FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-114-16-NURE
Cable bearing system BAKS with cables business TECHNOKABEL S.A.
This is an electronic version of a classification report which was made as a copy of classification report officially issued in a paper form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e.
FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor.
FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION IN ACCORDANCE WITH DIN 4102-12: 1998-11
FIRES-JR-114-16-NURE
FIRES 149/S-10/08/2015-E FIRES, s.r.o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk
Name of the product: Cable bearing system BAKS
with cables business TECHNOKABEL S.A.
Sponsor: BAKS Kazimierz Sielski ul. Jagodne 5
05-480 Karczew Poland
Prepared by: FIRES, s.r.o.
Approved Body No. SK01 Osloboditeľov 282
059 35 Batizovce Slovak Republic
Task No.: PR-16-0341 Date of issue: 31. 01. 2017
Reports: 5
Copy No.: 2
Distribution list:
Copy No. 1 FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic (electronic version)
Copy No. 2 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland (electronic version)
Copy No. 3 TECHNOKABEL S.A., Nasielska 55, 04-343 Warszawa, Poland (electronic version)
Copy No. 4 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland
Copy No. 5 TECHNOKABEL S.A., Nasielska 55, 04-343 Warszawa, Poland
This expert judgement report with classification may only be used or reproduced in its entirety.
1. INTRODUCTION
This expert judgement report with classification defines the function in fire classification assigned to element „Cable bearing system BAKS with cables business TECHNOKABEL S. A.” in accordance with the classes given in DIN 4102 – 12: 1998-11.
The test was carried out according to standard STN 92 0205 and meets requirements of DIN 4102-12: 1998-11. Basic deviation in process and carrying out of test between these standards is in measuring and in control of temperature in the test furnace. According to STN 92 0205, plate thermometers according to EN 1363-1 are used. According to DIN 4102-12: 1998-11, common thermocouples of construction which was used for this measurement till issue of EN 1363-1 are used.
Measurement by plate thermometers acc. to EN 1363-1 can be considered as stricter method of temperature control in test furnace in compare with thermocouples used till issue of EN 1363-1. Therefore, it is possible to use results of test according to STN 92 0205 for classification of tested cables according to DIN 4102-12: 1998-11, but not conversely. Identified deviation results in stricter course of test and it can lead to reduced classification of tested cables what is accepted as enhanced security in practice.
This expert judgement report defines field of application which is outside the field of direct application according test standard or outside the field of extended application according to relevant extended application standard. This expert judgement expresses the opinion of the FIRES and is based on the experience or internal rules of FIRES.
2. DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL
The element, Cable bearing system BAKS with power and communication halogen free cables business TECHNOKABEL S. A., is defined as a cable bearing system for power and communication halogen free cables with circuit integrity maintenance.
2.2 PRODUCT DESCRIPTION
The element comprise of cable bearing system BAKS – cable trays KBJ, KCP/KCOP, KFL, KGJ/KGOJ, cable mesh trays KDSZ, cable ladders DUD, DUP, DFP, ceiling ledges SDOP with clips UKO1, clips UDF, KSA and steel tubes RU and accessories (consoles WPCB, supports CWP/CWOP, CMP, hanger WT/WTO, brackets WU/WUO, WWS/WWSO, holders ZM/ZMO, threaded rods PG, dowels etc.) with power and communication non-halogen cables business TECHNOKABEL S. A., type NHXH, NHXHRHX, (N)HXH, (N)HXCH, (N)HXCH-J-SERVO, HTKSH, HTKSHekw and HDGs żo-W with circuit integrity maintenance in fire.
Cable trays KCP/KCOP
Cable trays are made from galvanized steel sheet thickness 1,5 mm. Height of side wall is 60 mm and maximum tested width of cable tray is 600 mm. Trays are fixed together by two junctions LPP/LPOPH60 (galvanized steel sheet thickness 1,5 mm) with nut bolts SGK M6x12 on sides and by junction BL/BLO (galvanized steel sheet thickness 1,0 mm) with nut bolts SGK M6x12 on the bottom. Trays are used as bearing system for the cables. Maximum loading of cable trays is 20 kg.m
-1(
KCOP 400H60) and25 kg.m
-1(KCP600H60
). Tested trays were KCP600H60 and KCP/
KCOP400H60.
Cable trays KFL
Cable trays are made from galvanized steel sheet thickness 0,7 mm. Height of side wall is 60 mm and maximum tested width of cable tray is 300 mm. Trays are fixed together by integrated coupling. Maximum tested loading is 10 kg.m
-1(KFL300H60) and 3 kg.m
-1(KFL50H60). Tested trays are KFL300H60 and KFL50H60.
Cable trays KBJ
Cable trays are made from galvanized steel sheet thickness 1,0 mm without perforation. Height of side
wall is 60 mm and maximum tested width of cable tray is 400 mm. Trays are fixed together by nut bolts
SGK M6x12. Maximum tested loading is 20 kg.m
-1. Tested tray is KBJ400H60.
Cable trays KGJ/KGOJ
Cable trays are made from galvanized steel sheet thickness 1,0 mm. Height of side wall is 60 mm and maximum tested width of cable tray is 400 mm. Trays are fixed together by nut bolts SGK M6x12. Maximum tested loading is 20 kg.m
-1. Tested tray is KGJ/KGOJ400H60.
Cable mesh trays KDSZ
Cable mesh trays are made from galvanized steel wire ∅ 4,5 mm. Height of side wall is 60 mm and maximum tested width of cable mesh tray is 400 mm. Mesh trays are fixed together by integrated coupling. Maximum tested loading is 20 kg.m
-1. Tested mesh trays are KDSZ400H60.
Cable ladders DUP/DUOP
Cable ladders are made from galvanized steel sheet thickness 1,5 mm and spacing of transoms is 300 mm. Height of side wall is 60 mm and maximum tested width of cable ladder is 600 mm. Cable ladders are fixed together by two junctions LDC/LDOCH60 and nut bolts SGK M8x14 on sides. Maximum tested loading is 30 kg.m
-1(DUP600H60, consoles in spacing of 1500 mm) and 20 kg.m
-1(DUP400H60, consoles in spacing of 1700 mm). Tested ladders are DUP400H60 and DUP600H60.
Cable ladder DFP
Cable ladder is made from galvanized steel sheet thickness 1,5 mm and spacing of transoms is 300 mm.
Height of side wall is 60 mm and maximum tested width of cable ladder is 300 mm. Cable ladders are fixed together by integrated coupling. Maximum tested loading is 10 kg.m
-1. Tested ladders are DFP300H60.
Consoles WPCB
Consoles consist of base plate with dimensions (130 x 45 x 5) mm and support with dimensions (50 x 35 x 2) mm. Consoles are used for gripping of brackets to ceiling.
Adjustable brackets WU/WUO
Adjustable brackets are made from galvanized steel sheet thickness 2,0 mm. Tested brackets are WU/WUO300. Brackets are used to gripping trays or ladders to consoles or to wall.
Brackets WWS/WWSO
Brackets are made from galvanized steel sheet thickness 2,0 mm. Tested brackets are WWS/WWSO300.
Brackets are used to gripping trays or ladders to consoles or to wall.
Support CWP/CWOP
Support CWP/CWOP40H40 with dimensions (40 x 40) mm is made from galvanized steel sheet thickness 1,5 mm. Supports with threaded rods are used to gripping trays or ladders to ceiling.
Support CMP
Support CMP41H21 with dimensions (41 x 21) mm and support CMP41H41 with dimensions (41 x 41) mm are made from galvanized steel sheet thickness 1,5 mm. Supports with threaded rods are used to gripping trays or ladders to ceiling.
Partitions PGJ
Partition is made from galvanized steel sheet thickness 1,0 mm. Partition is fixed to cable tray or mesh tray by nut bolts SGK M6x12 or clamping pieces ZS/ZSO and is used for separation of cables.
Partition PGDJ
Partition is made from galvanized steel sheet thickness 1,0 mm. Partition is fixed to cable ladder by nut bolts (SR M6x16) and is used for separation of cables.
Cover PKP
Cover is made from galvanized steel sheet thickness 1,5 mm. Cover is fixed to cable trays by holders ZPN.
Cover PDDP
Cover is made from galvanized steel sheet thickness 1,5 mm. Cover is fixed to cable ladder by holders ZAP2.
Ceiling ledges SDOP
Ceiling ledges type SDOC are made from galvanized steel sheet thickness 1,5 mm. Ceiling ledges are
used to gripping cables with clips UKO1 to ceiling or to wall. Tested ledges were SDOP200.
Cable clips UKO1
Cable clips UKO are made from galvanized steel sheet thickness 2,0 mm. Clips UKO1 are used to gripping cables to ledges or to ladders.
Cable clips KSA
Cable clips KSA are made from galvanized steel sheet thickness 1,2 mm. Clips are used to gripping cables to ceiling or to wall.
Cable clips UDF
Cable clips UDF are made from galvanized steel sheet thickness 1,2 mm or 2,0 mm. Clips are used to gripping cables to ceiling or to wall.
Holders WT/WTO
Holders are made from galvanized steel sheet thickness 2,5 mm. Holders are used to gripping trays or ladders to ceiling.
Holders WC 50
Holders are made from galvanized steel sheet thickness 2,0 mm. Holders are used to gripping trays to ceiling.
Holders ZM/ZMO
Holders are made from galvanized steel sheet thickness 3,0 mm. Holders are used to gripping ladders to supports.
Spacer BR
Spacer BR55 with dimensions (42 x 140) mm is made of steel sheet 1,5 mm thick and is used as reinforcement in place of fixing of bracket to console.
Steel tubes RU
Steel tubes are made from galvanized steel sheet thickness 1,5 mm. Tubes are used to gripping cables to ceiling or to wall.
Threaded rods PG
Threaded rods type PG are made from galvanized steel rods thickness ∅ 6 mm, ∅ 8 mm, ∅ 10 mm or
∅ 12 mm. Threaded rods are used to gripping supports to ceiling. Tested rods were PGM8 and PGM10.
All support systems are made of galvanized steel, according to Sendzimir method PN-EN 10346.
Cables
Power cables NHXH, NHXHRHX, (N)HXH, (N)HXCH and (N)HXCH-J-SERVO - fire resistant power cables, insulated and sheathed with halogen free compounds, are intended for power supply to fire protection equipment which is to operate in fire conditions (e.g. water pumps in fire extinguishing systems, smoke removing fans).
Halogen free cables shall be applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required.
Functions of the cables are maintained – power is supplied to equipment which must operate in fire conditions and during firefighting. The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive. The cables are suitable for indoor and outdoor installations.
Communication cables HTKSH, HTKSHekw and HDGsżo-W - fire resistant and halogen free cables are intended for installation in alarm, signalling, transmission, sound warning and similar systems, also for data processing systems and for analogue or digital data transmission in industrial electronics and control applications in objects of sharp fire protection requirements, particularly in fire alarm and fire automatic control systems.
Halogen free cables are applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required.
Functions of the cables are maintained – data are transmitted and power is supplied to equipment which must operate in fire conditions and during firefighting (e.g. emergency lighting). The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive. Cables circuits are protected by an overall electrostatic shield against external electric field interferences.
The cables are suitable for indoor installations.
Used cables by test:
Power cables:
NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV (10x) NHXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV (10x) NHXHRHX FE180 PH90/E90 1x16 RM 0.6/1 kV (12x) NHXHRHX FE180 PH90/E90 1x240 RM 0.6/1 kV (12x) (N)HXCH FE180 PH90/E90 4x1.5/1.5 RE 0.6/1 kV (6x) (N)HXCH FE180 PH90/E90 4x50/25 RM 0.6/1 kV (6x) (N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV (16x) (N)HXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV (16x) (N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 0.6/1 kV (20x) (N)HXCH-J-SERVO FE180 PH90/E90 4x50 RM 0.6/1 kV (20x) Communication cables:
HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V (28x) HTKSHekw FE180 PH90/E30-E90 1x2x0.8 mm 240 V (6x) HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V (10x) HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 V (10x) HDGsżo-W FE180 PH90/E30-E90 3x1 mm
2300/500 V (12x) The length of cables was 5,5 m and 4,0 m from that was exposed to fire.
Cable penetration through the wall of test furnace was sealed by mineral wool Rockwool.
Loading with cables and line steel weight with length 400 mm was used as the equivalent load.
More detailed information about product construction is shown in the drawings which form an integral part of test report [1]. Drawings were delivered by sponsor.
3. TEST REPORTS AND EXTENDED APPLICATION REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS AND EXTENDED APPLICATION REPORTS
No. Name of laboratory Name of sponsors Test report No. Date of the test Test method
[1]
Fires s.r.o., Batizovce Slovak Republic
BAKS Kazimierz Sielski Karczew, Poland
FIRES-FR-
200-16-AUNE 08. 09. 2016 STN 92 0205
3.2 TEST RESULTS
Test report No.
/Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
[1]
STN 92 0205
1 2 cables (N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 15 90 minutes no failure / interruption 2 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 15 74 minutes
3 2 cables NHXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 15 90 minutes no failure / interruption 4 2 cables NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 15 90 minutes no failure / interruption 5 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 14 90 minutes no failure / interruption 6 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x50 RM 14 88 minutes
7 2 cables (N)HXCH FE180 PH90/E90 4x50/25 RM 0.6/1 kV 14 90 minutes no failure / interruption 8 2 cables (N)HXCH FE180 PH90/E90 4x1.5/1.5 RE 0.6/1 kV 14 76 minutes
9 2 cables (N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 20 90 minutes no failure / interruption 10 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 20 90 minutes no failure / interruption 11 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x50 RM 13 90 minutes no failure / interruption 12 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 13 90 minutes no failure / interruption 13 2 cables (N)HXCH FE180 PH90/E90 4x50/25 RM 0.6/1 kV 12 26 minutes
14 2 cables (N)HXCH FE180 PH90/E90 4x1.5/1.5 RE 0.6/1 kV 12 90 minutes no failure / interruption 15 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 11 87 minutes
16 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x50 RM 11 90 minutes no failure / interruption 17 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 11 36 minutes
Test report No.
/Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
[1]
STN 92 0205
18 2 cables (N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 11 90 minutes no failure / interruption 19 2 cables (N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 10 90 minutes no failure / interruption 20 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 10 90 minutes no failure / interruption 21 2 cables NHXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 10 90 minutes no failure / interruption 22 2 cables NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 10 90 minutes no failure / interruption 23 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x50 RM 9 88 minutes
24 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 9 49 minutes 25 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 8 84 minutes 26 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x50 RM 8 52 minutes
27 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 7 90 minutes no failure / interruption 28 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x50 RM 7 90 minutes no failure / interruption 29 2 cables (N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 6 90 minutes no failure / interruption 30 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 6 90 minutes no failure / interruption 31 2 cables (N)HXCH FE180 PH90/E90 4x1.5/1.5 RE 0.6/1 kV 5 28 minutes
32 2 cables (N)HXCH FE180 PH90/E90 4x50/25 RM 0.6/1 kV 5 90 minutes no failure / interruption 33 2 cables NHXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 5 75 minutes
34 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 5 90 minutes no failure / interruption 35 2 cables (N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 5 25 minutes
36 2 cables NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 5 33 minutes 37 2 cables (N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 4 44 minutes
38 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 4 90 minutes no failure / interruption 39 2 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x50 RM 4 90 minutes no failure / interruption 40 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 4 90 minutes no failure / interruption 41 2 cables NHXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 4 90 minutes no failure / interruption 42 2 cables NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 4 90 minutes no failure / interruption 43 6 cables NHXHRHX FE180 PH90/E90 1x240 RM 0.6/1 kV 3 90 minutes no failure / interruption 44 6 cables NHXHRHX FE180 PH90/E90 1x16 RM 0.6/1 kV 3 90 minutes no failure / interruption 45 6 cables NHXHRHX FE180 PH90/E90 1x16 RM 0.6/1 kV 18 90 minutes no failure / interruption 46 6 cables NHXHRHX FE180 PH90/E90 1x240 RM 0.6/1 kV 18 90 minutes no failure / interruption 47 2 cables NHXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 2 90 minutes no failure / interruption 48 2 cables NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV 2 90 minutes no failure / interruption 49 2 cables (N)HXH-J FE180 PH90/E90 4x50 RM 0.6/1 kV 1 90 minutes no failure / interruption 50 2 cables (N)HXH-J FE180 PH90/E90 4x1,5 RE 0.6/1 kV 1 90 minutes no failure / interruption 51 6 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 17 90 minutes no failure / interruption 6 cables (N)HXCH-J-SERVO FE180 PH90/E90 4x50 RM 17 90 minutes no failure / interruption 52A 2 cables HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V 16 85 minutes
52B 2 cables HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 16 67 minutes
53A HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 16 90 minutes no failure / interruption 53B HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 16 89 minutes
54A HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V 15 65 minutes 54B HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V 15 65 minutes 55A HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 V 15 71 minutes
55B HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 V 15 90 minutes no failure / interruption 56A HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 15 90 minutes no failure / interruption 56B HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 15 81 minutes
57A HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 14 90 minutes no failure / interruption 57B HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 14 90 minutes no failure / interruption 58A HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V 20 86 minutes
58B HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V 20 84 minutes
59A HTKSHekw FE180 PH90/E30-E90 1x2x0.8 mm 240 V 20 90 minutes no failure / interruption 59B HTKSHekw FE180 PH90/E30-E90 1x2x0.8 mm 240 V 20 90 minutes no failure / interruption 60A HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 13 76 minutes
60B HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 13 87 minutes 61A HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V 10 80 minutes
61B HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V 10 90 minutes no failure / interruption 62A HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V 9 28 minutes
62B HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V 9 24 minutes
Test report No.
/Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
63A HTKSHekw FE180 PH90/E30-E90 1x2x0.8 mm 240 V 9 46 minutes [1]
STN 92 0205
63B HTKSHekw FE180 PH90/E30-E90 1x2x0.8 mm 240 V 9 29 minutes
64A HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V 6 90 minutes no failure / interruption 64B HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V 6 90 minutes no failure / interruption 65A HTKSHekw FE180 PH90/E30-E90 1x2x0.8 mm 240 V 6 90 minutes no failure / interruption 65B HTKSHekw FE180 PH90/E30-E90 1x2x0.8 mm 240 V 6 90 minutes no failure / interruption 66A HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V 5 22 minutes
66B HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V 5 23 minutes 67A HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 V 5 27 minutes 67B HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 V 5 21 minutes 68A HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 5 45 minutes 68B HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 5 20 minutes 69A HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 V 4 87 minutes 69B HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 V 4 76 minutes 70A HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V 4 44 minutes 70B HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V 4 41 minutes
71A 10 cables HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V 19 90 minutes no failure / interruption 71B 10 cables HTKSH FE180 PH90/E30-E90 1x2x0.8 mm 240 V 19 90 minutes no failure / interruption 72A HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 V 2 90 minutes no failure / interruption 72B HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 V 2 90 minutes no failure / interruption 73A HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V 2 90 minutes no failure / interruption 73B HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V 2 90 minutes no failure / interruption 74A HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 1 90 minutes no failure / interruption 74B HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V 1 90 minutes no failure / interruption
[1] The fire test was discontinued in 93
rdminute at the request of test sponsor.
Specimens S1 – S51 were tested by three-phase voltage supply 3 x 230/400V with bulbs 240V / 60 W.
Specimens S52 – S74 were tested by one-phase voltage supply 1 x 110V with LED diodes 3V /0,03W.
Circuit breakers with rating 3 A and performance characteristics B(gL) were used.
4. CLASSIFICATION AND FIELD OF APPLICATION
4.1 CLASSIFICATION ACCORDING TO DIN 4102-12: 1998-11
The element, cable bearing system BAKS – cable trays KBJ, KCP/KCOP, KFL, KGJ/KGOJ, cable mesh trays KDSZ, cable ladders DUD, DUP, DFP, ceiling ledges SDOP with clips UKO1, clips UDF, KSA and steel tubes RU and accessories (consoles WPCB, supports CWP/CWOP, CMP, hanger WT/WTO, brackets WU/WUO, WWS/WWSO, holders ZM/ZMO, threaded rods PG, dowels etc.) with power and communication non-halogen cables business TECHNOKABEL S. A., type NHXH, NHXHRHX, (N)HXH, (N)HXCH, (N)HXCH-J-SERVO, HTKSH, HTKSHekw and HDGs żo-W is classified according to the following combinations of performance parameters and classes as appropriate.
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
(N)HXH FE180 PH90/E90
(N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable trays KFL300H60.
Brackets WU/WUO300.
Brackets in spacing 1500 mm.
Loading 10 kg.m-1. Wall mounting.
Non-standard track No. 1.
E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 (N)HXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 90
HDGsżo-W FE180 PH90/E30-E90
HDGsżo-W FE180 PH90/E30-E90
3x1 mm2 300/500 V E 90
n x ≥ 1,0 mm2 n ≥ 3 E 90
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
NHXH FE180 PH90/E90
NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable trays KFL300H60.
Brackets WU/WUO300.
Brackets in spacing 1500 mm.
Loading 10 kg.m-1. Wall mounting.
Non-standard track No. 2.
E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 NHXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 90
HTKSH FE180 PH90/E30-E90
HTKSH FE180 PH90/E30-E90
1x2x1.2 mm 240 V E 90
n x 2 x ≥ 1,2 mm n ≥ 2 E 90 HTKSHekw
FE180 PH90/E30-E90
HTKSHekw FE180 PH90/E30-E90
1x2x1.2 mm 240 V E 90
n x 2 x ≥ 1,2 mm n ≥ 2 E 90
NHXHRHX FE180 PH90/E90
NHXHRHX FE180 PH90/E90 1x16 RM 0.6/1 kV
In cable ladders DUP600H60 with partitions PGDJH50
and covers PDDP600.
Consoles combined of horizontal supports CWP/CWOP40H40/07 and two threaded rods PGM10.
Consoles in spacing 1500 mm.
Loading 30 kg.m-1. Ceiling mounting.
Non-standard track No. 3.
E 90
n x ≥ 16 mm2 n = 1 E 90 NHXHRHX FE180 PH90/E90
1x240 RM 0.6/1 kV E 90
NHXH FE180 PH90/E90
NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable trays KCP600H60 with partitions PGJH60
and covers PKP600.
Consoles combined of horizontal supports CWP/CWOP40H40/07 and two threaded rods PGM10.
Consoles in spacing 1500 mm.
Loading 25 kg.m-1. Ceiling mounting.
Non-standard track No. 4.
E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 NHXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 90
(N)HXH FE180 PH90/E90
(N)HXH-J FE180 PH90/E90 4x1.5 RE
0.6/1 kV E 30
n x ≥ 1,5 mm2 n ≥ 2 E 30 (N)HXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 90
(N)HXCH SERVO
FE180 PH90/E90
(N)HXCH-J-SERVO FE180 PH90/E90
4x1.5 RE 0.6/1 kV E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 (N)HXCH-J-SERVO FE180 PH90/E90
4x50 RM 0.6/1 kV E 90
HTKSH FE180 PH90/E30-E90
HTKSH FE180 PH90/E30-E90
1x2x1.2 mm 240 V E 30
n x 2 x ≥ 1,2 mm n ≥ 2 E 30 HTKSHekw
FE180 PH90/E30-E90
HTKSHekw FE180 PH90/E30-E90
1x2x1.2 mm 240 V E 60
n x 2 x ≥ 1,2 mm n ≥ 2 E 60
NHXH FE180 PH90/E90
NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable ladders DUP600H60 with partitions PGDJH50
and covers PDDP600.
Consoles combined of horizontal supports CWP/CWOP40H40/07 and two threaded rods PGM10.
Consoles in spacing 1500 mm.
Loading 30 kg.m-1. Ceiling mounting.
Non-standard track No. 5.
E 30
n x ≥ 1,5 mm2 n ≥ 2 E 30 NHXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 60
(N)HXH FE180 PH90/E90
(N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV
Without classification
Without classification (N)HXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 90
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
(N)HXCH FE180 PH90/E90
(N)HXCH FE180 PH90/E90 4x1.5/1.5 RE 0.6/1 kV
In cable ladders DUP600H60 with partitions PGDJH50
and covers PDDP600.
Consoles combined of horizontal supports CWP/CWOP40H40/07 and two threaded rods PGM10.
Consoles in spacing 1500 mm.
Loading 30 kg.m-1. Ceiling mounting.
Non-standard track No. 5.
Without classification
Without classification (N)HXCH FE180 PH90/E90 4x50/25 RM
0.6/1 kV E 90
HTKSH FE180 PH90/E30-E90
HTKSH FE180 PH90/E30-E90 1x2x1.2 mm 240 V
Without classification
Without classification
HTKSHekw FE180 PH90/E30-E90
HTKSHekw FE180 PH90/E30-E90 1x2x1.2 mm 240 V
Without classification
Without classification HDGsżo-W
FE180 PH90/E30-E90
HDGsżo-W FE180 PH90/E30-E90 3x1 mm2 300/500 V
Without classification
Without classification
(N)HXH FE180 PH90/E90
(N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV
Straight line track without bending.
In cable trays KFL50H60.
Hanger WT/WTO120M6 with threaded rods PGM6
and holders WC50.
Hangers in spacing of 1500 mm.
Loading 3 kg.m-1. Non-standard track No. 6.
E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 (N)HXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 90
HTKSH FE180 PH90/E30-E90
HTKSH FE180 PH90/E30-E90
1x2x0,8 mm 240 V E 90
n x 2 x ≥ 0,8 mm n ≥ 2 E 90 HTKSHekw
FE180 PH90/E30-E90
HTKSHekw FE180 PH90/E30-E90
1x2x0,8 mm 240 V E 90
n x 2 x ≥ 0,8 mm n ≥ 2 E 90
(N)HXCH SERVO
FE180 PH90/E90
(N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable trays KFL300H60 with partitions PGJH60.
Consoles WPCB1000.
Brackets WWS/WWSO300.
Consoles in spacing of 1500 mm.
Loading 10 kg.m-1. Non-standard track No. 7.
E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 (N)HXCH-J-SERVO FE180 PH90/E90
4x50 RM 0.6/1 kV E 90
(N)HXCH SERVO
FE180 PH90/E90
(N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable trays DFP300H60 with partitions PGDJH50.
Consoles WPCB1000.
Brackets WWS/WWSO300.
Consoles in spacing of 1500 mm.
Loading 10 kg.m-1. Non-standard track No. 8.
E 60
n x ≥ 1,5 mm2 n ≥ 2 E 30 (N)HXCH-J-SERVO FE180 PH90/E90
4x50 RM 0.6/1 kV E 30
(N)HXCH SERVO
FE180 PH90/E90
(N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable trays KBJ400H60.
Consoles combined of horizontal supports CMP41H21/05 and two
threaded rods PGM8.
Consoles in spacing of 1500 mm.
Loading 20 kg.m-1. Non-standard track No. 9.
E 30
n x ≥ 1,5 mm2 n ≥ 2 E 30 (N)HXCH-J-SERVO FE180 PH90/E90
4x50 RM 0.6/1 kV E 60
HTKSH FE180 PH90/E30-E90
HTKSH FE180 PH90/E30-E90 1x2x0,8 mm 240 V
Without classification
Without classification
HTKSHekw FE180 PH90/E30-E90
HTKSHekw FE180 PH90/E30-E90 1x2x0,8 mm 240 V
Without classification
Without classification
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
NHXH FE180 PH90/E90
NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable ladder DUD400H60 fixed to ceiling at upside down position by hangers UTM/UTMO
and anchors PSRO M8x75 in spacing of 1500 mm.
Cables fixed to ladders by cable clamps UK1/UKO1 in spacing of 600 mm.
Loading 20 kg.m-1. Non-standard track No. 10.
E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 NHXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 90
(N)HXH FE180 PH90/E90
(N)HXH-J FE180 PH90/E90 4x1.5 RE
0.6/1 kV E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 (N)HXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 90
HTKSH FE180 PH90/E30-E90
HTKSH FE180 PH90/E30-E90
1x2x0,8 mm 240 V E 60
n x 2 x ≥ 0,8 mm n ≥ 2 E 60
(N)HXH FE180 PH90/E90
(N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable mash trays KDSZ400H60.
Consoles combined of horizontal supports CWP40H22/05 and two
threaded rods PGM10.
Consoles in spacing of 1500 mm.
Loading 20 kg.m-1. Non-standard track No. 11.
E 90
n x ≥ 1,5 mm2 n ≥ 2 E 30 (N)HXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 30
(N)HXCH SERVO
FE180 PH90/E90
(N)HXCH-J-SERVO FE180 PH90/E90
4x1.5 RE 0.6/1 kV E 60
n x ≥ 1,5 mm2 n ≥ 2 E 60 (N)HXCH-J-SERVO FE180 PH90/E90
4x50 RM 0.6/1 kV E 90
(N)HXCH FE180 PH90/E90
(N)HXCH FE180 PH90/E90 4x1.5/1.5 RE 0.6/1 kV
In cable mash trays KDSZ400H60.
Consoles combined of horizontal supports CWP40H22/05 and two
threaded rods PGM10.
Consoles in spacing of 1500 mm.
Loading 20 kg.m-1. Non-standard track No. 12.
E 90
Without classification (N)HXCH FE180 PH90/E90 4x50/25 RM
0.6/1 kV
Without classification
(N)HXCH SERVO
FE180 PH90/E90
(N)HXCH-J-SERVO FE180 PH90/E90
4x1.5 RE 0.6/1 kV In cable trays KGJ/KGOJ 400H60.
Consoles combined of horizontal supports CWP40H22/05 and two
threaded rods PGM10.
Consoles in spacing of 1500 mm.
Loading 20 kg.m-1. Non-standard track No. 13.
E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 (N)HXCH-J-SERVO FE180 PH90/E90
4x50 RM 0.6/1 kV E 90
HDGsżo-W FE180 PH90/E30-E90
HDGsżo-W FE180 PH90/E30-E90
3x1 mm2 300/500 V E 60
n x ≥ 1,0 mm2 n ≥ 3 E 60
(N)HXCH FE180 PH90/E90
(N)HXCH FE180 PH90/E90 4x1.5/1.5 RE 0.6/1 kV
In cable trays KCP/KCOP400H60.
Consoles combined of horizontal supports CMP41H41/05 and two
threaded rods PGM10.
Consoles in spacing of 1700 mm.
Loading 20 kg.m-1. Non-standard track No. 14.
E 60
n x ≥ 1,5 mm2 n ≥ 2 E 60 (N)HXCH FE180 PH90/E90 4x50/25 RM
0.6/1 kV E 90
(N)HXCH SERVO
FE180 PH90/E90
(N)HXCH-J-SERVO FE180 PH90/E90
4x1.5 RE 0.6/1 kV E 90
n x ≥ 1,5 mm2 n ≥ 2 E 60 (N)HXCH-J-SERVO FE180 PH90/E90
4x50 RM 0.6/1 kV E 60
HDGsżo-W FE180 PH90/E30-E90
HDGsżo-W FE180 PH90/E30-E90
3x1 mm2 300/500 V E 90
n x ≥ 1,0 mm2 n ≥ 3 E 90
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
NHXH FE180 PH90/E90
NHXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable ladders DUP400H60.
Consoles combined of horizontal supports CMP41H41/05 and two
threaded rods PGM10.
Consoles in spacing of 1700 mm.
Loading 20 kg.m-1. Non-standard track No. 15.
E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 NHXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 90
(N)HXH FE180 PH90/E90
(N)HXH-J FE180 PH90/E90 4x1.5 RE
0.6/1 kV E 90
n x ≥ 1,5 mm2 n ≥ 2 E 60 (N)HXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 60
HTKSH FE180 PH90/E30-E90
HTKSH FE180 PH90/E30-E90
1x2x1.2 mm 240 V In cable ladders DUP400H60.
Consoles combined of horizontal supports CMP41H41/05 and two
threaded rods PGM10.
Consoles in spacing of 1700 mm.
Loading 20 kg.m-1. Non-standard track No. 15.
E 60
n x 2 x ≥ 1,2 mm n ≥ 2 E 60 HTKSHekw
FE180 PH90/E30-E90
HTKSHekw FE180 PH90/E30-E90
1x2x1.2 mm 240 V E 60
n x 2 x ≥ 1,2 mm n ≥ 2 E 60 HDGsżo-W
FE180 PH90/E30-E90
HDGsżo-W FE180 PH90/E30-E90
3x1 mm2 300/500 V E 60
n x ≥ 1,0 mm2 n ≥ 3 E 60 HTKSH
FE180 PH90/E30-E90
HTKSH FE180 PH90/E30-E90
1x2x1.2 mm 240 V In cable trays KGJ/KGOJ 400H60.
Consoles combined of horizontal supports CMP41H21/05 and two
threaded rods PGM10.
Consoles in spacing of 1500 mm.
Loading 20 kg.m-1. Non-standard track No. 16.
E 60
n x 2 x ≥ 1,2 mm n ≥ 2 E 60 HTKSHekw
FE180 PH90/E30-E90
HTKSHekw FE180 PH90/E30-E90
1x2x1.2 mm 240 V E 60
n x 2 x ≥ 1,2 mm n ≥ 2 E 60 HDGsżo-W
FE180 PH90/E30-E90
HDGsżo-W FE180 PH90/E30-E90
3x1 mm2 300/500 V E 60
n x ≥ 1,0 mm2 n ≥ 3 E 60
(N)HXCH SERVO
FE180 PH90/E90
3 cables
(N)HXCH-J-SERVO FE180 PH90/E90 4x1.5 RE 0.6/1 kV
In cable clips KSA with threaded rods PGM6 (100 mm) or PGM8 (100 mm) fixed at ceiling
to anchors TRSO.
Clips in spacing of 600 mm.
Loading by tested cables.
Non-standard track No. 17.
E 90 max. 3 cables in one clip n x ≥ 1,5 mm2
n ≥ 2 E 90 3 cables
(N)HXCH-J-SERVO FE180 PH90/E90 4x50 RM 0.6/1 kV
E 90
NHXHRHX FE180 PH90/E90
NHXHRHX FE180 PH90/E90 1x16 RM 0.6/1 kV
In cable clips UDF fixed at ceiling to anchors
SRO M6x30.
Clips in spacing of 600 mm.
Loading by tested cables.
Non-standard track No. 18.
E 90
n x ≥ 16 mm2 n = 1 E 90 NHXHRHX FE180 PH90/E90
1x240 RM 0.6/1 kV E 90
HTKSH FE180 PH90/E30-E90
10 cables in one clip
HTKSH FE180 PH90/E30-E90 1x2x0,8 mm 240 V
In cable clips UKO1 in the ledges SDOP200.
Clips in spacing of 600 mm.
Loading by tested cables.
Non-standard track No. 19.
E 90
max. 10 cables in one clip n x 2 x ≥ 0,8 mm
n ≥ 2 E 90
(N)HXH FE180 PH90/E90
(N)HXH-J FE180 PH90/E90 4x1.5 RE 0.6/1 kV
Straight line track without bending.
In steel tubes RU in clips OBS with threaded rods PGM6 (100 mm) or PGM8 (100 mm) fixed at ceiling
to anchors TRSO.
Clips in spacing of 1200 mm.
Loading by tested cables.
Non-standard track No. 20.
E 90
n x ≥ 1,5 mm2 n ≥ 2 E 90 (N)HXH-J FE180 PH90/E90 4x50 RM
0.6/1 kV E 90
HTKSH FE180 PH90/E30-E90
HTKSH FE180 PH90/E30-E90
1x2x0,8 mm 240 V E 60
n x 2 x ≥ 0,8 mm n ≥ 2 E 60 HTKSHekw
FE180 PH90/E30-E90
HTKSHekw FE180 PH90/E30-E90
1x2x0,8 mm 240 V E 90
n x 2 x ≥ 0,8 mm n ≥ 2 E 90