• Nie Znaleziono Wyników

Name of the product: Cable bearing system BAKS

N/A
N/A
Protected

Academic year: 2021

Share "Name of the product: Cable bearing system BAKS "

Copied!
12
0
0

Pełen tekst

(1)

FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-084-15-NURE

Cable bearing system BAKS with cables business TECHNOKABEL S.A.

This is an electronic version of a classification report which was made as a copy of classification report officially issued in a paper form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e.

FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor.

(2)

FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION IN ACCORDANCE WITH DIN 4102-12: 1998-11

FIRES-JR-084-15-NURE

FIRES 149/S-10/08/2015-E FIRES, s.r.o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk

Name of the product: Cable bearing system BAKS

with cables business TECHNOKABEL S.A.

Sponsor: BAKS Kazimierz Sielski ul. Jagodne 5

05-480 Karczew Poland

Prepared by: FIRES, s.r.o.

Approved Body No. SK01 Osloboditeľov 282

059 35 Batizovce Slovak Republic

Task No.: PR-15-0333 Date of issue: 10. 09. 2015

Reports: 5

Copy No.: 2

Distribution list:

Copy No. 1 FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic (electronic version)

Copy No. 2 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland (electronic version)

Copy No. 3 TECHNOKABEL S.A., Nasielska 55, 04-343 Warszawa, Poland (electronic version)

Copy No. 4 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland

Copy No. 5 TECHNOKABEL S.A., Nasielska 55, 04-343 Warszawa, Poland

This expert judgement report with classification may only be used or reproduced in its entirety.

(3)

1. INTRODUCTION

This expert judgement report with classification defines the function in fire classification assigned to element Cable bearing system BAKS with cables business TECHNOKABEL S. A. in accordance with the classes given in DIN 4102 – 12: 1998-11.

This test was carried out according to standard STN 92 0205 and meets requirements of DIN 4102-12: 1998-11. Basic deviation in process and carrying out of test between these standards is in measuring and in control of temperature in the test furnace. According to STN 92 0205, plate thermometers according to EN 1363-1 are used. According to DIN 4102-12: 1998-11, common thermocouples of construction which was used for this measurement till issue of EN 1363-1 are used.

Measurement by plate thermometers acc. to EN 1363-1 can be considered as stricter method of temperature control in test furnace in compare with thermocouples used till issue of EN 1363-1. Therefore, it is possible to use results of test according to STN 92 025 for classification of tested cables according to DIN 4102-12: 1998-11, but not conversely.

This expert judgement report defines field of application which is outside the field of direct application according test standard or outside the field of extended application according to relevant extended application standard. This expert judgement expresses the opinion of the FIRES and is based on the experience or internal rules of FIRES.

This products have already been classified by FIRES, s.r.o. and number of previous classification of function in fire is FIRES-CR-020-09-AUPE, issued on 25. 05. 2009.

2. DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL

The element, Cable bearing system BAKS with power and communication halogen free cables business TECHNOKABEL S. A., is defined as a cable bearing system for power and communication halogen free cables with circuit integrity maintenance.

2.2 PRODUCT DESCRIPTION

The element comprise of cable bearing system BAKS – cable trays KCOD and KCOJ, cable ladders DGOP, DGOD and DUOP, cable holders OZO, ceiling ledges SDOC with clips UKO1, clips UDF, UEF and KSA, and accessories (consoles WPCO, hangers WFLO, booms, WMCO and WWSO, supports CWOP, holders UPWO, UTMO and WPPOVE, threaded rods, dowels etc.) with power and communication non-halogen cables business TECHNOKABEL S. A., type NHXH, NHXCH, HTKSH, HTKSHekw, HDGsżo, HDGsekwżo, with circuit integrity maintenance in fire.

Cable trays KCOD

Cable trays type KCOD…H60N are made from galvanized steel sheet thickness 1,2 mm. Trays are jointed together by two junctions type LPOPH60N (galvanized steel sheet thickness 1,5 mm) and by sheet type BLO…N (galvanized steel sheet thickness 1,0 mm) with screws type SGN M6x12. Trays are used as bearing system for the cables. Tested trays were

KCOD 400H60/3N

.

Cable trays KCOJ…H60E

Cable trays type KCOJ…H60E are made from stainless steel sheet thickness 1,0 mm. Trays are jointed together by two junctions type LPOPH60E (stainless steel sheet thickness 1,5 mm) and by sheet type BLO…E (stainless steel sheet thickness 1,0 mm) with screws type SGN M6x12/E. Trays are used as bearing system for the cables. Tested trays were

KCOJ 400H60/3E

.

Cable ladders DGOP

Cable ladders type DGOP H60 are made from galvanized steel sheet thickness 1,5 mm and spacing of

transoms is 150 mm. Ladders are jointed together by two junction type LDOCH60N (galvanized steel

sheet thickness 2,0 mm) with screws type SGN M8x14. Ladders are used as bearing system for the

cables. Tested ladders were

DGOP 400H60/3N

.

(4)

Cable ladders DGOD…H60E

Cable ladders type DGOD…H60E are made from stainless steel sheet thickness 1,2 mm and spacing of transoms is 150 mm. Ladders are jointed together by two junction type LDOCH60E (stainless steel sheet thickness 2,0 mm) with screws type SGN M8x14/E. Ladders are used as bearing system for the cables.

Tested ladders were

DGOD 400H60/3E

. Cable ladders DUOP

Cable ladders type DUOP H60 are made from galvanized steel sheet thickness 1,2 mm and spacing of transoms is 300 mm. Ladders are jointed together by two junction type LDOCH60N (galvanized steel sheet thickness 2,0 mm) with screws type SGN M8x14. Ladders are used as bearing system for the cables. Tested ladders were

DUOP 400H60/3N

.

Consoles WPCO

Consoles type WPCO are made from galvanized steel sheet thickness 5,0 mm and 2,0 mm. Hangers are used to gripping trays or ladders to ceiling. Tested consoles were WPCO 800.

Booms WMCO

Booms type WMCO are made from galvanized steel sheet thickness 5,0 mm and 2,5 mm. Booms are used to gripping trays or ladders to consoles WPCO or to wall. Tested booms were WMCO 300.

Booms WWSO

Booms type WMCO are made from galvanized steel sheet thickness 2,0 mm. Booms are used to gripping trays or ladders to consoles WPCO or to wall. Tested booms were WWSO 400.

Hangers WFLO

Hangers type WFLO are made from galvanized steel sheet thickness 2,0 mm. Hangers are used to gripping trays or ladders to ceiling or to wall. Tested hangers were WFLO 500 and WFLO 400.

Holders UTMO

Holders type UTMO are made from galvanized steel sheet thickness 2,0 mm. Holders are used to gripping ladders to ceiling or to wall.

Holders UPWO

Holders type UPWO are made from galvanized steel sheet thickness 2,0 mm. Holders are used to gripping threaded rods to ceiling.

Holders WPPOWE

Holders type WPPOVE are made from stainless steel sheet thickness 5,0 mm. Holders are used to gripping threaded rods to ceiling.

Supports CWOP…E

Supports CWOP40H40…E are made from stainless steel sheet thickness 1,5 mm. Supports with threaded rods are used to gripping trays or ladders to ceiling. Tested supports were CWOP40H40/05E.

Ceiling ledges SDOC

Ceiling ledges type SDOC are made from galvanized steel sheet thickness 2,0 mm. Ceiling ledges are used to gripping cables with clips UKO1 to ceiling or to wall.

Cable clips UKO1

Cable clips UKO are made from steel sheet thickness 2,0 mm. Clips UKO1 are used to gripping cables to ledges or to ladders.

Cable holders OZO

Cable holders type OZO are made from steel sheet thickness 1,5 mm. Cable holders are used to gripping cables to ceiling or to wall.

Cable clips UDF and UEF

Cable clips UDF and UEF are made from steel sheet thickness 1,2 mm or 2,0 mm. Clips are used to gripping cables to ceiling or to wall.

Cable clips KSA

Cable clips KSA are made from steel sheet thickness 1,2 mm. Clips are used to gripping cables to ceiling

or to wall.

(5)

Cables

Power cables NHXH, NHXCH, - fire resistant power cables, insulated and sheathed with halogen free compounds, are intended for power supply to fire protection equipment which is to operate in fire conditions (e.g. water pumps in fire extinguishing systems, smoke removing fans).

Halogen free cables shall be applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required.

Functions of the cables are maintained – power is supplied to equipment which must operate in fire conditions and during firefighting. The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive. The cables are suitable for indoor and outdoor installations.

Communication cables HTKSH, HTKSHekw, HDGsżo, HDGsekwżo - fire resistant and halogen free cables are intended for installation in alarm, signalling, transmission, sound warning and similar systems, also for data processing systems and for analogue or digital data transmission in industrial electronics and control applications in objects of sharp fire protection requirements, particularly in fire alarm and fire automatic control systems.

Halogen free cables are applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required.

Functions of the cables are maintained – data are transmitted and power is supplied to equipment which must operate in fire conditions and during firefighting (e.g. emergency lighting). The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive. Cables circuits are protected by an overall electrostatic shield against external electric field interferences.

The cables are suitable for indoor installations.

Used cables by test:

Power cables:

NHXH 4x1,5 RE FE180 PH30/E30 ( 4 x )

NHXH 4x50 RM FE180 PH30/E30 ( 4 x )

NHXCH 4x1,5/1,5 RE FE180 PH30/E30 ( 4 x ) NHXCH 4x50/25 RM FE180 PH30/E30 ( 4 x )

NHXH 4x1,5 RE FE180 PH90/E90 ( 18 x )

NHXH 4x16 RM FE180 PH90/E90 ( 2 x )

NHXH 4x50 RM FE180 PH90/E90 ( 16 x )

NHXCH 4x1,5/1,5 RE FE180 PH90/E90 ( 10 x ) NHXCH 4x16/16 RM FE180 PH90/E90 ( 2 x ) NHXCH 4x50/25 RM FE180 PH90/E90 ( 10 x ) Communication cables:

HTKSH 1x2x0,8 FE180 PH90/E30-E90 ( 20 x ) HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 ( 16 x ) HDGszo 3x2,5 FE180 PH90/E30-E90 ( 16 x ) HDGsekwzo 3x2,5 FE180 PH90/E30-E90 ( 12 x )

Cables were fixed to trays by clips UDF and ladders by clips UKO1 according to the cable diameter.

More detailed information about product construction is shown in the drawings which form an integral part of test report [1]. Drawings were delivered by sponsor.

3. TEST REPORTS AND EXTENDED APPLICATION REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS AND EXTENDED APPLICATION REPORTS

No. Name of laboratory Name of sponsors Test report No. Date of the test Test method

[1] Fires s.r.o., Batizovce, SR

BAKS Kazimierz Sielski,

Karczew, PL

FIRES-FR-

004-09-AUNE 16. 01. 2009 DIN 4102 – 12:

1998-11

(6)

3.2 TEST RESULTS

Test report No.

/Test method

Specimen

No. Cables Track

No.

Time to first failure / interruption of conductor

[1]

DIN 4102-12

1 2 cables NHXCH 4x50/25 RM FE180 PH90/E90 14 90 minutes no failure / interruption 2 2 cables NHXCH 4x1,5/1,5 RE FE180 PH90/E90 14 90 minutes no failure / interruption 3 2 cables NHXH 4x50 RM FE180 PH90/E90 13 90 minutes no failure / interruption 4 2 cables NHXH 4x1,5 RE FE180 PH90/E90 13 90 minutes no failure / interruption 5 NHXH 4x1,5 RE FE180 PH90/E90 9 90 minutes no failure / interruption 6 NHXH 4x1,5 RE FE180 PH90/E90 9 90 minutes no failure / interruption 7 NHXH 4x50 RM FE180 PH90/E90 9 90 minutes no failure / interruption 8 NHXH 4x50 RM FE180 PH90/E90 9 90 minutes no failure / interruption 9 NHXCH 4x50/25 RM FE180 PH90/E90 9 90 minutes no failure / interruption 10 NHXCH 4x50/25 RM FE180 PH90/E90 9 90 minutes no failure / interruption 11 NHXH 4x50 RM FE180 PH90/E90 8 90 minutes no failure / interruption 12 NHXH 4x50 RM FE180 PH90/E90 8 90 minutes no failure / interruption 13 NHXH 4x1,5 RE FE180 PH90/E90 8 90 minutes no failure / interruption 14 NHXH 4x1,5 RE FE180 PH90/E90 8 90 minutes no failure / interruption 15 2 cables NHXCH 4x1,5/1,5 RE FE180 PH90/E90 12 90 minutes no failure / interruption 16 2 cables NHXCH 4x50/25 RM FE180 PH90/E90 12 90 minutes no failure / interruption 17 2 cables NHXCH 4x1,5/1,5 RE FE180 PH30/E30 7 90 minutes no failure / interruption 18 2 cables NHXH 4x1,5 RE FE180 PH30/E30 7 23 minutes

19 2 cables NHXCH 4x50/25 RM FE180 PH30/E30 7 71 minutes 20 2 cables NHXH 4x50 RM FE180 PH30/E30 7 18 minutes

21 2 cables NHXCH 4x1,5/1,5 RE FE180 PH90/E90 6 90 minutes no failure / interruption 22 2 cables NHXCH 4x50/25 RM FE180 PH90/E90 6 90 minutes no failure / interruption 23 2 cables NHXH 4x50 RM FE180 PH30/E30 6 59 minutes

24 NHXCH 4x50/25 RM FE180 PH90/E90 5 90 minutes no failure / interruption 25 NHXCH 4x50/25 RM FE180 PH90/E90 5 90 minutes no failure / interruption 26 NHXCH 4x1,5/1,5 RE FE180 PH90/E90 5 90 minutes no failure / interruption 27 NHXCH 4x1,5/1,5 RE FE180 PH90/E90 5 90 minutes no failure / interruption 28 2 cables NHXH 4x50 RM FE180 PH90/E90 4 90 minutes no failure / interruption 29 2 cables NHXH 4x1,5 RE FE180 PH90/E90 4 90 minutes no failure / interruption 30 2 cables NHXH 4x1,5 RE FE180 PH90/E90 22 90 minutes no failure / interruption 31 2 cables NHXH 4x50 RM FE180 PH90/E90 22 90 minutes no failure / interruption 32 2 cables NHXH 4x1,5 RE FE180 PH90/E90 11 90 minutes no failure / interruption 33 2 cables NHXCH 4x1,5/1,5 RE FE180 PH90/E90 11 90 minutes no failure / interruption 34 2 cables NHXCH 4x16/16 RM FE180 PH90/E90 11 90 minutes no failure / interruption 35 2 cables NHXH 4x16 RM FE180 PH90/E90 11 80 minutes

36 2 cables (N)HXH 1x50 RM FE180 PH90/E90 3 28 minutes

37 2 cables NHXH 4x1,5 RE FE180 PH30/E30 3 90 minutes no failure / interruption 38 2 cables NHXCH 4x50/25 RM FE180 PH30/E30 3 81 minutes

39 2 cables NHXCH 4x1,5/1,5 RE FE180 PH30/E30 3 90 minutes no failure / interruption 40 NHXH 4x50 RM FE180 PH90/E90 2 90 minutes no failure / interruption 41 NHXH 4x50 RM FE180 PH90/E90 2 90 minutes no failure / interruption 42 NHXH 4x1,5 RE FE180 PH90/E90 2 90 minutes no failure / interruption 43 NHXH 4x1,5 RE FE180 PH90/E90 2 90 minutes no failure / interruption 44 NHXH 4x50 RM FE180 PH90/E90 1 90 minutes no failure / interruption 45 NHXH 4x50 RM FE180 PH90/E90 1 90 minutes no failure / interruption 46 NHXH 4x1,5 RE FE180 PH90/E90 1 90 minutes no failure / interruption 47 NHXH 4x1,5 RE FE180 PH90/E90 1 90 minutes no failure / interruption 48 2 cables NHXH 4x50 RM FE180 PH90/E90 15 65 minutes

49 2 cables NHXH 4x1,5 RE FE180 PH90/E90 15 90 minutes no failure / interruption

50 (N)HXH 1x50 RM FE180 PH90/E90 15 57 minutes

51 (N)HXH 1x50 RM FE180 PH90/E90 15 90 minutes no failure / interruption 52A HTKSH 1x2x0,8 FE180 PH90/E30-E90 20 90 minutes no failure / interruption 52B HTKSH 1x2x0,8 FE180 PH90/E30-E90 20 90 minutes no failure / interruption 53A HDGszo 3x2,5 FE180 PH90/E30-E90 19 90 minutes no failure / interruption 53B HDGszo 3x2,5 FE180 PH90/E30-E90 19 90 minutes no failure / interruption 54A 2 cables HTKSH 1x2x0,8 FE180 PH90/E30-E90 12 90 minutes no failure / interruption

(7)

Test report No.

/Test method

Specimen

No. Cables Track

No.

Time to first failure / interruption of conductor

[1]

DIN 4102-12

54B 2 cables HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 12 90 minutes no failure / interruption 55A HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 9 90 minutes no failure / interruption 55B HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 9 90 minutes no failure / interruption 56A HTKSH 1x2x0,8 FE180 PH90/E30-E90 9 90 minutes no failure / interruption 56B HTKSH 1x2x0,8 FE180 PH90/E30-E90 9 90 minutes no failure / interruption 57A HDGsekwzo 3x2,5 FE180 PH90/E30-E90 9 24 minutes

57B HDGsekwzo 3x2,5 FE180 PH90/E30-E90 9 36 minutes

58A HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 58B HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 59A HDGszo 3x2,5 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 59B HDGszo 3x2,5 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 60A HTKSH 1x2x0,8 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 60B HTKSH 1x2x0,8 FE180 PH90/E30-E90 8 90 minutes no failure / interruption 61A 2 cables HDGsekwzo 3x2,5 FE180 PH90/E30-E90 5 90 minutes no failure / interruption 61B 2 cables HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 5 90 minutes no failure / interruption 62A 2 cables HDGszo 3x2,5 FE180 PH90/E30-E90 4 90 minutes no failure / interruption 62B 2 cables HTKSH 1x2x0,8 FE180 PH90/E30-E90 4 90 minutes no failure / interruption 63A 2 cables HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 21 90 minutes no failure / interruption 63B 2 cables HTKSH 1x2x0,8 FE180 PH90/E30-E90 21 90 minutes no failure / interruption 64A 2 cables HTKSH 1x2x0,8 FE180 PH90/E30-E90 11 90 minutes no failure / interruption 64B 2 cables HDGsekwzo 3x2,5 FE180 PH90/E30-E90 11 90 minutes no failure / interruption 65A HDGszo 3x2,5 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 65B HDGszo 3x2,5 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 66A HTKSH 1x2x0,8 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 66B HTKSH 1x2x0,8 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 67A HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 67B HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 2 90 minutes no failure / interruption 68A HDGsekwzo 3x2,5 FE180 PH90/E30-E90 1 90 minutes no failure / interruption 68B HDGsekwzo 3x2,5 FE180 PH90/E30-E90 1 47 minutes

69A HTKSH 1x2x0,8 FE180 PH90/E30-E90 1 90 minutes no failure / interruption 69B HTKSH 1x2x0,8 FE180 PH90/E30-E90 1 90 minutes no failure / interruption 70A HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 1 90 minutes no failure / interruption 70B HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 1 90 minutes no failure / interruption 71A 2 cables HDGszo 3x2,5 FE180 PH90/E30-E90 10 90 minutes no failure / interruption 71B 2 cables HDGsekwzo 3x2,5 FE180 PH90/E30-E90 10 49 minutes

72A 2 cables HDGsekwzo 3x2,5 FE180 PH90/E30-E90 10 90 minutes no failure / interruption 72B 2 cables HDGszo 3x2,5 FE180 PH90/E30-E90 10 90 minutes no failure / interruption 73A 2 cables HTKSHekw 1x2x0,8 FE180 PH90/E30-E90 18 90 minutes no failure / interruption 73B 2 cables HDGszo 3x2,5 FE180 PH90/E30-E90 15 90 minutes no failure / interruption 74A HTKSH 1x2x0,8 FE180 PH90/E30-E90 17 90 minutes no failure / interruption 74B HTKSH 1x2x0,8 FE180 PH90/E30-E90 17 90 minutes no failure / interruption 75A HDGszo 3x2,5 FE180 PH90/E30-E90 16 90 minutes no failure / interruption 75B HDGszo 3x2,5 FE180 PH90/E30-E90 16 90 minutes no failure / interruption

[1] The fire test was discontinued in 96

th

minute at the request of sponsor.

Specimens S1 – S51 were tested by three-phase voltage supply 3 x 230/400V with bulbs 240V / 60 W.

Specimens S52 – S75 were tested by one-phase voltage supply 1 x 110V with LED diodes 3V /0,03W.

Circuit breakers with rating 3 A and performance characteristics B(gL) were used.

4. CLASSIFICATION AND FIELD OF APPLICATION 4.1 REFERENCE OF CLASSIFICATION

This classification has been carried out in accordance with clause 3.2 of DIN 4102 – 12:1998-11.

(8)

4.2 CLASSIFICATION ACCORDING TO DIN 4102-12: 1998-11

The element, cable bearing system BAKS – cable trays KCOD and KCOJ, cable ladders DGOP, DGOD and DUOP, cable holders OZO, ceiling ledges SDOC with clips UKO1, clips UDF, UEF and KSA, and accessories (consoles WPCO, hangers WFLO, booms, WMCO and WWSO, supports CWOP, holders UPWO, UTMO and WPPOVE, threaded rods, dowels etc.) with power and communication non-halogen cables business TECHNOKABEL S. A., type NHXH, NHXCH, HTKSH, HTKSHekw, HDGs żo, HDGsekwżo is classified according to the following combinations of performance parameters and classes as appropriate.

Used cables by test are classified as follows:

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

NHXH FE180 PH90/E90

NHXH 4x1,5 RE FE180 PH90/E90

Cable trays KCOD 400H60/3N.

Hangers WFLO 500 fixed to ceiling by two dowels PSRO M10x80.

Hangers WFLO 400 with threaded rods PGM10.

Consoles in spacing of 1500 mm.

Loading 10 kg.m-1. Track No. 1.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

NHXH 4x50 RM FE180 PH90/E90 E 90

HTKSHekw FE180 PH90/E30-E90

HTKSHekw 1x2x0,8 FE180

PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH

FE180 PH90/E30-E90

HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGsekwzo

FE180 PH90/E30-E90

HDGsekwzo 3x2,5 FE180 PH90/E30-

E90 E 30

n x ≥ 2,5 mm2 n ≥ 3 E 30

NHXH FE180 PH90/E90

NHXH 4x1,5 RE FE180 PH90/E90

Cable ladders DUOP 400H60/3N.

Hangers WFLO 500 fixed to ceiling by two dowels PSRO M10x80.

Hangers WFLO 400 with threaded rods PGM10.

Consoles in spacing of 1500 mm.

Loading 20 kg.m-1. Track No. 2.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

NHXH 4x50 RM FE180 PH90/E90 E 90

HTKSHekw FE180 PH90/E30-E90

HTKSHekw 1x2x0,8 FE180

PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH

FE180 PH90/E30-E90

HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGszo

FE180 PH90/E30-E90

HDGszo 3x2,5 FE180 PH90/E30-E90 E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90

NHXCH FE180 PH30/E30

NHXCH 4x1,5/1,5 RE FE180 PH30/E30 Cable trays KCOD 400H60/3N.

Hangers WFLO 500 fixed to ceiling by two dowels PSRO M10x80.

Hangers WFLO 400 with threaded rods PGM10.

Consoles in spacing of 1500 mm.

Loading 10 kg.m-1. Track No. 3.

E 90

n x ≥1,5/1,5 mm2 n ≥ 2 E 60

NHXCH 4x50/25 RM FE180 PH30/E30 E 60

NHXH FE180 PH30/E30

NHXH 4x1,5 RE FE180 PH30/E30 E 90 Without

classification

NHXH FE180 PH90/E90

NHXH 4x1,5 RE FE180 PH90/E90

Cable ladders DUOP 400H60/3N.

Booms WMCO 300 fixed to ceiling by two dowels PSRO M10x80.

Hangers UTMO.

Booms in spacing of 1500 mm.

Loading 20 kg.m-1. Track No. 4.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

NHXH 4x50 RM FE180 PH90/E90 E 90

HTKSH FE180 PH90/E30-E90

HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGszo

FE180 PH90/E30-E90

HDGszo 3x2,5 FE180 PH90/E30-E90 E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90

(9)

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

NHXCH FE180 PH90/E90

NHXCH 4x1,5/1,5 RE FE180 PH90/E90

Cable ladders DGOP 400H60/3N.

Booms WMCO 300 fixed to ceiling by two dowels PSRO M10x80.

Hangers UTMO.

Booms in spacing of 1500 mm.

Loading 20 kg.m-1. Track No. 5.

E 90

n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 PH90/E90 E 90

HTKSHekw FE180 PH90/E30-E90

HTKSHekw 1x2x0,8 FE180

PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGsekwzo

FE180 PH90/E30-E90

HDGsekwzo 3x2,5 FE180

PH90/E30-E90 E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90

NHXCH FE180 PH90/E90

NHXCH 4x1,5/1,5 RE FE180 PH90/E90 Cable trays KCOD 400H60/3N.

Consoles WPCO 800 fixed to ceiling by two dowels PSRO M10x80.

Booms WWSO 400 with holders UPWO and threaded rods PGM10

with holders USOV.

Consoles in spacing of 1500 mm.

Loading 10 kg.m-1. Track No. 6.

E 90

n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 PH90/E90 E 90

NHXH FE180 PH30/E30

NHXH 4x50 RM FE180 PH30/E30 E 30 Without

classification

NHXH FE180 PH30/E30

NHXH 4x1,5 RE FE180 PH30/E30

Cable ladders DUOP 400H60/3N.

Consoles WPCO 800 fixed to ceiling by two dowels PSRO M10x80.

Booms WWSO 400 with holders UPWO and threaded rods PGM10

with holders USOV.

Consoles in spacing of 1500 mm.

Loading 20 kg.m-1. Track No. 7.

Without classification

Without classification

NHXH 4x50 RM FE180 PH30/E30 Without

classification

NHXCH FE180 PH30/E30

NHXCH 4x1,5/1,5 RE FE180 PH30/E30 E 90

n x ≥1,5/1,5 mm2 n ≥ 2 E 60

NHXCH 4x50/25 RM FE180 PH30/E30 E 60

NHXH FE180 PH90/E90

NHXH 4x1,5 RE FE180 PH90/E90

Cable trays KCOJ 400H60/3-E.

Consoles combined of supporting profiles CWP/CWOP40H40/05-E and two threaded rods PGM10-E

with hangers WPPOV-E and dowels PSRO M10x80E.

(All rustles steel).

Consoles in spacing of 1500 mm.

Loading 10 kg.m-1. Track No. 8.

E 90

n x ≥1,5 mm2 n ≥ 2 E 90

NHXH 4x50 RM FE180 PH90/E90 E 90

HTKSHekw FE180 PH90/E30-E90

HTKSHekw 1x2x0,8 FE180

PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH

FE180 PH90/E30-E90

HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGszo

FE180 PH90/E30-E90

HDGszo 3x2,5 FE180 PH90/E30-E90 E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90

NHXH FE180 PH90/E90

NHXH 4x1,5 RE FE180 PH90/E90 Cable ladders DGOD 400H60/3-E.

Consoles combined of supporting profiles CWP/CWOP40H40/05-E and two threaded rods PGM10-E

with hangers WPPOV-E and dowels PSRO M10x80E.

(All rustles steel).

Consoles in spacing of 1500 mm.

Loading 20 kg.m-1. Track No. 9.

E 90

n x ≥1,5 mm2 n ≥ 2 E 90

NHXH 4x50 RM FE180 PH90/E90 E 90

NHXCH FE180 PH90/E90

NHXCH 4x50/25 RM FE180 PH90/E90 E 90 Without

classification

(10)

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

HTKSHekw FE180 PH90/E30-E90

HTKSHekw 1x2x0,8 FE180 PH90/E30-E90

Cable ladders DGOD 400H60/3-E.

Consoles combined of supporting profiles CWP/CWOP40H40/05-E and two threaded rods PGM10-E

with hangers WPPOV-E and dowels PSRO M10x80E.

(All rustles steel).

Consoles in spacing of 1500 mm.

Loading 20 kg.m-1. Track No. 9.

E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH

FE180 PH90/E30-E90

HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGsekwzo

FE180 PH90/E30-E90

HDGsekwzo 3x2,5 FE180 PH90/E30-E90

Without classification

Without classification

HDGsekwzo FE180 PH90/E30-E90

HDGsekwzo 3x2,5 FE180

PH90/E30-E90 Clips UEF.

Clips fixed by dowels SRO M6x30.

Clips in spacing of 600 mm.

Ceiling mounting.

Track No. 10.

E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90

HDGszo FE180 PH90/E30-E90

HDGszo 3x2,5 FE180 PH90/E30-E90 E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90

HDGsekwzo FE180 PH90/E30-E90

HDGsekwzo 3x2,5 FE180

PH90/E30-E90 Clips UDF.

Clips fixed by dowels SRO M6x30.

Clips in spacing of 600 mm.

Ceiling mounting.

Track No. 10.

E 30

n x ≥ 2,5 mm2 n ≥ 3 E 30

HDGszo FE180 PH90/E30-E90

HDGszo 3x2,5 FE180 PH90/E30-E90 E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90

NHXH FE180 PH90/E90

NHXH 4x1,5 RE FE180 PH90/E90

Clips UKO1 in the ledges SDOC 400.

Ledges fixed by dowels SRO M6x30.

Clips and ledges in spacing of 600 mm.

Ceiling mounting.

Track No. 11.

E 90

n x 1,5 - 16 mm2 n ≥ 2 E 60

NHXH 4x16 RM FE180 PH90/E90 E 60

NHXCH FE180 PH90/E90

NHXCH 4x1,5/1,5 RE FE180 PH90/E90 E 90 n x 1,5/1,5

- 16/16 mm2 n ≥ 2 E 90

NHXCH 4x16/16 RM FE180 PH90/E90 E 90

HDGsekwzo FE180 PH90/E30-E90

HDGsekwzo 3x2,5 FE180

PH90/E30-E90 E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90 HTKSH

FE180 PH90/E30-E90

HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90

NHXCH FE180 PH90/E90

NHXCH 4x1,5/1,5 RE FE180 PH90/E90

Cable holders OZO Holders fixed by dowels

GRO 6x40 in spacing of 600 mm.

Ceiling mounting.

Track No. 12.

E 90

n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 PH90/E90 E 90

HTKSHekw FE180 PH90/E30-E90

HTKSHekw 1x2x0,8 FE180

PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH

FE180 PH90/E30-E90

HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90

(11)

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

NHXH FE180 PH90/E90

NHXH 4x1,5 RE FE180 PH90/E90 Clips UEF.

Clips fixed by dowels KWBO 6x40.

Clips in spacing of 600 mm.

Ceiling mounting.

Track No. 13.

E 90

n x ≥1,5 mm2 n ≥ 2 E 90

NHXH 4x50 RM FE180 PH90/E90 E 90

NHXCH FE180 PH90/E90

NHXCH 4x1,5/1,5 RE FE180 PH90/E90

Cable ladders DGOP 400H60/3N.

Hangers UTMO fixed to wall by two dowels PSRO M8x75.

Hangers in spacing of 1500 mm.

Clips UKO1 in spacing of 600 mm.

Loading 20 kg.m-1. Wall mounting.

Track No. 14.

E 90

n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 PH90/E90 E 90

NHXH FE180 PH90/E90

NHXH 4x1,5 RE FE180 PH90/E90

Cable ladders DGOP 400H60/3N.

Hangers UTMO fixed to wall by two dowels PSRO M8x75.

Hangers in spacing of 1500 mm.

Clips UKO1 in spacing of 600 mm.

Loading 20 kg.m-1. Wall mounting.

Track No. 15.

E 90

n x ≥1,5 mm2 n ≥ 2 E 60

NHXH 4x50 RM FE180 PH90/E90 E 60

HDGszo FE180 PH90/E30-E90

HDGszo 3x2,5 FE180 PH90/E30-E90 E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90

HDGszo FE180 PH90/E30-E90

HDGszo 3x2,5 FE180 PH90/E30-E90

Plastic ledges LS Emiter with clips UDF.

Clips fixed by dowels SRO M6x30.

Clips in spacing of 300 mm.

Wall mounting. Track No. 16.

E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90

HTKSHekw FE180 PH90/E30-E90

HTKSHekw 1x2x0,8 FE180 PH90/E30-E90

Plastic ledges LS Emiter with clips UDF.

Clips fixed by dowels SRO M6x30.

Clips in spacing of 300 mm.

Ceiling mounting.

Track No. 17 - 19.

E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH

FE180 PH90/E30-E90

HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGszo

FE180 PH90/E30-E90

HDGszo 3x2,5 FE180 PH90/E30-E90 E 90

n x ≥ 2,5 mm2 n ≥ 3 E 90

HTKSH FE180 PH90/E30-E90

HTKSH 1x2x0,8 FE180 PH90/E30-E90

Plastic ledges LS Emiter with clips UEF.

Clips fixed by dowels SRO M6x30.

Clips in spacing of 300 mm.

Ceiling mounting. Track No. 20.

E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90

HTKSHekw FE180 PH90/E30-E90

HTKSHekw 1x2x0,8 FE180 PH90/E30-E90

Clips KSA.

Clips fixed by dowels SRO M6x30.

Clips in spacing of 600 mm.

Ceiling mounting.

Track No. 21.

E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSH

FE180 PH90/E30-E90

HTKSH 1x2x0,8 FE180 PH90/E30-E90 E 90

n x 2 x ≥ 0,8 mm n ≥ 1 E 90

NHXH FE180 PH90/E90

NHXH 4x1,5 RE FE180 PH90/E90

Clips KSA.

Clips fixed by threaded rods PGM6 and dowels TRSO M6.

Clips in spacing of 600 mm.

Ceiling mounting.

Track No. 22.

E 90 n x ≥1,5 mm2 n ≥ 2 E 90

NHXH 4x50 RM FE180 PH90/E90 E 90

The element, cable bearing system BAKS – cable trays KCOD and KCOJ, cable ladders DGOP,

DGOD and DUOP, cable holders OZO, ceiling ledges SDOC with clips UKO1, clips UDF, UEF and

KSA, and accessories (consoles WPCO, hangers WFLO, booms, WMCO and WWSO, supports

CWOP, holders UPWO, UTMO and WPPOVE, threaded rods, dowels etc.) with power and

communication non-halogen cables business TECHNOKABEL S. A., type NHXH, NHXCH, HTKSH,

HTKSHekw, HDGsżo, HDGsekwżo are classified to classes according to achieved test results of

tested cables at tracks. Other classification is not allowed.

(12)

4.3 FIELD OF APPLICATION

This classification is valid for the following end use applications:

§ throughout the period during which circuit integrity is to be maintained, neighbouring building components shall not have a negative effect on circuit integrity;

§ classification for type of cable (by cross-sections and number of conductors) is valid only for tested cable types, number and cross-sections of conductors;

§ classification for cable is valid for all numbers and cross-sections of tested cable type;

§ although testing is only carried out on cables arranged horizontally, test results also apply to cables arranged either diagonally or vertically (e.g. risers), as long as the cable system is supported in transitional areas (i.e. where it switches from a horizontal to a vertical arrangement) in such a manner that the cables will not slip or kink at corners;

§ test results of function in fire test of cables tested at standard supporting construction are also applicable for tested standard supporting construction of other producers;

§ test results of function in fire test of cables tested at standard supporting construction are also applicable for cables of other producers tested at standard supporting construction;

§ test results of function in fire test of cables at nonstandard supporting construction are valid only for tested construction with particular tested cable type and are also applicable for supporting construction with smaller spacing of consoles and smaller loading;

§ test results of cables tested in cable trays or ladders are applicable also for cable trays and ladders with particular construction with smaller width as tested with particular smaller loading;

§ test results of cables tested at cable trays or ladders are applicable also for another products trays and ladders (cross, elbow, T-bend, bends and etc.);

§ maximal length of increasing routing shall be 3500 mm with consistent horizontal placing of cable with minimal length of 300 mm (apart from cable bending) and with maximal spacing of clips of 300 mm, eventually the cables are stabilized by cable transmissions at floor or ceiling with particular fire resistance;

§ for vertical systems, the test results obtained for cables mounted singly on the ceiling using single clips apply. Brackets of proven suitability may also be used, as long as their spacing is equal to that of the single clips tested;

§ results of testing single cables on the ceiling apply also to cables mounted horizontally on walls;

§ results of testing bunched cables on a ladder or tray also apply to support construction attached to a wall. However, such constructions required proof of suitability by means of a test certificate or other document issued by an accredited testing laboratory;

§ test results are applicable only for systems without connection elements (e.g. junction box, branch bar).

5. LIMITATIONS

Load-bearing construction elements for fixing of cable systems must be proved for at least the same fire resistance compare to classified function in fire of cable system.

The construction contractor is solely responsible for proper preparation.

This classification document does not represent type approval or certification of the product.

The classification is valid until 10. 09. 2020 provided that the product, field of application and standards and regulations are not changed.

Approved: Signed:

Ing. Štefan Rástocký Miroslav Hudák

leader of the testing laboratory technician of the testing laboratory

Cytaty

Powiązane dokumenty

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clamps and hangers with accessories (consoles, brackets,

The element, Cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clips and hangers with accessories (consoles, brackets, supports, etc.) and power

Consoles combined of assembling profile CWP40H22/05 and threaded rods PG M8 fixed to.. ceiling by anchors HKD

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clips and hangers with accessories (consoles, brackets,

The element, Cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clips and hangers with accessories (consoles, brackets, supports, hangers, etc.)

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable clips with accessories (consoles, brackets, cable clamps, etc.) and power and communication

The element, Cable bearing system BAKS – cable trays, cable ladders, cable clips and clamps with accessories (consoles, brackets, supports, hangers, etc.) and

Product comprise of cable bearing system of company BAKS Kazimierz Sielski – cable trays, mesh trays, ladders, cable clamps with accessories (consoles, brackets, supports,