FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-038-14-NURE
Cable bearing system BAKS with cables business Zaklady Kablowe BITNER Celina Bitner with fixing accessories of RAWLPLUG S.A.
This is an electronic version of a classification report which was made as a copy of classification report officially issued in a paper form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e.
FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor.
FIRES 004/S2-20/12/2012-E-el
FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION IN ACCORDANCE WITH DIN 4102-12: 1998-11
FIRES-JR-038-14-NURE
FIRES 149/S-28/03/2014-E FIRES, s.r.o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk Notified Body No. 1396, Approved Body No. SK01, Member of EGOLF
Name of the product: Cable bearing system BAKS with cables business Zaklady Kablowe BITNER Celina Bitner with fixing accessories of RAWLPLUG S.A.
Sponsor: BAKS Kazimierz Sielski ul. Jagodne 5
05 - 480 Karczew Poland
Prepared by: FIRES, s.r.o.
Approved Body No. SK01 Osloboditeľov 282
059 35 Batizovce Slovak Republic
Task No.: PR-14-0129 Date of issue: 27. 05. 2014
Reports: 7
Copy No.: 2
Distribution list:
Copy No. 1 FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic (electronic version)
Copy No. 2 BAKS Kazimierz Sielski, ul. Jagodne 5, 05 - 480 Karczew, Poland (electronic version)
Copy No. 3 Zakłady Kablowe BITNER Celina Bitner, Friedleina 3/3, 30 009 Kraków, Poland (electronic version)
Copy No. 4 RAWLPLUG S.A., Kwidzyńska 6, 51 – 416 Wrocław, Poland (electronic version) Copy No. 5 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland
Copy No. 6 Zakłady Kablowe BITNER Celina Bitner, Friedleina 3/3, 30 009 Kraków, Poland
Copy No. 7 RAWLPLUG S.A., Kwidzyńska 6, 51 – 416 Wrocław, Poland
1. INTRODUCTION
This expert judgement report with classification defines the function in fire classification assigned to element „Cable bearing system BAKS with cables business Zaklady Kablowe BITNER Celina Bitner with fixing accessories of RAWLPLUG S.A.” in accordance with the classes given in DIN 4102-12: 1998-11.
This test was carried out according to standard STN 92 0205: 2012 and meets requirements of DIN 4102-12: 1998-11. Basic deviation in process and carrying out of test between these standards is in measuring and in control of temperature in the test furnace. According to STN 92 0205: 2012, plate thermometers according to EN 1363-1 are used. According to DIN 4102-12: 1998-11, common thermocouples of construction which was used for this measurement till issue of EN 1363-1 are used.
Measurement by plate thermometers acc. to EN 1363-1 can be considered as stricter method of temperature control in test furnace in compare with thermocouples used till issue of EN 1363-1. Therefore, it is possible to use results of test according to STN 92 025: 2012 for classification of tested cables according to DIN 4102-12: 1998-11, but not conversely.
This expert judgement report defines field of application which is outside the field of direct application according test standard or outside the field of extended application according to relevant extended application standard. This expert judgement expresses the opinion of the FIRES and is based on the experience or internal rules of FIRES.
2. DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL
The element, Cable bearing system BAKS with cables business Zaklady Kablowe BITNER Celina Bitner with fixing accessories of RAWLPLUG S.A., is defined as a cable bearing system for power and communication halogen free cables with circuit integrity maintenance.
2.2 PRODUCT DESCRIPTION
Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable clips with accessories (consoles, brackets, cable clamps, etc.) and power and communication halogen free cables of Zaklady Kablowe BITNER Celina Bitner company with fixing accessories (anchors, screws, etc.) of RAWLPLUG S.A..
Cable trays
Cable trays type KGJ/KGOJ…H60 are made from steel sheet thickness 0,9 mm.
Cable trays type KGL/KGOL…H60 are made from steel sheet thickness 0,7 mm.
Cable trays type KBL…H60 (trays without perforation) are made from steel sheet thickness 0,7 mm.
Trays are connected together and fixed by screws (SGK M6x12).
Cable trays type KCP/KCOP…H60 are made from steel sheet thickness 1,5 mm. Trays are jointed together by two junctions (LPP/LPOPH60 - steel sheet 1,5 mm thick) on sides and by junction (BL/BLO…
- steel sheet 1,0 mm thick) on the bottom and with screws (SGK M6x12).
Trays are used as a bearing system for the cables.
Cable ladders
Cable ladders type DGOP…H60N are made from steel sheet thickness 1,5 mm and spacing of transoms is 150 mm. Ladders are jointed together by two junctions (LDC/LDOCH60 - steel sheet 1,5 mm thick) on sides and by screws (SGK M8x14).
Cable ladders type DUD/DUOD…H60 are made from steel sheet thickness 1,2 mm and spacing of transoms is 300 mm. Ladders are jointed together by two junctions (LDC/LDOCH60 - steel sheet 1,5 mm thick) on sides and by screws (SGK M8x14).
Cable ladders are used as bearing system for the cables.
FIRES-JR-038-14-NURE
FIRES 149/S-28/03/2014-E Page: 3/10
Cable clips
Single cable clips UDF are made of steel sheet 1,2 mm thick. Cable clips are used for fixing of cables directly to wall or ceiling.
Cable clamps
Cable clamps UK1/UKO1 are made of steel sheet 2,0 mm thick. Cable clamps are used for fixing of cables to cable ladders (e.g. DGOP, DUP/DUOP) or assembling profiles (SDOP).
Brackets
Brackets type WMC/WMCO… are made from steel sheet thickness 2,5 mm and 5 mm.
Brackets type WWS/WWSO… are made from steel sheet thickness 2,0 mm.
Brackets type WWCT/WWCTO… are made from steel sheet thickness 3,0 mm and 8,0 mm.
Brackets are used to gripping trays or ladders to ceiling or to wall.
Assembling profiles
Assembling profiles type CWP/CWOP40H40 and CWP40H22 are made from steel sheet thickness 1,5 mm. Assembling profiles are used to gripping trays or ladders.
Assembling profiles type CT70H50 are made from steel sheet thickness 3,0 mm. Profiles are used for suspension tracks for fixing of brackets.
Assembling profiles type SDOP… are made from steel sheet thickness 1,5 mm. Profiles are used for gripping of cables to ceiling or wall by cable clamps UK1/UKO1.
Ceiling suspension
Ceiling suspension PSEN is made from steel 4,0 mm thick. Suspension is used for fixing assembling profiles CT70H50 to ceiling.
Consoles
Consoles type WPCW/WPCO… are made from steel sheet thickness 2,0 mm and 6,0 mm.
Used cables by test:
Power cables:
NHXH 4x1,5RE FE180/E90 0,6/1kV (4x) NHXH 4x50RM FE180/E90 0,6/1kV (4x) NHXCH 4x1,5RE/1,5 FE180/E90 0,6/1kV (4x) NHXCH 4x50RM/25 FE180/E90 0,6/1kV (4x) (N)HXH 4x1,5RE FE180/E90 0,6/1kV (4x) (N)HXH 4x50RM FE180/E90 0,6/1kV (4x) (N)HXCH 4x1,5RE/1,5 FE180/E90 0,6/1kV (4x) (N)HXCH 4x50RM/25 FE180/E90 0,6/1kV (4x) BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV (16x) BiTflame 1000 4x50RM FE180/E90 0,6/1kV (16x) BiTflame 1000 C 4x1,5RE FE180/E90 0,6/1kV (8x) BiTflame 1000 C 4x50RM FE180/E90 0,6/1kV (8x) BiTservo
®FS 4G1,5 FE180/E90 0,6/1kV (10x) BiTservo
®FS 4G50 FE180/E90 0,6/1kV (10x) Communication cables:
HTKSH 1x2x0,8 FE180/PH90/E90 225V (10x) HTKSHekwf 1x2x0,8 FE180/PH90/E90 225V (8x) HDGs 2x1,0 FE180/PH90/E90 300/500V (18x) HDGsekwf 2x1,0 FE180/PH90/E90 300/500V (10x)
The length of cables was 5,5 m and 4,0 m from that was exposed to fire.
More detailed information about product construction is shown in the drawings which form an integral part
of test report [1]. Drawings were delivered by sponsor.
3. TEST REPORTS AND EXTENDED APPLICATION REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS AND EXTENDED APPLICATION REPORTS
No. Name of
laboratory Name of sponsor Test report No. Date of the
test Test method [1] FIRES, s.r.o.,
Batizovce, SR
BAKS Kazimierz Sielski, 05 - 480 Karczew, Poland
FIRES-FR- 066-14-AUNE
10. 04.
2014
STN 92 0205 ZP-27/2008 DIN 4102-12 3.2 TEST RESULTS
No./
Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
[1]
STN 92 0205 ZP-27/2008 DIN 4102-12
1 2 cables NHXCH 4x50RM/25 FE180/E90 0,6/1kV
13 90 minutes no failure / interruption 2 2 cables NHXCH 4x1,5RE/1,5 FE180/E90 0,6/1kV 90 minutes no failure / interruption 3 2 cables NHXH 4x50RM FE180/E90 0,6/1kV
12 90 minutes no failure / interruption 4 2 cables NHXH 4x1,5RM FE180/E90 0,6/1kV 90 minutes no failure / interruption 5 2 cables NHXCH 4x50RM/25 FE180/E90 0,6/1kV
11
90 minutes no failure / interruption 6 2 cables NHXCH 4x1,5RE/1,5 FE180/E90 0,6/1kV 90 minutes no failure / interruption 7 2 cables NHXH 4x50RM FE180/E90 0,6/1kV
10
90 minutes no failure / interruption 8 2 cables NHXH 4x1,5RM FE180/E90 0,6/1kV 90 minutes no failure / interruption 9 2 cables BiTservo® FS 4G1,5 FE180/E90 0,6/1kV
17
90 minutes no failure / interruption 10 2 cables BiTflame 1000 C 4x1,5RE FE180/E90 0,6/1kV 90 minutes no failure / interruption 11 2 cables BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV 90 minutes no failure / interruption 12 2 cables BiTservo® FS 4G50 FE180/E90 0,6/1kV 90 minutes no failure / interruption 13 2 cables BiTflame 1000 C 4x50RM FE180/E90 0,6/1kV 90 minutes no failure / interruption 14 2 cables BiTflame 1000 4x50RM FE180/E90 0,6/1kV 90 minutes no failure / interruption 15 2 cables BiTservo® FS 4G1,5 FE180/E90 0,6/1kV
9
71 minutes 16 2 cables BiTservo® FS 4G50 FE180/E90 0,6/1kV 41 minutes
17 2 cables BiTflame 1000 4x50RM FE180/E90 0,6/1kV 90 minutes no failure / interruption 18 2 cables BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV 90 minutes no failure / interruption 19 2 cables BiTflame 1000 4x50RM FE180/E90 0,6/1kV
8 90 minutes no failure / interruption 20 2 cables BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV 44 minutes
21 2 cables BiTflame 1000 4x50RM FE180/E90 0,6/1kV
7 90 minutes no failure / interruption 22 2 cables BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV 90 minutes no failure / interruption 23 2 cables BiTservo® FS 4G1,5 FE180/E90 0,6/1kV
4, 6
19 minutes 24 2 cables BiTservo® FS 4G50 FE180/E90 0,6/1kV 65 minutes 25 2 cables BiTflame 1000 C 4x50RM FE180/E90 0,6/1kV
6
90 minutes no failure / interruption 26 2 cables BiTflame 1000 C 4x1,5RE FE180/E90 0,6/1kV 90 minutes no failure / interruption 27 2 cables BiTservo® FS 4G1,5 FE180/E90 0,6/1kV
3, 5 42 minutes
28 2 cables BiTservo® FS 4G50 FE180/E90 0,6/1kV 90 minutes no failure / interruption 29 2 cables BiTflame 1000 C 4x50RM FE180/E90 0,6/1kV
5 90 minutes no failure / interruption 30 2 cables BiTflame 1000 C 4x1,5RE FE180/E90 0,6/1kV 90 minutes no failure / interruption 31 2 cables (N)HXCH 4x1,5RE/1,5 FE180/E90 0,6/1kV
16
90 minutes no failure / interruption 32 2 cables (N)HXH 4x1,5RM FE180/E90 0,6/1kV 66 minutes
33 2 cables (N)HXCH 4x50RM/25 FE180/E90 0,6/1kV 90 minutes no failure / interruption 34 2 cables (N)HXH 4x50RM FE180/E90 0,6/1kV 90 minutes no failure / interruption 35 2 cables BiTflame 1000 4x50RM FE180/E90 0,6/1kV
4 90 minutes no failure / interruption 36 2 cables BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV 90 minutes no failure / interruption
FIRES-JR-038-14-NURE
FIRES 149/S-28/03/2014-E Page: 5/10
No./
Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
[1]
STN 92 0205 ZP-27/2008 DIN 4102-12
37 2 cables BiTflame 1000 4x50RM FE180/E90 0,6/1kV
3 90 minutes no failure / interruption 38 2 cables BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV 90 minutes no failure / interruption 39 2 cables BiTservo® FS 4G50 FE180/E90 0,6/1kV
2 67 minutes 40 2 cables BiTservo® FS 4G1,5 FE180/E90 0,6/1kV 86 minutes 41 2 cables BiTflame 1000 4x50RM FE180/E90 0,6/1kV
1
90 minutes no failure / interruption 42 2 cables BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV 90 minutes no failure / interruption 43 2 cables BiTflame 1000 C 4x1,5RE FE180/E90 0,6/1kV
15
90 minutes no failure / interruption 44 2 cables BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV 90 minutes no failure / interruption 45 2 cables BiTflame 1000 C 4x50RM FE180/E90 0,6/1kV 11 minutes
46 2 cables BiTflame 1000 4x50RM FE180/E90 0,6/1kV 90 minutes no failure / interruption 47 2 cables (N)HXH 4x50RM FE180/E90 0,6/1kV
14
90 minutes no failure / interruption 48 2 cables (N)HXCH 4x50RM/25 FE180/E90 0,6/1kV 90 minutes no failure / interruption 49 2 cables (N)HXH 4x1,5RM FE180/E90 0,6/1kV 90 minutes no failure / interruption 50 2 cables (N)HXCH 4x1,5RE/1,5 FE180/E90 0,6/1kV 90 minutes no failure / interruption 52 2 cables HDGs 2x1,0 FE180/PH90/E90 300/500V
13 44 minutes 53 2 cables HDGsekwf 2x1,0 FE180/PH90/E90 300/500V 26 minutes 54 2 cables HTKSH 1x2x0,8 FE180/PH90/E90 225V
12 90 minutes no failure / interruption 55 2 cables HTKSHekwf 1x2x0,8 FE180/PH90/E90 225V 90 minutes no failure / interruption 56 2 cables HDGs 2x1,0 FE180/PH90/E90 300/500V
11 51 minutes 57 2 cables HDGsekwf 2x1,0 FE180/PH90/E90 300/500V 50 minutes 58 2 cables HTKSH 1x2x0,8 FE180/PH90/E90 225V
10 90 minutes no failure / interruption 59 2 cables HTKSHekwf 1x2x0,8 FE180/PH90/E90 225V 90 minutes no failure / interruption 60 2 cables HDGs 2x1,0 FE180/PH90/E90 300/500V 17 90 minutes no failure / interruption 61 2 cables HDGs 2x1,0 FE180/PH90/E90 300/500V 8 43 minutes
62 2 cables HDGs 2x1,0 FE180/PH90/E90 300/500V 7 86 minutes 63 2 cables HDGsekwf 2x1,0 FE180/PH90/E90 300/500V 6 28 minutes 64 2 cables HDGsekwf 2x1,0 FE180/PH90/E90 300/500V 5 25 minutes 65 2 cables HDGs 2x1,0 FE180/PH90/E90 300/500V 4 38 minutes
66 2 cables HDGs 2x1,0 FE180/PH90/E90 300/500V 3 90 minutes no failure / interruption 67 2 cables HDGsekwf 2x1,0 FE180/PH90/E90 300/500V
2 90 minutes no failure / interruption 68 2 cables HDGs 2x1,0 FE180/PH90/E90 300/500V 90 minutes no failure / interruption 69 2 cables HTKSHekwf 1x2x0,8 FE180/PH90/E90 225V
1 90 minutes no failure / interruption 70 2 cables HTKSH 1x2x0,8 FE180/PH90/E90 225V 90 minutes no failure / interruption 71 2 cables HTKSHekwf 1x2x0,8 FE180/PH90/E90 225V
15 90 minutes no failure / interruption 72 2 cables HTKSH 1x2x0,8 FE180/PH90/E90 225V 90 minutes no failure / interruption 73 2 cables HDGs 2x1,0 FE180/PH90/E90 300/500V
14 90 minutes no failure / interruption 74 2 cables HTKSH 1x2x0,8 FE180/PH90/E90 225V 90 minutes no failure / interruption
[1] The test was discontinued in 96
thminute at the request of test sponsor.
Specimens S1 – S50 were tested by three-phase voltage supply 3 x 230/400V with bulbs 240V / 60 W.
Specimens S52 – S74 were tested by one-phase voltage supply 1 x 110V with LED diodes 3V /0,03W.
Circuit breakers with rating 3 A were used.
4. CLASSIFICATION AND FIELD OF APPLICATION 4.1 REFERENCE OF CLASSIFICATION
This classification has been carried out in accordance with clause 3.2 of DIN 4102 – 12:1998-11.
4.2 CLASSIFICATION ACCORDING TO DIN 4102-12: 1998-11
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
BiTflame 1000 FE180/E90
0,6/1kV
BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV
Cable ladders DUD/DUOD400H60. Consoles combined of ceiling suspension PSEN and assembling profile
CT70H50 and brackets WWCT/WWCTO400.
Loading 15kg.m-1. Consoles fixed to ceiling by anchors R-HPTII-ZF-10080/20
in spacing of 1500 mm.
Track No. 1 and 2.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90 BiTflame 1000 4x50RM FE180/E90
0,6/1kV E 90
BiTservo® FS FE180/E90
0,6/1kV
BiTservo® FS 4G1,5 FE180/E90 0,6/1kV E 60 n x ≥1,5 mm2
n ≥ 2 E 60
BiTservo® FS 4G50 FE180/E90 0,6/1kV E 60
HTKSH FE180/PH90
E90
HTKSH 1x2x0,8 FE180/PH90/E90 225V E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSHekwf
FE180/PH90 E90
HTKSHekwf 1x2x0,8
FE180/PH90/E90 225V E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HDGs
FE180/PH90 E90
HDGs 2x1,0 FE180/PH90/E90 300/500V E 90
n x ≥ 1,0 mm2 n ≥ 2 E 90 HDGsekwf
FE180/PH90 E90
HDGsekwf 2x1,0 FE180/PH90/E90
300/500V E 90
n x ≥ 1,0 mm2 n ≥ 2 E 90 BiTflame 1000
FE180/E90 0,6/1kV
BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV
Cable trays KCP/KCOP400H60.
Consoles WPCW/WPCO1000, brackets WMC/WMCO400,
holders UPW/UPWO and threaded rods PG M10.
Loading 10kg.m-1. Consoles fixed to ceiling by anchors R-HPTII-ZF-10080/20
and R-DCA-10-40 in spacing of 1500 mm.
Track No. 3 and 5.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90 BiTflame 1000 4x50RM FE180/E90
0,6/1kV E 90
BiTflame 1000 C FE180/E90
0,6/1kV
BiTflame 1000 C 4x1,5RE FE180/E90
0,6/1kV E 90 n x ≥1,5 mm2
n ≥ 2 E 90 BiTflame 1000 C 4x50RM FE180/E90
0,6/1kV E 90
BiTservo® FS FE180/E90
0,6/1kV
BiTservo® FS 4G1,5 FE180/E90 0,6/1kV E 30 n x ≥1,5 mm2
n ≥ 2 E 30
BiTservo® FS 4G50 FE180/E90 0,6/1kV E 90
HDGs FE180/PH90
E90
HDGs 2x1,0 FE180/PH90/E90 300/500V E 90
n x ≥ 1,0 mm2 n ≥ 2 E 90 HDGsekwf
FE180/PH90 E90
HDGsekwf 2x1,0 FE180/PH90/E90 300/500V
Without classification
Without classification
BiTflame 1000 FE180/E90
0,6/1kV
BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV
Cable ladders DGOP400H60N.
Consoles WPCW/WPCO1000, brackets WMC/WMCO400,
holders UPW/UPWO and threaded rods PG M10.
Loading 20kg.m-1. Consoles fixed to ceiling by anchors R-HPTII-ZF-10080/20
and R-DCA-10-40 in spacing of 1500 mm.
Track No. 4 and 6.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90 BiTflame 1000 4x50RM FE180/E90
0,6/1kV E 90
BiTflame 1000 C FE180/E90
0,6/1kV
BiTflame 1000 C 4x1,5RE FE180/E90
0,6/1kV E 90 n x ≥1,5 mm2
n ≥ 2 E 90 BiTflame 1000 C 4x50RM FE180/E90
0,6/1kV E 90
BiTservo® FS FE180/E90
0,6/1kV
BiTservo® FS 4G1,5 FE180/E90 0,6/1kV Without
classification Without classification
BiTservo® FS 4G50 FE180/E90 0,6/1kV E 60
FIRES-JR-038-14-NURE
FIRES 149/S-28/03/2014-E Page: 7/10
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
HDGs FE180/PH90
E90
HDGs 2x1,0 FE180/PH90/E90 300/500V
Cable ladders DGOP400H60N.
Consoles WPCW/WPCO1000, brackets WMC/WMCO400,
holders UPW/UPWO and threaded rods PG M10.
Loading 20kg.m-1. Consoles fixed to ceiling by anchors R-HPTII-ZF-10080/20
and R-DCA-10-40 in spacing of 1500 mm.
Track No. 4 and 6.
E 30
n x ≥ 1,0 mm2 n ≥ 2 E 30
HDGsekwf FE180/PH90
E90
HDGsekwf 2x1,0 FE180/PH90/E90 300/500V
Without classification
Without classification
BiTflame 1000 FE180/E90
0,6/1kV
BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV
Cable trays KGL/KGOL300H60 covered by PKL300 with connectors ZPDH60. Consoles combined of assembling profiles CWP40H22/04 and threaded rods
PG M8 fixed to ceiling by anchors R-DCA-08-30.
Loading 15kg.m-1. Consoles in spacing of 1500 mm.
Track No. 7.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90 BiTflame 1000 4x50RM FE180/E90
0,6/1kV E 90
HDGs FE180/PH90
E90
HDGs 2x1,0 FE180/PH90/E90 300/500V E 60
n x ≥ 1,0 mm2 n ≥ 2 E 60
BiTflame 1000 FE180/E90
0,6/1kV
BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV
Cable trays KBL300H60 covered by PKL300 with connectors ZPDH60. Consoles combined of
assembling profiles CWP40H22/04 and threaded rods
PG M8 fixed to ceiling by anchors R-DCA-08-30.
Loading 15kg.m-1. Consoles in spacing of 1500 mm.
Track No. 8.
E 30 n x ≥1,5 mm2 n ≥ 2 E 30 BiTflame 1000 4x50RM FE180/E90
0,6/1kV E 90
HDGs FE180/PH90
E90
HDGs 2x1,0 FE180/PH90/E90 300/500V E 30
n x ≥ 1,0 mm2 n ≥ 2 E 30
BiTflame 1000 FE180/E90
0,6/1kV
BiTflame 1000 4x1,5RE FE180/E90
0,6/1kV Cable ladders
DUD/DUOD400H60. Consoles combined of assembling profiles CWP40H22/05 and threaded rods
PG M10 fixed to ceiling by anchors R-DCA-10-40.
Loading 25kg.m-1. Consoles in spacing of 1500 mm.
Track No. 9.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90 BiTflame 1000 4x50RM FE180/E90
0,6/1kV E 90
BiTservo® FS FE180/E90
0,6/1kV
BiTservo® FS 4G1,5 FE180/E90 0,6/1kV E 60 n x ≥1,5 mm2
n ≥ 2 E 30
BiTservo® FS 4G50 FE180/E90 0,6/1kV E 30
NHXH FE180/E90
NHXH 4x1,5RM FE180/E90 0,6/1kV Cable trays KGJ/KGOJ400H60.
Consoles combined of assembling profiles CWP/CWOP40H40/1,
brackets WMC/WMCO400, holders UPW/UPWO and
threaded rods PG M10.
Loading 15kg.m-1. Consoles fixed to wall in
spacing of 1500 mm.
Track No. 10.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
NHXH 4x50RM FE180/E90 0,6/1kV E 90
HTKSH FE180/PH90
E90
HTKSH 1x2x0,8 FE180/PH90/E90 225V E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSHekwf
FE180/PH90 E90
HTKSHekwf 1x2x0,8
FE180/PH90/E90 225V E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
NHXCH FE180/E90
NHXCH 4x1,5RE/1,5 FE180/E90 0,6/1kV Cable trays KGJ/KGOJ400H60.
Consoles combined of assembling profiles CWP/CWOP40H40/1,
brackets WWS/WWSO400, holders UPW/UPWO and
threaded rods PG M10.
Loading 15kg.m-1. Consoles fixed to wall in
spacing of 1500 mm.
Track No. 11.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
NHXCH 4x50RM/25 FE180/E90 0,6/1kV E 90
HDGs FE180/PH90
E90
HDGs 2x1,0 FE180/PH90/E90 300/500V E 30
n x ≥ 1,0 mm2 n ≥ 2 E 30 HDGsekwf
FE180/PH90 E90
HDGsekwf 2x1,0 FE180/PH90/E90
300/500V E 30
n x ≥ 1,0 mm2 n ≥ 2 E 30
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
NHXH FE180/E90
NHXH 4x1,5RM FE180/E90 0,6/1kV Cable ladders DUD/DUOD400H60. Consoles
combined of assembling profiles CWP/CWOP40H40/1,
brackets WMC/WMCO400, holders UPW/UPWO and
threaded rods PG M10.
Loading 20kg.m-1. Consoles fixed to wall in
spacing of 1500 mm.
Track No. 12.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
NHXH 4x50RM FE180/E90 0,6/1kV E 90
HTKSH FE180/PH90
E90
HTKSH 1x2x0,8 FE180/PH90/E90 225V E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSHekwf
FE180/PH90 E90
HTKSHekwf 1x2x0,8
FE180/PH90/E90 225V E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
NHXCH FE180/E90
NHXCH 4x1,5RE/1,5 FE180/E90 0,6/1kV Cable ladders DUD/DUOD400H60. Consoles
combined of assembling profiles CWP/CWOP40H40/1,
brackets WWS/WWSO400, holders UPW/UPWO and
threaded rods PG M10.
Loading 20kg.m-1. Consoles fixed to wall in
spacing of 1500 mm.
Track No. 13.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
NHXCH 4x50RM/25 FE180/E90 0,6/1kV E 90
HDGs FE180/PH90
E90
HDGs 2x1,0 FE180/PH90/E90 300/500V E 30
n x ≥ 1,0 mm2 n ≥ 2 E 30 HDGsekwf
FE180/PH90 E90
HDGsekwf 2x1,0 FE180/PH90/E90 300/500V
Without classification
Without classification
(N)HXH FE180/E90
(N)HXH 4x1,5RM FE180/E90 0,6/1kV
Track is made of single cable clips (UDF) fixed to steel sheet 0,7 mm thick on wall by steel self-drilling screws (OC-48016) in spacing of
600 mm.
Track No. 14.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90
(N)HXH 4x50RM FE180/E90 0,6/1kV E 90
(N)HXCH FE180/E90
(N)HXCH 4x1,5RE/1,5 FE180/E90
0,6/1kV E 90 n x ≥1,5 mm2
n ≥ 2 E 90 (N)HXCH 4x50RM/25 FE180/E90
0,6/1kV E 90
HDGs FE180/PH90
E90
HDGs 2x1,0 FE180/PH90/E90 300/500V E 90
n x ≥ 1,0 mm2 n ≥ 2 E 90 HTKSH
FE180/PH90 E90
HTKSH 1x2x0,8 FE180/PH90/E90 225V E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 BiTflame 1000
FE180/E90 0,6/1kV
BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV
Track is made of single cable clips (UDF) fixed to ceiling by anchors (GS-06040) in spacing of 600 mm.
Track No. 15.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90 BiTflame 1000 4x50RM FE180/E90
0,6/1kV E 90
BiTflame 1000 C FE180/E90
0,6/1kV
BiTflame 1000 C 4x1,5RE FE180/E90
0,6/1kV E 90
Without classification BiTflame 1000 C 4x50RM FE180/E90
0,6/1kV
Without classification HTKSH
FE180/PH90 E90
HTKSH 1x2x0,8 FE180/PH90/E90 225V E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 HTKSHekwf
FE180/PH90 E90
HTKSHekwf 1x2x0,8
FE180/PH90/E90 225V E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
(N)HXH FE180/E90
(N)HXH 4x1,5RM FE180/E90 0,6/1kV
Track is made of single cable clips (UDF) fixed to ceiling by steel screws (WHO-75052) in spacing
of 600 mm.
Track No. 16.
E 60 n x ≥1,5 mm2 n ≥ 2 E 60
(N)HXH 4x50RM FE180/E90 0,6/1kV E 90
(N)HXCH FE180/E90
(N)HXCH 4x1,5RE/1,5 FE180/E90
0,6/1kV E 90 n x ≥1,5 mm2
n ≥ 2 E 90 (N)HXCH 4x50RM/25 FE180/E90
0,6/1kV E 90
FIRES-JR-038-14-NURE
FIRES 149/S-28/03/2014-E Page: 9/10
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
BiTflame 1000 FE180/E90
0,6/1kV
BiTflame 1000 4x1,5RE FE180/E90 0,6/1kV
Track is made of assembling profiles SDOP700 fixed to ceiling
by expansion anchors (R-HPTII- ZF-08100/35). Cables are fixed to
profiles by cable clamps (UK1/UKO1).
Spacing of profiles 600 mm.
Track No. 17.
E 90 n x ≥1,5 mm2 n ≥ 2 E 90 BiTflame 1000 4x50RM FE180/E90
0,6/1kV E 90
BiTflame 1000 C FE180/E90
0,6/1kV
BiTflame 1000 C 4x1,5RE FE180/E90
0,6/1kV E 90 n x ≥1,5 mm2
n ≥ 2 E 90 BiTflame 1000 C 4x50RM FE180/E90
0,6/1kV E 90
BiTservo® FS FE180/E90
0,6/1kV
BiTservo® FS 4G1,5 FE180/E90 0,6/1kV E 90 n x ≥1,5 mm2
n ≥ 2 E 90
BiTservo® FS 4G50 FE180/E90 0,6/1kV E 90
HDGs FE180/PH90
E90
HDGs 2x1,0 FE180/PH90/E90 300/500V E 90
n x ≥ 1,0 mm2 n ≥ 2 E 90