS with cables business TECHNOKABEL S. A. in accordance with the classes given in DIN 4102 – 12: 1998-11.
This test was carried out according to standard STN 92 0205 and meets requirements of DIN 4102-12: 1998-11. Basic deviation in process and carrying out of test between these standards is in measuring and in control of temperature in the test furnace. According to STN 92 0205, plate thermometers according to EN 1363-1 are used. According to DIN 4102-12: 1998-11, common thermocouples of construction which was used for this measurement till issue of EN 1363-1 are used.
Measurement by plate thermometers acc. to EN 1363-1 can be considered as stricter method of temperature control in test furnace in compare with thermocouples used till issue of EN 1363-1. Therefore, it is possible to use results of test according to STN 92 025 for classification of tested cables according to DIN 4102-12: 1998-11, but not conversely.
This expert judgement report defines field of application which is outside the field of direct application according test standard or outside the field of extended application according to relevant extended application standard. This expert judgement expresses the opinion of the FIRES and is based on the experience or internal rules of FIRES.
This products have already been classified by FIRES, s.r.o. and number of previous classification of function in fire is FIRES-CR-020-09-AUPE, issued on 25. 05. 2009.
2. DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL
The element, Cable bearing system BAKS with power and communication halogen free cables business TECHNOKABEL S. A., is defined as a cable bearing system for power and communication halogen free cables with circuit integrity maintenance.
2.2 PRODUCT DESCRIPTION
The element comprise of cable bearing system BAKS – cable trays KCOD and KCOJ, cable ladders DGOP, DGOD and DUOP, cable holders OZO, ceiling ledges SDOC with clips UKO1, clips UDF, UEF and KSA, and accessories (consoles WPCO, hangers WFLO, booms, WMCO and WWSO, supports CWOP, holders UPWO, UTMO and WPPOVE, threaded rods, dowels etc.) with power and communication non-halogen cables business TECHNOKABEL S. A., type NHXH, NHXCH, HTKSH, HTKSHekw, HDGsżo, HDGsekwżo, with circuit integrity maintenance in fire.
Cable trays KCOD
Cable trays type KCOD…H60N are made from galvanized steel sheet thickness 1,2 mm. Trays are jointed together by two junctions type LPOPH60N (galvanized steel sheet thickness 1,5 mm) and by sheet type BLO…N (galvanized steel sheet thickness 1,0 mm) with screws type SGN M6x12. Trays are used as bearing system for the cables. Tested trays were
KCOD 400H60/3N.
Cable trays KCOJ…H60E
Cable trays type KCOJ…H60E are made from stainless steel sheet thickness 1,0 mm. Trays are jointed together by two junctions type LPOPH60E (stainless steel sheet thickness 1,5 mm) and by sheet type BLO…E (stainless steel sheet thickness 1,0 mm) with screws type SGN M6x12/E. Trays are used as bearing system for the cables. Tested trays were
KCOJ 400H60/3E.
Cable ladders DGOP
Cable ladders type DGOP H60 are made from galvanized steel sheet thickness 1,5 mm and spacing of
transoms is 150 mm. Ladders are jointed together by two junction type LDOCH60N (galvanized steel
sheet thickness 2,0 mm) with screws type SGN M8x14. Ladders are used as bearing system for the
cables. Tested ladders were
DGOP 400H60/3N.
Cable ladders DGOD…H60E
Cable ladders type DGOD…H60E are made from stainless steel sheet thickness 1,2 mm and spacing of transoms is 150 mm. Ladders are jointed together by two junction type LDOCH60E (stainless steel sheet thickness 2,0 mm) with screws type SGN M8x14/E. Ladders are used as bearing system for the cables.
Tested ladders were
DGOD 400H60/3E. Cable ladders DUOP
Cable ladders type DUOP H60 are made from galvanized steel sheet thickness 1,2 mm and spacing of transoms is 300 mm. Ladders are jointed together by two junction type LDOCH60N (galvanized steel sheet thickness 2,0 mm) with screws type SGN M8x14. Ladders are used as bearing system for the cables. Tested ladders were
DUOP 400H60/3N.
Consoles WPCO
Consoles type WPCO are made from galvanized steel sheet thickness 5,0 mm and 2,0 mm. Hangers are used to gripping trays or ladders to ceiling. Tested consoles were WPCO 800.
Booms WMCO
Booms type WMCO are made from galvanized steel sheet thickness 5,0 mm and 2,5 mm. Booms are used to gripping trays or ladders to consoles WPCO or to wall. Tested booms were WMCO 300.
Booms WWSO
Booms type WMCO are made from galvanized steel sheet thickness 2,0 mm. Booms are used to gripping trays or ladders to consoles WPCO or to wall. Tested booms were WWSO 400.
Hangers WFLO
Hangers type WFLO are made from galvanized steel sheet thickness 2,0 mm. Hangers are used to gripping trays or ladders to ceiling or to wall. Tested hangers were WFLO 500 and WFLO 400.
Holders UTMO
Holders type UTMO are made from galvanized steel sheet thickness 2,0 mm. Holders are used to gripping ladders to ceiling or to wall.
Holders UPWO
Holders type UPWO are made from galvanized steel sheet thickness 2,0 mm. Holders are used to gripping threaded rods to ceiling.
Holders WPPOWE
Holders type WPPOVE are made from stainless steel sheet thickness 5,0 mm. Holders are used to gripping threaded rods to ceiling.
Supports CWOP…E
Supports CWOP40H40…E are made from stainless steel sheet thickness 1,5 mm. Supports with threaded rods are used to gripping trays or ladders to ceiling. Tested supports were CWOP40H40/05E.
Ceiling ledges SDOC
Ceiling ledges type SDOC are made from galvanized steel sheet thickness 2,0 mm. Ceiling ledges are used to gripping cables with clips UKO1 to ceiling or to wall.
Cable clips UKO1
Cable clips UKO are made from steel sheet thickness 2,0 mm. Clips UKO1 are used to gripping cables to ledges or to ladders.
Cable holders OZO
Cable holders type OZO are made from steel sheet thickness 1,5 mm. Cable holders are used to gripping cables to ceiling or to wall.
Cable clips UDF and UEF
Cable clips UDF and UEF are made from steel sheet thickness 1,2 mm or 2,0 mm. Clips are used to gripping cables to ceiling or to wall.
Cable clips KSA
Cable clips KSA are made from steel sheet thickness 1,2 mm. Clips are used to gripping cables to ceiling
or to wall.
Cables
Power cables NHXH, NHXCH, - fire resistant power cables, insulated and sheathed with halogen free compounds, are intended for power supply to fire protection equipment which is to operate in fire conditions (e.g. water pumps in fire extinguishing systems, smoke removing fans).
Halogen free cables shall be applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required.
Functions of the cables are maintained – power is supplied to equipment which must operate in fire conditions and during firefighting. The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive. The cables are suitable for indoor and outdoor installations.
Communication cables HTKSH, HTKSHekw, HDGsżo, HDGsekwżo - fire resistant and halogen free cables are intended for installation in alarm, signalling, transmission, sound warning and similar systems, also for data processing systems and for analogue or digital data transmission in industrial electronics and control applications in objects of sharp fire protection requirements, particularly in fire alarm and fire automatic control systems.
Halogen free cables are applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required.
Functions of the cables are maintained – data are transmitted and power is supplied to equipment which must operate in fire conditions and during firefighting (e.g. emergency lighting). The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive. Cables circuits are protected by an overall electrostatic shield against external electric field interferences.
The cables are suitable for indoor installations.
Used cables by test:
Power cables:
NHXH 4x1,5 RE FE180 PH30/E30 ( 4 x )
NHXH 4x50 RM FE180 PH30/E30 ( 4 x )
NHXCH 4x1,5/1,5 RE FE180 PH30/E30 ( 4 x ) NHXCH 4x50/25 RM FE180 PH30/E30 ( 4 x )
NHXH 4x1,5 RE FE180 PH90/E90 ( 18 x )
NHXH 4x16 RM FE180 PH90/E90 ( 2 x )
NHXH 4x50 RM FE180 PH90/E90 ( 16 x )
NHXCH 4x1,5/1,5 RE FE180 PH90/E90 ( 10 x ) NHXCH 4x16/16 RM FE180 PH90/E90 ( 2 x ) NHXCH 4x50/25 RM FE180 PH90/E90 ( 10 x ) Communication cables:
HTKSH 1x2x0,8 FE180 PH90/E30-E90 ( 20 x ) HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 ( 16 x ) HDGszo 3x2,5 FE180 PH90/E30-E90 ( 16 x ) HDGsekwzo 3x2,5 FE180 PH90/E30-E90 ( 12 x )
Cables were fixed to trays by clips UDF and ladders by clips UKO1 according to the cable diameter.
More detailed information about product construction is shown in the drawings which form an integral part of test report [1]. Drawings were delivered by sponsor.
3. TEST REPORTS AND EXTENDED APPLICATION REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS AND EXTENDED APPLICATION REPORTS
No. Name of laboratory Name of sponsors Test report No. Date of the test Test method
[1] Fires s.r.o., Batizovce, SR
BAKS Kazimierz Sielski,
Karczew, PL
FIRES-FR-
004-09-AUNE 16. 01. 2009 DIN 4102 – 12:
1998-11
3.2 TEST RESULTS
Test report No.
/Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
[1]
DIN 4102-12
1 2 cables NHXCH 4x50/25 RM FE180 PH90/E90 14 90 minutes no failure / interruption 2 2 cables NHXCH 4x1,5/1,5 RE FE180 PH90/E90 14 90 minutes no failure / interruption 3 2 cables NHXH 4x50 RM FE180 PH90/E90 13 90 minutes no failure / interruption 4 2 cables NHXH 4x1,5 RE FE180 PH90/E90 13 90 minutes no failure / interruption 5 NHXH 4x1,5 RE FE180 PH90/E90 9 90 minutes no failure / interruption 6 NHXH 4x1,5 RE FE180 PH90/E90 9 90 minutes no failure / interruption 7 NHXH 4x50 RM FE180 PH90/E90 9 90 minutes no failure / interruption 8 NHXH 4x50 RM FE180 PH90/E90 9 90 minutes no failure / interruption 9 NHXCH 4x50/25 RM FE180 PH90/E90 9 90 minutes no failure / interruption 10 NHXCH 4x50/25 RM FE180 PH90/E90 9 90 minutes no failure / interruption 11 NHXH 4x50 RM FE180 PH90/E90 8 90 minutes no failure / interruption 12 NHXH 4x50 RM FE180 PH90/E90 8 90 minutes no failure / interruption 13 NHXH 4x1,5 RE FE180 PH90/E90 8 90 minutes no failure / interruption 14 NHXH 4x1,5 RE FE180 PH90/E90 8 90 minutes no failure / interruption 15 2 cables NHXCH 4x1,5/1,5 RE FE180 PH90/E90 12 90 minutes no failure / interruption 16 2 cables NHXCH 4x50/25 RM FE180 PH90/E90 12 90 minutes no failure / interruption 17 2 cables NHXCH 4x1,5/1,5 RE FE180 PH30/E30 7 90 minutes no failure / interruption 18 2 cables NHXH 4x1,5 RE FE180 PH30/E30 7 23 minutes
19 2 cables NHXCH 4x50/25 RM FE180 PH30/E30 7 71 minutes 20 2 cables NHXH 4x50 RM FE180 PH30/E30 7 18 minutes
21 2 cables NHXCH 4x1,5/1,5 RE FE180 PH90/E90 6 90 minutes no failure / interruption 22 2 cables NHXCH 4x50/25 RM FE180 PH90/E90 6 90 minutes no failure / interruption 23 2 cables NHXH 4x50 RM FE180 PH30/E30 6 59 minutes
24 NHXCH 4x50/25 RM FE180 PH90/E90 5 90 minutes no failure / interruption 25 NHXCH 4x50/25 RM FE180 PH90/E90 5 90 minutes no failure / interruption 26 NHXCH 4x1,5/1,5 RE FE180 PH90/E90 5 90 minutes no failure / interruption 27 NHXCH 4x1,5/1,5 RE FE180 PH90/E90 5 90 minutes no failure / interruption 28 2 cables NHXH 4x50 RM FE180 PH90/E90 4 90 minutes no failure / interruption 29 2 cables NHXH 4x1,5 RE FE180 PH90/E90 4 90 minutes no failure / interruption 30 2 cables NHXH 4x1,5 RE FE180 PH90/E90 22 90 minutes no failure / interruption 31 2 cables NHXH 4x50 RM FE180 PH90/E90 22 90 minutes no failure / interruption 32 2 cables NHXH 4x1,5 RE FE180 PH90/E90 11 90 minutes no failure / interruption 33 2 cables NHXCH 4x1,5/1,5 RE FE180 PH90/E90 11 90 minutes no failure / interruption 34 2 cables NHXCH 4x16/16 RM FE180 PH90/E90 11 90 minutes no failure / interruption 35 2 cables NHXH 4x16 RM FE180 PH90/E90 11 80 minutes
36 2 cables (N)HXH 1x50 RM FE180 PH90/E90 3 28 minutes
37 2 cables NHXH 4x1,5 RE FE180 PH30/E30 3 90 minutes no failure / interruption 38 2 cables NHXCH 4x50/25 RM FE180 PH30/E30 3 81 minutes
39 2 cables NHXCH 4x1,5/1,5 RE FE180 PH30/E30 3 90 minutes no failure / interruption 40 NHXH 4x50 RM FE180 PH90/E90 2 90 minutes no failure / interruption 41 NHXH 4x50 RM FE180 PH90/E90 2 90 minutes no failure / interruption 42 NHXH 4x1,5 RE FE180 PH90/E90 2 90 minutes no failure / interruption 43 NHXH 4x1,5 RE FE180 PH90/E90 2 90 minutes no failure / interruption 44 NHXH 4x50 RM FE180 PH90/E90 1 90 minutes no failure / interruption 45 NHXH 4x50 RM FE180 PH90/E90 1 90 minutes no failure / interruption 46 NHXH 4x1,5 RE FE180 PH90/E90 1 90 minutes no failure / interruption 47 NHXH 4x1,5 RE FE180 PH90/E90 1 90 minutes no failure / interruption 48 2 cables NHXH 4x50 RM FE180 PH90/E90 15 65 minutes
49 2 cables NHXH 4x1,5 RE FE180 PH90/E90 15 90 minutes no failure / interruption
50 (N)HXH 1x50 RM FE180 PH90/E90 15 57 minutes
51 (N)HXH 1x50 RM FE180 PH90/E90 15 90 minutes no failure / interruption 52A HTKSH 1x2x0,8 FE180 PH90/E30-E90 20 90 minutes no failure / interruption 52B HTKSH 1x2x0,8 FE180 PH90/E30-E90 20 90 minutes no failure / interruption 53A HDGszo 3x2,5 FE180 PH90/E30-E90 19 90 minutes no failure / interruption 53B HDGszo 3x2,5 FE180 PH90/E30-E90 19 90 minutes no failure / interruption 54A 2 cables HTKSH 1x2x0,8 FE180 PH90/E30-E90 12 90 minutes no failure / interruption
Test report No.
/Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
[1]
DIN 4102-12
54B 2 cables HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 12 90 minutes no failure / interruption 55A HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 9 90 minutes no failure / interruption 55B HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 9 90 minutes no failure / interruption 56A HTKSH 1x2x0,8 FE180 PH90/E30-E90 9 90 minutes no failure / interruption 56B HTKSH 1x2x0,8 FE180 PH90/E30-E90 9 90 minutes no failure / interruption 57A HDGsekwzo 3x2,5 FE180 PH90/E30-E90 9 24 minutes
57B HDGsekwzo 3x2,5 FE180 PH90/E30-E90 9 36 minutes
58A HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 58B HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 59A HDGszo 3x2,5 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 59B HDGszo 3x2,5 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 60A HTKSH 1x2x0,8 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 60B HTKSH 1x2x0,8 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 61A 2 cables HDGsekwzo 3x2,5 FE180 PH90/E30-E90 5 90 minutes no failure / interruption 61B 2 cables HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 5 90 minutes no failure / interruption 62A 2 cables HDGszo 3x2,5 FE180 PH90/E30-E90 4 90 minutes no failure / interruption 62B 2 cables HTKSH 1x2x0,8 FE180 PH90/E30-E90 4 90 minutes no failure / interruption 63A 2 cables HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 21 90 minutes no failure / interruption 63B 2 cables HTKSH 1x2x0,8 FE180 PH90/E30-E90 21 90 minutes no failure / interruption 64A 2 cables HTKSH 1x2x0,8 FE180 PH90/E30-E90 11 90 minutes no failure / interruption 64B 2 cables HDGsekwzo 3x2,5 FE180 PH90/E30-E90 11 90 minutes no failure / interruption 65A HDGszo 3x2,5 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 65B HDGszo 3x2,5 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 66A HTKSH 1x2x0,8 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 66B HTKSH 1x2x0,8 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 67A HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 67B HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 68A HDGsekwzo 3x2,5 FE180 PH90/E30-E90 1 90 minutes no failure / interruption 68B HDGsekwzo 3x2,5 FE180 PH90/E30-E90 1 47 minutes
69A HTKSH 1x2x0,8 FE180 PH90/E30-E90 1 90 minutes no failure / interruption 69B HTKSH 1x2x0,8 FE180 PH90/E30-E90 1 90 minutes no failure / interruption 70A HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 1 90 minutes no failure / interruption 70B HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 1 90 minutes no failure / interruption 71A 2 cables HDGszo 3x2,5 FE180 PH90/E30-E90 10 90 minutes no failure / interruption 71B 2 cables HDGsekwzo 3x2,5 FE180 PH90/E30-E90 10 49 minutes
72A 2 cables HDGsekwzo 3x2,5 FE180 PH90/E30-E90 10 90 minutes no failure / interruption 72B 2 cables HDGszo 3x2,5 FE180 PH90/E30-E90 10 90 minutes no failure / interruption 73A 2 cables HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 18 90 minutes no failure / interruption 73B 2 cables HDGszo 3x2,5 FE180 PH90/E30-E90 15 90 minutes no failure / interruption 74A HTKSH 1x2x0,8 FE180 PH90/E30-E90 17 90 minutes no failure / interruption 74B HTKSH 1x2x0,8 FE180 PH90/E30-E90 17 90 minutes no failure / interruption 75A HDGszo 3x2,5 FE180 PH90/E30-E90 16 90 minutes no failure / interruption 75B HDGszo 3x2,5 FE180 PH90/E30-E90 16 90 minutes no failure / interruption
[1] The fire test was discontinued in 96
thminute at the request of sponsor.
Specimens S1 – S51 were tested by three-phase voltage supply 3 x 230/400V with bulbs 240V / 60 W.
Specimens S52 – S75 were tested by one-phase voltage supply 1 x 110V with LED diodes 3V /0,03W.
Circuit breakers with rating 3 A and performance characteristics B(gL) were used.
4. CLASSIFICATION AND FIELD OF APPLICATION 4.1 REFERENCE OF CLASSIFICATION
This classification has been carried out in accordance with clause 3.2 of DIN 4102 – 12:1998-11.
4.2 CLASSIFICATION ACCORDING TO DIN 4102-12: 1998-11
The element, cable bearing system BAKS – cable trays KCOD and KCOJ, cable ladders DGOP, DGOD and DUOP, cable holders OZO, ceiling ledges SDOC with clips UKO1, clips UDF, UEF and KSA, and accessories (consoles WPCO, hangers WFLO, booms, WMCO and WWSO, supports CWOP, holders UPWO, UTMO and WPPOVE, threaded rods, dowels etc.) with power and communication non-halogen cables business TECHNOKABEL S. A., type NHXH, NHXCH, HTKSH, HTKSHekw, HDGs żo, HDGsekwżo is classified according to the following combinations of performance parameters and classes as appropriate.
Used cables by test are classified as follows:
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
NHXH FE180 PH90/E90
NHXH 4x1,5 RE FE180 PH90/E90
Cable trays KCOD 400H60/3N.
Hangers WFLO 500 fixed to ceiling by two dowels PSRO M10x80.
Hangers WFLO 400 with threaded rods PGM10.
Consoles in spacing of 1500 mm.
Loading 10 kg.m-1. Track No. 1.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
NHXH 4x50 RM FE180 PH90/E90 E 90
HTKSHekw FE180 PH90/E30-E90
HTKSHekw 1x2x0,8 FE180
PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH
FE180 PH90/E30-E90
HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGsekwzo
FE180 PH90/E30-E90
HDGsekwzo 3x2,5 FE180 PH90/E30-
E90 E 30
n x ≥ 2,5 mm2 n ≥ 3 E 30
NHXH FE180 PH90/E90
NHXH 4x1,5 RE FE180 PH90/E90
Cable ladders DUOP 400H60/3N.
Hangers WFLO 500 fixed to ceiling by two dowels PSRO M10x80.
Hangers WFLO 400 with threaded rods PGM10.
Consoles in spacing of 1500 mm.
Loading 20 kg.m-1. Track No. 2.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
NHXH 4x50 RM FE180 PH90/E90 E 90
HTKSHekw FE180 PH90/E30-E90
HTKSHekw 1x2x0,8 FE180
PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH
FE180 PH90/E30-E90
HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGszo
FE180 PH90/E30-E90
HDGszo 3x2,5 FE180 PH90/E30-E90 E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90
NHXCH FE180 PH30/E30
NHXCH 4x1,5/1,5 RE FE180 PH30/E30 Cable trays KCOD 400H60/3N.
Hangers WFLO 500 fixed to ceiling by two dowels PSRO M10x80.
Hangers WFLO 400 with threaded rods PGM10.
Consoles in spacing of 1500 mm.
Loading 10 kg.m-1. Track No. 3.
E 90
n x ≥1,5/1,5 mm2 n ≥ 2 E 60
NHXCH 4x50/25 RM FE180 PH30/E30 E 60
NHXH FE180 PH30/E30
NHXH 4x1,5 RE FE180 PH30/E30 E 90 Without
classification
NHXH FE180 PH90/E90
NHXH 4x1,5 RE FE180 PH90/E90
Cable ladders DUOP 400H60/3N.
Booms WMCO 300 fixed to ceiling by two dowels PSRO M10x80.
Hangers UTMO.
Booms in spacing of 1500 mm.
Loading 20 kg.m-1. Track No. 4.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
NHXH 4x50 RM FE180 PH90/E90 E 90
HTKSH FE180 PH90/E30-E90
HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGszo
FE180 PH90/E30-E90
HDGszo 3x2,5 FE180 PH90/E30-E90 E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
NHXCH FE180 PH90/E90
NHXCH 4x1,5/1,5 RE FE180 PH90/E90
Cable ladders DGOP 400H60/3N.
Booms WMCO 300 fixed to ceiling by two dowels PSRO M10x80.
Hangers UTMO.
Booms in spacing of 1500 mm.
Loading 20 kg.m-1. Track No. 5.
E 90
n x ≥1,5/1,5 mm2 n ≥ 2 E 90
NHXCH 4x50/25 RM FE180 PH90/E90 E 90
HTKSHekw FE180 PH90/E30-E90
HTKSHekw 1x2x0,8 FE180
PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGsekwzo
FE180 PH90/E30-E90
HDGsekwzo 3x2,5 FE180
PH90/E30-E90 E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90
NHXCH FE180 PH90/E90
NHXCH 4x1,5/1,5 RE FE180 PH90/E90 Cable trays KCOD 400H60/3N.
Consoles WPCO 800 fixed to ceiling by two dowels PSRO M10x80.
Booms WWSO 400 with holders UPWO and threaded rods PGM10
with holders USOV.
Consoles in spacing of 1500 mm.
Loading 10 kg.m-1. Track No. 6.
E 90
n x ≥1,5/1,5 mm2 n ≥ 2 E 90
NHXCH 4x50/25 RM FE180 PH90/E90 E 90
NHXH FE180 PH30/E30
NHXH 4x50 RM FE180 PH30/E30 E 30 Without
classification
NHXH FE180 PH30/E30
NHXH 4x1,5 RE FE180 PH30/E30
Cable ladders DUOP 400H60/3N.
Consoles WPCO 800 fixed to ceiling by two dowels PSRO M10x80.
Booms WWSO 400 with holders UPWO and threaded rods PGM10
with holders USOV.
Consoles in spacing of 1500 mm.
Loading 20 kg.m-1. Track No. 7.
Without classification
Without classification
NHXH 4x50 RM FE180 PH30/E30 Without
classification
NHXCH FE180 PH30/E30
NHXCH 4x1,5/1,5 RE FE180 PH30/E30 E 90
n x ≥1,5/1,5 mm2 n ≥ 2 E 60
NHXCH 4x50/25 RM FE180 PH30/E30 E 60
NHXH FE180 PH90/E90
NHXH 4x1,5 RE FE180 PH90/E90
Cable trays KCOJ 400H60/3-E.
Consoles combined of supporting profiles CWP/CWOP40H40/05-E and two threaded rods PGM10-E
with hangers WPPOV-E and dowels PSRO M10x80E.
(All rustles steel).
Consoles in spacing of 1500 mm.
Loading 10 kg.m-1. Track No. 8.
E 90
n x ≥1,5 mm2 n ≥ 2 E 90
NHXH 4x50 RM FE180 PH90/E90 E 90
HTKSHekw FE180 PH90/E30-E90
HTKSHekw 1x2x0,8 FE180
PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH
FE180 PH90/E30-E90
HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGszo
FE180 PH90/E30-E90
HDGszo 3x2,5 FE180 PH90/E30-E90 E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90
NHXH FE180 PH90/E90
NHXH 4x1,5 RE FE180 PH90/E90 Cable ladders DGOD 400H60/3-E.
Consoles combined of supporting profiles CWP/CWOP40H40/05-E and two threaded rods PGM10-E
with hangers WPPOV-E and dowels PSRO M10x80E.
(All rustles steel).
Consoles in spacing of 1500 mm.
Loading 20 kg.m-1. Track No. 9.
E 90
n x ≥1,5 mm2 n ≥ 2 E 90
NHXH 4x50 RM FE180 PH90/E90 E 90
NHXCH FE180 PH90/E90
NHXCH 4x50/25 RM FE180 PH90/E90 E 90 Without
classification
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
HTKSHekw FE180 PH90/E30-E90
HTKSHekw 1x2x0,8 FE180 PH90/E30-E90
Cable ladders DGOD 400H60/3-E.
Consoles combined of supporting profiles CWP/CWOP40H40/05-E and two threaded rods PGM10-E
with hangers WPPOV-E and dowels PSRO M10x80E.
(All rustles steel).
Consoles in spacing of 1500 mm.
Loading 20 kg.m-1. Track No. 9.
E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH
FE180 PH90/E30-E90
HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGsekwzo
FE180 PH90/E30-E90
HDGsekwzo 3x2,5 FE180 PH90/E30-E90
Without classification
Without classification
HDGsekwzo FE180 PH90/E30-E90
HDGsekwzo 3x2,5 FE180
PH90/E30-E90 Clips UEF.
Clips fixed by dowels SRO M6x30.
Clips in spacing of 600 mm.
Ceiling mounting.
Track No. 10.
E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90
HDGszo FE180 PH90/E30-E90
HDGszo 3x2,5 FE180 PH90/E30-E90 E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90
HDGsekwzo FE180 PH90/E30-E90
HDGsekwzo 3x2,5 FE180
PH90/E30-E90 Clips UDF.
Clips fixed by dowels SRO M6x30.
Clips in spacing of 600 mm.
Ceiling mounting.
Track No. 10.
E 30
n x ≥ 2,5 mm2 n ≥ 3 E 30
HDGszo FE180 PH90/E30-E90
HDGszo 3x2,5 FE180 PH90/E30-E90 E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90
NHXH FE180 PH90/E90
NHXH 4x1,5 RE FE180 PH90/E90
Clips UKO1 in the ledges SDOC 400.
Ledges fixed by dowels SRO M6x30.
Clips and ledges in spacing of 600 mm.
Ceiling mounting.
Track No. 11.
E 90
n x 1,5 - 16 mm2 n ≥ 2 E 60
NHXH 4x16 RM FE180 PH90/E90 E 60
NHXCH FE180 PH90/E90
NHXCH 4x1,5/1,5 RE FE180 PH90/E90 E 90 n x 1,5/1,5
- 16/16 mm2 n ≥ 2 E 90
NHXCH 4x16/16 RM FE180 PH90/E90 E 90
HDGsekwzo FE180 PH90/E30-E90
HDGsekwzo 3x2,5 FE180
PH90/E30-E90 E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90 HTKSH
FE180 PH90/E30-E90
HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
NHXCH FE180 PH90/E90
NHXCH 4x1,5/1,5 RE FE180 PH90/E90
Cable holders OZO Holders fixed by dowels
GRO 6x40 in spacing of 600 mm.
Ceiling mounting.
Track No. 12.
E 90
n x ≥1,5/1,5 mm2 n ≥ 2 E 90
NHXCH 4x50/25 RM FE180 PH90/E90 E 90
HTKSHekw FE180 PH90/E30-E90
HTKSHekw 1x2x0,8 FE180
PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH
FE180 PH90/E30-E90
HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
NHXH FE180 PH90/E90
NHXH 4x1,5 RE FE180 PH90/E90 Clips UEF.
Clips fixed by dowels KWBO 6x40.
Clips in spacing of 600 mm.
Ceiling mounting.
Track No. 13.
E 90
n x ≥1,5 mm2 n ≥ 2 E 90
NHXH 4x50 RM FE180 PH90/E90 E 90
NHXCH FE180 PH90/E90
NHXCH 4x1,5/1,5 RE FE180 PH90/E90
Cable ladders DGOP 400H60/3N.
Hangers UTMO fixed to wall by two dowels PSRO M8x75.
Hangers in spacing of 1500 mm.
Clips UKO1 in spacing of 600 mm.
Loading 20 kg.m-1. Wall mounting.
Track No. 14.
E 90
n x ≥1,5/1,5 mm2 n ≥ 2 E 90
NHXCH 4x50/25 RM FE180 PH90/E90 E 90
NHXH FE180 PH90/E90
NHXH 4x1,5 RE FE180 PH90/E90
Cable ladders DGOP 400H60/3N.
Hangers UTMO fixed to wall by two dowels PSRO M8x75.
Hangers in spacing of 1500 mm.
Clips UKO1 in spacing of 600 mm.
Loading 20 kg.m-1. Wall mounting.
Track No. 15.
E 90
n x ≥1,5 mm2 n ≥ 2 E 60
NHXH 4x50 RM FE180 PH90/E90 E 60
HDGszo FE180 PH90/E30-E90
HDGszo 3x2,5 FE180 PH90/E30-E90 E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90
HDGszo FE180 PH90/E30-E90
HDGszo 3x2,5 FE180 PH90/E30-E90
Plastic ledges LS Emiter with clips UDF.
Clips fixed by dowels SRO M6x30.
Clips in spacing of 300 mm.
Wall mounting. Track No. 16.
E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90
HTKSHekw FE180 PH90/E30-E90
HTKSHekw 1x2x0,8 FE180 PH90/E30-E90
Plastic ledges LS Emiter with clips UDF.
Clips fixed by dowels SRO M6x30.
Clips in spacing of 300 mm.
Ceiling mounting.
Track No. 17 - 19.
E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH
FE180 PH90/E30-E90
HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGszo
FE180 PH90/E30-E90
HDGszo 3x2,5 FE180 PH90/E30-E90 E 90
n x ≥ 2,5 mm2 n ≥ 3 E 90
HTKSH FE180 PH90/E30-E90
HTKSH 1x2x0,8 FE180 PH90/E30-E90
Plastic ledges LS Emiter with clips UEF.
Clips fixed by dowels SRO M6x30.
Clips in spacing of 300 mm.
Ceiling mounting. Track No. 20.
E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
HTKSHekw FE180 PH90/E30-E90
HTKSHekw 1x2x0,8 FE180 PH90/E30-E90
Clips KSA.
Clips fixed by dowels SRO M6x30.
Clips in spacing of 600 mm.
Ceiling mounting.
Track No. 21.
E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH
FE180 PH90/E30-E90
HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
NHXH FE180 PH90/E90
NHXH 4x1,5 RE FE180 PH90/E90
Clips KSA.
Clips fixed by threaded rods PGM6 and dowels TRSO M6.
Clips in spacing of 600 mm.
Ceiling mounting.
Track No. 22.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
NHXH 4x50 RM FE180 PH90/E90 E 90