FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-014-15-NURE
Cable bearing system BAKS with cables business Tele-Fonika Kable
This is an electronic version of a classification report which was made as a copy of classification report officially issued in a paper form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e.
FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor.
FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION IN ACCORDANCE WITH DIN 4102-12: 1998-11
FIRES-JR-014-15-NURE
FIRES 149/S-28/03/2014-E FIRES, s.r.o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk Notified Body No. 1396, Approved Body No. SK01, Member of EGOLF
Name of the product: Cable bearing system BAKS with cables business Tele-Fonika Kable Sponsor: BAKS Kazimierz Sielski
ul. Jagodne 5 05 - 480 Karczew Poland
Prepared by: FIRES, s.r.o.
Approved Body No. SK01 Osloboditeľov 282
059 35 Batizovce Slovak Republic
Task No.: PR-15-0039 Date of issue: 12. 03. 2015
Reports: 5
Copy No.: 2
Distribution list:
Copy No. 1 FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic (electronic version)
Copy No. 2 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland (electronic version)
Copy No. 3 Tele-Fonika Kable sp. z o.o. S.K.A., ul. Wielicka 114, 30-630 Kraków, Poland (electronic version)
Copy No. 4 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland
Copy No. 5 Tele-Fonika Kable sp. z o.o. S.K.A., ul. Wielicka 114, 30-630 Kraków, Poland
1. INTRODUCTION
This expert judgement report with classification defines the function in fire classification assigned to element „Cable bearing system BAKS with cables business Tele-Fonika Kable” in accordance with the classes given in DIN 4102-12: 1998-11.
This test was carried out according to standard STN 92 0205: 2012 and meets requirements of DIN 4102-12: 1998-11. Basic deviation in process and carrying out of test between these standards is in measuring and in control of temperature in the test furnace. According to STN 92 0205: 2012, plate thermometers according to EN 1363-1 are used. According to DIN 4102-12: 1998-11, common thermocouples of construction which was used for this measurement till issue of EN 1363-1 are used.
Measurement by plate thermometers acc. to EN 1363-1 can be considered as stricter method of temperature control in test furnace in compare with thermocouples used till issue of EN 1363-1. Therefore, it is possible to use results of test according to STN 92 025: 2012 for classification of tested cables according to DIN 4102-12: 1998-11, but not conversely.
This expert judgement report defines field of application which is outside the field of direct application according test standard or outside the field of extended application according to relevant extended application standard. This expert judgement expresses the opinion of the FIRES and is based on the experience or internal rules of FIRES.
2. DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL
The element, Cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clamps and hangers with accessories (consoles, brackets, supports, etc.) and power and communication halogen free cables of company Tele-Fonika Kable with circuit integrity maintenance classes.
2.2 PRODUCT DESCRIPTION
Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clamps and hangers with accessories (consoles, brackets, supports, etc.) and power and communication halogen free cables of company Tele-Fonika Kable with circuit integrity maintenance classes.
Cable trays KGJ/KGOJ
Cable trays are made of steel sheet thickness 0,9 mm. Height of side wall is 60 mm and maximum tested width of cable tray is 400 mm. Trays are fixed together by nut bolts SGK M6x12. Maximum tested loading is 20kg.m
-1. Tested tray is KGJ/KGOJ400H60.
Cable trays KGL/KGOL
Cable trays are made of steel sheet thickness 0,7 mm. Height of side wall is 60 mm and maximum tested width of cable tray is 300 mm. Trays are fixed together by nut bolts SGK M6x12. Maximum tested loading is 20kg.m
-1. Cable trays could be covered by cover PKJ made of steel sheet thickness 1,0 mm and fixed to cable tray by clips ZPD H60. Tested tray is KGL/KGOL300H60 together with cover and KGL/KGOL100H60.
Cable trays KFL
Cable trays are made of steel sheet thickness 0,7 mm. Height of side wall is 60 mm and maximum tested width of cable tray is 300 mm. Trays are fixed together by integrated junctions and nut bolts SGK M6x12.
Maximum tested loading is 10kg.m
-1. Tested tray is KFL300H60.
Cable trays KBJ
Cable trays are made of steel sheet thickness 0,9 mm. Trays are not perforated. Height of side wall is
60 mm and maximum tested width of cable tray is 400 mm. Trays are fixed together by nut bolts
SGK M6x12. Maximum tested loading is 20kg.m
-1. Tested tray is KBJ400H60.
FIRES-JR-014-15-NURE
FIRES 149/S-28/03/2014-E Page: 3/10
Cable mesh trays KDS/KDSO
Cable mesh trays are made of steel wire ∅ 4,0 mm and ∅ 4,5 mm. Height of side wall is 60 mm and maximum tested width of cable mesh tray is 400 mm. Mesh trays are fixed together by junctions (USS/USSO). Maximum tested loading is 20kg.m
-1. Tested mesh trays are KDS/KDSO100H60 and KDS/KDSO400H60.
Cable ladders DUP
Cable ladders are made of steel sheet thickness 1,5 mm and spacing of transoms is 300 mm. Height of side wall is 60 mm and maximum tested width of cable ladder is 600 mm. Cable ladders are fixed together by two junctions (LDC/LDOCH60) and nut bolts (SGK M8x14) on sides. Maximum tested loading is 20kg.m
-1. Tested ladder is DUP600H60.
Cable ladders DUD
Cable ladders are made of steel sheet thickness 1,2 mm and spacing of transoms is 300 mm. Height of side wall is 60 mm and maximum tested width of cable ladder is 400 mm. Cable ladders are fixed together by two junctions (LDC/LDOCH60) and nut bolts (SGK M8x14) on sides. Maximum tested loading is 20kg.m
-1. Tested ladder is DUD400H60.
Cable clips KSA
Single cable clips KSA are made of steel sheet 1,2 mm thick. Cable clips are used for fixing of cables directly to wall or ceiling.
Cable hangers
Cable hangers OZ/OZO with dimensions (100 x 120 x 82) mm are made of steel sheet thickness 1,5 mm.
Cable hangers OZS/OZSO with dimensions (52 x 81 x 38) mm are made of steel sheet thickness 0,7 mm.
Cable hangers OZM/OZMO with dimensions (42 x 62 x 33) mm are made of steel sheet thickness 0,7 mm.
Brackets WWS/WWSO
Brackets are made from steel sheet thickness 2,0 mm. Tested brackets are WWS/WWSO300 and WWS/WWSO400.Brackets are used to gripping trays or ladders to ceiling or to wall.
Consoles WPCB
Consoles consist of base plate with dimensions (130 x 45 x 5) mm and support with dimensions (50 x 35 x 2) mm. Consoles are used for gripping of brackets to ceiling.
Supports CWP40H22
Supports CWP40H22 with dimensions (40 x 22) mm are made of steel sheet thickness 1,5 mm.
Beam clips ZSU
Beam clips ZSU are made of steel sheet thickness 1,0 mm and are used for installation of cables to steel beams.
Used cables by test:
Power cables:
(N)HXH FE180/PH90/E90 4x1,5 RE (22x)
(N)HXH FE180/PH90/E90 4x6 RE (4x)
(N)HXH FE180/PH90/E90 4x50 RM (20x)
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE (26x) (N)HXCH FE180/PH90/E90 4x50/25 RM (24x) Communication cables:
Je-H(St)H 1x2x0,8 Bd FE180/E90 (24x)
HDGs 5x1 300/500V (24x)
The length of cables was 5,2 m and 4,0 m from that was exposed to fire.
More detailed information about product construction is shown in the drawings which form an integral part
of test report [1]. Drawings were delivered by sponsor.
3. TEST REPORTS AND EXTENDED APPLICATION REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS AND EXTENDED APPLICATION REPORTS
No. Name of
laboratory Name of sponsor Test report No. Date of the
test Test method [1] FIRES, s.r.o.,
Batizovce, SR
BAKS Kazimierz Sielski, 05 - 480 Karczew, Poland
FIRES-FR-
010-15-AUNE 29. 01. 2015 STN 92 0205
3.2 TEST RESULTS
No./
Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
[1]
STN 92 0205
1 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM
16 90 minutes no failure / interruption 2 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE 80 minutes
3 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM
15 90 minutes no failure / interruption 4 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE 79 minutes
5 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE
14 90 minutes no failure / interruption 6 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM 90 minutes no failure / interruption 7 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE
22 90 minutes no failure / interruption 8 2 cables (N)HXH FE180/PH90/E90 4x50 RM 90 minutes no failure / interruption 9 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE
13
36 minutes 10 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE 35 minutes
11 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM 90 minutes no failure / interruption 12 2 cables (N)HXH FE180/PH90/E90 4x50 RM 90 minutes no failure / interruption 13 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE
12
76 minutes
14 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM 90 minutes no failure / interruption 15 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE 75 minutes
16 2 cables (N)HXH FE180/PH90/E90 4x50 RM 90 minutes no failure / interruption 17 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE
11
90 minutes no failure / interruption 18 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM 90 minutes no failure / interruption 19 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE 89 minutes
20 2 cables (N)HXH FE180/PH90/E90 4x50 RM 90 minutes no failure / interruption 21 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM
9, 10 90 minutes no failure / interruption 22 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE 75 minutes
23 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM
7, 8 90 minutes no failure / interruption 24 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE 86 minutes
25 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM
6 85 minutes 26 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE 32 minutes 27 2 cables (N)HXH FE180/PH90/E90 4x50 RM
5 82 minutes 28 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE 32 minutes 29 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM
21
90 minutes no failure / interruption 30 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE 84 minutes
31 2 cables (N)HXH FE180/PH90/E90 4x50 RM 90 minutes no failure / interruption
32 2 cables (N)HXH FE180/PH90/E90 4x6 RE 36 minutes
33 2 cables (N)HXH FE180/PH90/E90 4x6 RE
20 90 minutes no failure / interruption 34 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE 76 minutes
35 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE
19 74 minutes 36 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE 75 minutes
FIRES-JR-014-15-NURE
FIRES 149/S-28/03/2014-E Page: 5/10
No./
Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
[1]
STN 92 0205
37 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM
4 90 minutes no failure / interruption 38 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE 34 minutes
39 2 cables (N)HXH FE180/PH90/E90 4x50 RM
3 29 minutes 40 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE 37 minutes 41 2 cables (N)HXH FE180/PH90/E90 4x50 RM
18 90 minutes no failure / interruption 42 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE 90 minutes no failure / interruption 43 2 cables (N)HXCH FE180/PH90/E90 4x50/25 RM
2 90 minutes no failure / interruption 44 2 cables (N)HXCH FE180/PH90/E90 4x1,5/1,5 RE 79 minutes
45 2 cables (N)HXH FE180/PH90/E90 4x50 RM
1 90 minutes no failure / interruption 46 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE 70 minutes
47 2 cables (N)HXH FE180/PH90/E90 4x50 RM
17
90 minutes no failure / interruption 48 2 cables (N)HXH FE180/PH90/E90 4x1,5 RE 90 minutes no failure / interruption 52 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90
15 63 minutes
53 2 cables HDGs 5x1 300/500V 62 minutes
54 2 cables HDGs 5x1 300/500V 13 32 minutes
55 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90
22 81 minutes
56 2 cables HDGs 5x1 300/500V 90 minutes no failure / interruption
57 2 cables HDGs 5x1 300/500V 10 84 minutes
58 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90 9 60 minutes 59 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90 7 39 minutes
60 2 cables HDGs 5x1 300/500V 6 30 minutes
61 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90 5 39 minutes 62 2 cables HDGs 5x1 300/500V
21 36 minutes 63 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90 43 minutes 64 2 cables HDGs 5x1 300/500V
20 90 minutes no failure / interruption 65 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90 43 minutes
66 2 cables HDGs 5x1 300/500V
19 90 minutes no failure / interruption 67 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90 64 minutes
68 2 cables HDGs 5x1 300/500V
3 31 minutes 69 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90 38 minutes 70 2 cables HDGs 5x1 300/500V
18
90 minutes no failure / interruption 71 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90 83 minutes
72 2 cables HDGs 5x1 300/500V 2 35 minutes
73 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90 1 90 minutes no failure / interruption 74 2 cables HDGs 5x1 300/500V
17 78 minutes
75 2 cables JE-H(St)H 1x2x0,8 Bd FE180/E90 90 minutes no failure / interruption
The fire test was discontinued in 94
thminute at the request of test sponsor.
Specimens S1 – S48 were tested by three-phase voltage supply 3 x 230/400V with bulbs 240V / 60 W.
Specimens S52 – S75 were tested by one-phase voltage supply 1 x 110V with LED diodes 3V /0,03W.
Circuit breakers with rating 3 A were used.
4. CLASSIFICATION AND FIELD OF APPLICATION 4.1 REFERENCE OF CLASSIFICATION
This classification has been carried out in accordance with clause 3.2 of DIN 4102 – 12: 1998-11.
4.2 CLASSIFICATION ACCORDING TO DIN 4102 – 12: 1998-11
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
(N)HXH FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE
Cable trays KFL300H60.
Consoles WPCB1000 reinforced in place of fixing brackets by
spacer BR55. Brackets WWS/WWSO300.
Loading 10kg.m-1. Consoles in spacing of 1500 mm.
Tracks No. 1 and 2.
E 60 n x ≥1,5 mm2 n ≥ 2 E 60
(N)HXH FE180/PH90/E90 4x50 RM E 90
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE E 60 n x ≥1,5 mm2
n ≥ 2 E 60
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGs
300/500V HDGs 5x1 300/500V E 30
n x ≥ 1,0 mm2 n ≥ 5 E 30 (N)HXH
FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE
Cable ladders DUP600H60.
Consoles WPCB1000, ladders fixed to consoles vertically by
brackets UTM/UTMO.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Tracks No. 3 and 4.
E 30
Without classification
(N)HXH FE180/PH90/E90 4x50 RM Without
classification
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE E 30 n x ≥1,5 mm2
n ≥ 2 E 30
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 30
n x 2 x ≥ 0,8 mm n ≥ 1 E 30 HDGs
300/500V HDGs 5x1 300/500V E 30
n x ≥ 1,0 mm2 n ≥ 5 E 30 (N)HXH
FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE
Cable ladders DUD300H60.
Consoles WPCB1000 reinforced in place of fixing brackets by
spacer BR55. Brackets WWS/WWSO300.
Loading 10kg.m-1. Consoles in spacing of 1500 mm.
Tracks No. 5 and 6.
E 30 n x ≥1,5 mm2 n ≥ 2 E 30
(N)HXH FE180/PH90/E90 4x50 RM E 60
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE E 30 n x ≥1,5 mm2
n ≥ 2 E 30
(N)HXCH FE180/PH90/E90 4x50/25 RM E 60
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 30
n x 2 x ≥ 0,8 mm n ≥ 1 E 30 HDGs
300/500V HDGs 5x1 300/500V E 30
n x ≥ 1,0 mm2 n ≥ 5 E 30
FIRES-JR-014-15-NURE
FIRES 149/S-28/03/2014-E Page: 7/10
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE
Cable trays KGL/KGOL100H60.
Trays are fixed to ceiling by threaded rods PG M6.
Loading 5kg.m-1. Consoles in spacing of 1500 mm.
Tracks No. 7 and 8.
E 60 n x ≥1,5 mm2 n ≥ 2 E 60
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 30
n x 2 x ≥ 0,8 mm n ≥ 1 E 30 (N)HXCH
FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE
Cable mesh trays KDS/KDSO100H60.
Mesh trays are fixed to ceiling by threaded rods PG M6 and center
hanger ZSW.
Loading 5kg.m-1. Consoles in spacing of 1500 mm.
Tracks No. 9 and 10.
E 60 n x ≥1,5 mm2 n ≥ 2 E 60
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 60
n x 2 x ≥ 0,8 mm n ≥ 1 E 60 HDGs
300/500V HDGs 5x1 300/500V E 60
n x ≥ 1,0 mm2 n ≥ 5 E 60 (N)HXH
FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE Cable trays KGJ/KGOJ400H60 with partition PGJ60.
Consoles WPCB1000, spacers BR55, brackets WWS/WWSO400, holders UPW/UPWO and
threaded rods PG M10.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Track No. 11.
E 60 n x ≥1,5 mm2 n ≥ 2 E 60
(N)HXH FE180/PH90/E90 4x50 RM E 90
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE E 90 n x ≥1,5 mm2
n ≥ 2 E 90
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
(N)HXH FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE Cable mesh trays KDS/KDSO400H60 with partition PGJ50.
Consoles WPCB1000, spacers BR55, brackets WWS/WWSO400, holders UPW/UPWO and
threaded rods PG M10.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Track No. 12.
E 60 n x ≥1,5 mm2 n ≥ 2 E 60
(N)HXH FE180/PH90/E90 4x50 RM E 90
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE E 60 n x ≥1,5 mm2
n ≥ 2 E 60
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
(N)HXH FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE
Cable ladders DUD400H60.
Consoles WPCB1000, spacers BR55, brackets WWS/WWSO400, holders UPW/UPWO and
threaded rods PG M10.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Track No. 13.
E 30 n x ≥1,5 mm2 n ≥ 2 E 30
(N)HXH FE180/PH90/E90 4x50 RM E 90
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE E 30 n x ≥1,5 mm2
n ≥ 2 E 30
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
HDGs
300/500V HDGs 5x1 300/500V E 30
n x ≥ 1,0 mm2 n ≥ 5 E 30
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE
Cable trays KGJ/KGOJ400H60.
Consoles combined of supports CWP40H22/05 and threaded rods PG M12.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Track No. 14.
E 90
n x ≥1,5 mm2 n ≥ 2 E 90
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE
Cable trays KBJ400H60.
Consoles combined of supports CWP40H22/05 and threaded rods PG M12.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Track No. 15.
E 60 n x ≥1,5 mm2 n ≥ 2 E 60
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 60
n x 2 x ≥ 0,8 mm n ≥ 1 E 60 HDGs
300/500V HDGs 5x1 300/500V E 60
n x ≥ 1,0 mm2 n ≥ 5 E 60
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE
Cable trays KGL/KGOL300H60 with cover PKJ300.
Consoles combined of supports CWP40H22/05 and threaded rods PG M12.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Track No. 16.
E 60
n x ≥1,5 mm2 n ≥ 2 E 60
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
(N)HXH FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE
Track is made of single cable clips (KSA) fixed to steel beams by
beam clips (ZSU3 13/3) and threaded rods (PG M6)
in spacing of 600 mm.
Track No. 17.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
(N)HXH FE180/PH90/E90 4x50 RM E 90
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGs
300/500V HDGs 5x1 300/500V E 60
n x ≥ 1,0 mm2 n ≥ 5 E 60 (N)HXH
FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE
Track is made of single cable clips (KSA) fixed to steel beams by
beam clamps (ZK8) and threaded rods (PG M6)
in spacing of 600 mm.
Track No. 18.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
(N)HXH FE180/PH90/E90 4x50 RM E 90
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 60
n x 2 x ≥ 0,8 mm n ≥ 1 E 60 HDGs
300/500V HDGs 5x1 300/500V E 90
n x ≥ 1,0 mm2 n ≥ 5 E 90 (N)HXH
FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE
Track is made of cable hangers (OZM/OZMO) fixed to steel beams
by beam clamps (ZK8) and threaded rods (PG M6)
in spacing of 600 mm.
Track No. 19.
E 60 Without
classification (N)HXCH
FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE E 60 Without
classification JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 60
n x 2 x ≥ 0,8 mm n ≥ 1 E 60 HDGs
300/500V HDGs 5x1 300/500V E 90
n x ≥ 1,0 mm2 n ≥ 5 E 90 (N)HXH
FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE
Track is made of cable hangers (OZS/OZSO) fixed to steel beams
by beam clamps (ZK8) and threaded rods (PG M6)
in spacing of 600 mm.
Track No. 20.
E 60 n x 1,5 – 6 mm2 n ≥ 2 E 60
(N)HXH FE180/PH90/E90 4x6 RE E 90
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 30
n x 2 x ≥ 0,8 mm n ≥ 1 E 30 HDGs
300/500V HDGs 5x1 300/500V E 90
n x ≥ 1,0 mm2 n ≥ 5 E 90
FIRES-JR-014-15-NURE
FIRES 149/S-28/03/2014-E Page: 9/10
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
(N)HXH FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x6 RE
Track is made of cable hangers (OZ/OZO) fixed to steel beams by beam clamps (ZK8) and threaded
rods (PG M6) in spacing of 600 mm.
Track No. 21.
E 30 n x ≥ 6 mm2 n ≥ 2 E 30
(N)HXH FE180/PH90/E90 4x50 RM E 90
(N)HXCH FE180 PH90/E90
(N)HXCH FE180/PH90/E90 4x1,5/1,5 RE E 60 n x ≥1,5 mm2
n ≥ 2 E 60
(N)HXCH FE180/PH90/E90 4x50/25 RM E 90
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 30
n x 2 x ≥ 0,8 mm n ≥ 1 E 30 HDGs
300/500V HDGs 5x1 300/500V E 30
n x ≥ 1,0 mm2 n ≥ 5 E 30 (N)HXH
FE180 PH90/E90
(N)HXH FE180/PH90/E90 4x1,5 RE
Track is made of steel pipes (Ø 16 mm, Ø 63 mm) fixed to ceiling by hangers (OBS) in spacing of 1500 mm. Steel pipes are at mid-length separated and there is created the
offset.
Track No. 22.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
(N)HXH FE180/PH90/E90 4x50 RM E 90
JE-H(St)H
FE180/E90 JE-H(St)H 1x2x0,8 Bd FE180/E90 E 60
n x 2 x ≥ 0,8 mm n ≥ 1 E 60 HDGs
300/500V HDGs 5x1 300/500V E 90
n x ≥ 1,0 mm2 n ≥ 5 E 90