FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-086-15-NURE

Cable bearing system BAKS with cables business Celina Bitner Zaklady Kablowe BITNER

This is an electronic version of a classification report which was made as a copy of classification report officially issued in a paper form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e.

FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor.

FIRES 004/S2-20/12/2012-E-el

(2)

FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION IN ACCORDANCE WITH DIN 4102-12: 1998-11

FIRES-JR-086-15-NURE

FIRES 149/S-10/08/2015-E FIRES, s.r.o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk

Name of the product: Cable bearing system BAKS

with cables business Celina Bitner Zaklady Kablowe BITNER

Sponsor: BAKS Kazimierz Sielski ul. Jagodne 5

05-480 Karczew Poland

Prepared by: FIRES, s.r.o.

Approved Body No. SK01 Osloboditeľov 282

059 35 Batizovce Slovak Republic

Task No.: PR-15-0333 Date of issue: 10. 09. 2015

Reports: 5

Copy No.: 2

Distribution list:

Copy No. 1 FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic (electronic version)

Copy No. 2 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland (electronic version)

Copy No. 3 Celina Bitner Zaklady Kablowe BITNER, ul. Józefa Friedleina 3/3 30-009 Kraków, Poland (electronic version)

Copy No. 4 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland Copy No. 5 Celina Bitner Zaklady Kablowe BITNER, ul. Józefa Friedleina 3/3

30-009 Kraków, Poland

This expert judgement report with classification may only be used or reproduced in its entirety.

(3)

FIRES-JR-086-15-NURE

FIRES 149/S-10/08/2015-E Page: 2/8

1. INTRODUCTION

This expert judgement report with classification defines the function in fire classification assigned to element Cable bearing system BAKS with cables business Celina Bitner Zaklady Kablowe BITNER in accordance with the classes given in DIN 4102 – 12: 1998-11.

This test was carried out according to standard STN 92 0205 and meets requirements of DIN 4102-12: 1998-11. Basic deviation in process and carrying out of test between these standards is in measuring and in control of temperature in the test furnace. According to STN 92 0205, plate thermometers according to EN 1363-1 are used. According to DIN 4102-12: 1998-11, common thermocouples of construction which was used for this measurement till issue of EN 1363-1 are used.

Measurement by plate thermometers acc. to EN 1363-1 can be considered as stricter method of temperature control in test furnace in compare with thermocouples used till issue of EN 1363-1. Therefore, it is possible to use results of test according to STN 92 025 for classification of tested cables according to DIN 4102-12: 1998-11, but not conversely.

This expert judgement report defines field of application which is outside the field of direct application according test standard or outside the field of extended application according to relevant extended application standard. This expert judgement expresses the opinion of the FIRES and is based on the experience or internal rules of FIRES.

This products have already been classified by FIRES, s.r.o. and number of previous classification of function in fire is FIRES-CR-007-09-AUPE, issued on 29. 05. 2009.

2. DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL

The element, Cable bearing system BAKS with cables business Celina Bitner Zaklady Kablowe BITNER, is defined as a cable bearing system for power halogen free cables with circuit integrity maintenance.

2.2 PRODUCT DESCRIPTION

The element comprise of cable bearing system BAKS – cable trays KCOD and KCOJ, cable ladders DGOD, cable holders OZO, ceiling ledges SDOC with clips UKO1, clips UDF, UEF and accessories (consoles WPCO, booms WMCO and WWSO, supports CWOP, holders UPWO, WPPOVE, threaded rods, dowels etc.) with power and communication non-halogen cables business Celina Bitner Zaklady Kablowe BITNER, type NHXH, (N)HXH, NHXCH, (N)HXCH with circuit integrity maintenance in fire.

Cable trays KCOD

Cable trays type KCOD…H60N are made from galvanized steel sheet thickness 1,2 mm. Trays are jointed together by two junctions type LPOPH60N (galvanized steel sheet thickness 1,5 mm) and by sheet type BLO…N (galvanized steel sheet thickness 1,0 mm) with screws type SGN M6x12. Trays are used as bearing system for the cables. Tested trays were KCOD 400H60/3N.

Cable trays KCOJ…H60E

Cable trays type KCOJ…H60E are made from stainless steel sheet thickness 1,0 mm. Trays are jointed together by two junctions type LPOPH60E (stainless steel sheet thickness 1,5 mm) and by sheet type BLO…E (stainless steel sheet thickness 1,0 mm) with screws type SGN M6x12/E. Trays are used as bearing system for the cables. Tested trays were KCOJ 400H60/3E.

Cable ladders DGOD…H60N

Cable ladders type DGOD…H60N are made from galvanized steel sheet thickness 1,2 mm and spacing of transoms is 150 mm. Ladders are jointed together by two junction type LDOCH60N (galvanized steel sheet thickness 2,0 mm) with screws type SGN M8x14. Ladders are used as bearing system for the cables. Tested ladders were DGOD 400H60/3N.

Cable ladders DGOD…H60E

Cable ladders type DGOD…H60E are made from stainless steel sheet thickness 1,2 mm and spacing of transoms is 150 mm. Ladders are jointed together by two junction type LDOCH60N (stainless steel sheet thickness 2,0 mm) with screws type SGN M8x14/E. Ladders are used as bearing system for the cables.

Tested ladders were DGOD 400H60/3E.

(4)

Consoles WPCO

Consoles type WPCO are made from galvanized steel sheet thickness 5,0 mm and 2,0 mm. Hangers are used to gripping trays or ladders to ceiling. Tested consoles were WPCO 900.

Consoles WPCO…E

Consoles type WPCO are made from stainless steel sheet thickness 5,0 mm and 2,0 mm. Hangers are used to gripping trays or ladders to ceiling. Tested consoles were WPCO 900E.

Booms WMCO…E

Booms type WMCO are made from stainless steel sheet thickness 5,0 mm and 2,5 mm. Booms are used to gripping trays or ladders to consoles WPCO or to wall. Tested booms were WMCO 400E.

Booms WWSO

Booms type WMCO are made from galvanized steel sheet thickness 2,0 mm. Booms are used to gripping trays or ladders to consoles WPCO or to wall. Tested booms were WWSO 400.

Holders UPWOE

Holders type UPWOE are made from stainless steel sheet thickness 2,0 mm. Holders are used to gripping threaded rods to ceiling.

Holders USOV

Holders type USOV are made from galvanized steel sheet thickness 5,0 mm. Holders are used to gripping threaded rods to ceiling.

Holders USOVE

Holders type USOVE are made from stainless steel sheet thickness 5,0 mm. Holders are used to gripping threaded rods to ceiling.

Holders WPPOWE

Holders type WPPOVE are made from stainless steel sheet thickness 5,0 mm. Holders are used to gripping threaded rods to ceiling.

Supports CWOP…E

Supports CWOP40H40…E are made from stainless steel sheet thickness 1,5 mm. Supports with threaded rods are used to gripping trays or ladders to ceiling. Tested supports were CWOP40H40/05E.

Ceiling ledges SDOC…E

Ceiling ledges type SDOC are made from stainless steel sheet thickness 2,0 mm. Ceiling ledges are used to gripping cables with clips UKO1 to ceiling or to wall. Tested ledges were SDOC 400E.

Cable clips UKO1E

Cable clips UKO are made from stainless steel sheet thickness 2,0 mm. Clips UKO1E are used to gripping cables to ledges or to ladders.

Cable holders OZOE

Cable holders type OZOE are made from stainless steel sheet thickness 1,5 mm. Cable holders are used to gripping cables to ceiling or to wall.

Cable clips UDF and UEF

Cable clips UDF and UEF are made from galvanized steel sheet thickness 1,2 mm or 2,0 mm. Clips are used to gripping cables to ceiling or to wall.

Cable clips UDFE

Cable clips UDFE are made from stainless steel sheet thickness 1,2 mm or 2,0 mm. Clips are used to gripping cables to ceiling or to wall.

Cables

Power cables NHXH, (N)HXH, NHXCH, (N)HXCH - safety cables are used in all locations where a special protection against fire and fire damage is necessary for human life and equipment and where strict safety regulations have to be met and where large emergency running time is necessary. They may be used indoor and outdoor, but not directly in earth and water. They are considered as protectively insulated.

(5)

FIRES-JR-086-15-NURE

FIRES 149/S-10/08/2015-E Page: 4/8

Used cables by test:

Power cables:

NHXH 4x1,5 RE FE180 E90 MICA ( 18 x )

NHXH 4x1,5 RE FE180 MICA 01 ( 2 x )

NHXH 4x1,5 RE FE180 MICA 02 ( 2 x )

NHXH 4x1,5 RE FE180 MICA 03 ( 2 x )

NHXH 4x10 RE FE180 E90 MICA ( 6 x )

NHXH 4x50 RM FE180 E90 MICA ( 16 x )

(N)HXH 4x1,5 RE FE180 CERAMIC 0508 ( 2 x ) (N)HXH 4x1,5 RE FE180 CERAMIC 0957 ( 2 x ) (N)HXH 4x1,5 RE FE180 CERAMIC 1384 ( 2 x ) (N)HXH 4x10 RE FE180 E90 CERAMIC ( 4 x ) NHXCH 4x1,5/1,5 RE FE180 E90 MICA ( 18 x )

NHXCH 4x1,5/1,5 RE FE180 MICA 01 ( 2 x )

NHXCH 4x1,5/1,5 RE FE180 MICA 02 ( 2 x )

NHXCH 4x1,5/1,5 RE FE180 MICA 03 ( 2 x )

NHXCH 4x10/10 RE FE180 E90 MICA ( 2 x )

NHXCH 4x50/25 RM FE180 E90 MICA ( 16 x )

(N)HXCH 4x1,5/1,5 RE FE180 CERAMIC 0508 ( 2 x ) (N)HXCH 4x1,5/1,5 RE FE180 CERAMIC 0957 ( 2 x ) (N)HXCH 4x1,5/1,5 RE FE180 CERAMIC 1384 ( 2 x )

Cables were fixed to trays by clips UDF and ladders by clips UKO1 according to the cable diameter.

More detailed information about product construction is shown in the drawings which form an integral part of test report [1]. Drawings were delivered by sponsor.

3. TEST REPORTS AND EXTENDED APPLICATION REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS AND EXTENDED APPLICATION REPORTS

No. Name of laboratory Name of sponsors Test report No. Date of the test Test method

[1] Fires s.r.o., Batizovce, SR

BAKS Kazimierz Sielski,

Karczew, PL

FIRES-FR-256-

08-AUNE 20. 11. 2008 DIN 4102 – 12:

1998-11

3.2 TEST RESULTS

Test report No.

/Test method

Specimen

No. Cables Track

No.

Time to first failure / interruption of conductor

[1]

DIN 4102-12

1 2 cables NHXCH 4x50/25 RM FE180 E90 MICA 14 90 minutes no failure / interruption 2 2 cables (N)HXH 4x1,5 RE FE180 CERAMIC 0508

14 70 minutes 2 cables (N)HXCH 4x1,5/1,5 RE FE180 CERAMIC 0508 70 minutes

3 2 cables NHXCH 4x1,5/1,5 RE FE180 E90 MICA 14 90 minutes no failure / interruption 4 2 cables NHXCH 4x50/25 RM FE180 E90 MICA 12 90 minutes no failure / interruption 5 2 cables NHXH 4x50 RM FE180 E90 MICA 12 90 minutes no failure / interruption 6 2 cables NHXCH 4x1,5/1,5 RE FE180 E90 MICA 12 90 minutes no failure / interruption 7 2 cables NHXH 4x1,5 RE FE180 E90 MICA 12 90 minutes no failure / interruption 8 2 cables NHXH 4x50 RM FE180 E90 MICA 10 90 minutes no failure / interruption 9 2 cables (N)HXCH 4x1,5/1,5 RE FE180 CERAMIC 1384 10 90 minutes no failure / interruption 10 2 cables (N)HXH 4x1,5 RE FE180 CERAMIC 1384 10 90 minutes no failure / interruption 11 2 cables NHXH 4x1,5 RE FE180 E90 MICA 10 90 minutes no failure / interruption 12 2 cables NHXH 4x10 RE FE180 E90 MICA 8 90 minutes no failure / interruption 13 2 cables (N)HXH 4x10 RE FE180 E90 CERAMIC 8 90 minutes no failure / interruption 14 2 cables NHXCH 4x50/25 RM FE180 E90 MICA 13 90 minutes no failure / interruption

(6)

Test report No.

/Test method

Specimen

No. Cables Track

No.

Time to first failure / interruption of conductor

[1]

DIN 4102-12

15 2 cables (N)HXCH 4x1,5/1,5 RE FE180 CERAMIC 0957 13 36 minutes 16 2 cables (N)HXH 4x1,5 RE FE180 CERAMIC 0957 13 38 minutes

17 2 cables NHXCH 4x1,5/1,5 RE FE180 E90 MICA 13 90 minutes no failure / interruption 18 2 cables NHXCH 4x50/25 RM FE180 E90 MICA 11 90 minutes no failure / interruption 19 2 cables NHXH 4x50 RM FE180 E90 MICA 11 90 minutes no failure / interruption 20 2 cables NHXCH 4x1,5/1,5 RE FE180 E90 MICA 11 90 minutes no failure / interruption 21 2 cables NHXH 4x1,5 RE FE180 E90 MICA 11 90 minutes no failure / interruption 22 2 cables NHXH 4x50 RM FE180 E90 MICA 9 90 minutes no failure / interruption 23 2 cables NHXCH 4x1,5/1,5 RE FE180 MICA 02 9 76 minutes

24 2 cables NHXH 4x1,5 RE FE180 MICA 02 9 89 minutes

25 2 cables NHXH 4x1,5 RE FE180 E90 MICA 9 90 minutes no failure / interruption 26 2 cables NHXH 4x10 RE FE180 E90 MICA 7 76 minutes

27 2 cables (N)HXH 4x10 RE FE180 E90 CERAMIC 7 90 minutes no failure / interruption 28 2 cables NHXCH 4x1,5/1,5 RE FE180 E90 MICA 6 90 minutes no failure / interruption 29 2 cables NHXH 4x1,5 RE FE180 E90 MICA 6 90 minutes no failure / interruption 30 2 cables NHXCH 4x50/25 RM FE180 E90 MICA 6 90 minutes no failure / interruption 31 2 cables NHXH 4x50 RM FE180 E90 MICA 6 51 minutes

32 2 cables NHXCH 4x1,5/1,5 RE FE180 E90 MICA 5 90 minutes no failure / interruption 33 2 cables NHXH 4x1,5 RE FE180 E90 MICA 5 90 minutes no failure / interruption 34 2 cables NHXCH 4x50/25 RM FE180 E90 MICA 5 90 minutes no failure / interruption 35 2 cables NHXH 4x50 RM FE180 E90 MICA 5 41 minutes

36 2 cables NHXCH 4x10/10 RE FE180 E90 MICA 4 90 minutes no failure / interruption 37 2 cables NHXH 4x10 RE FE180 E90 MICA 4 90 minutes no failure / interruption 38 2 cables NHXCH 4x50/25 RM FE180 E90 MICA 1 90 minutes no failure / interruption 39 2 cables NHXCH 4x1,5/1,5 RE FE180 MICA 03 1 90 minutes no failure / interruption 40 2 cables NHXH 4x1,5 RE FE180 MICA 03 1 90 minutes no failure / interruption 41 2 cables NHXCH 4x1,5/1,5 RE FE180 E90 MICA 1 90 minutes no failure / interruption 42 2 cables NHXCH 4x50/25 RM FE180 E90 MICA 2 90 minutes no failure / interruption 43 2 cables NHXH 4x50 RM FE180 E90 MICA 2 90 minutes no failure / interruption 44 2 cables NHXCH 4x1,5/1,5 RE FE180 E90 MICA 2 90 minutes no failure / interruption 45 2 cables NHXH 4x1,5 RE FE180 E90 MICA 2 48 minutes

46 2 cables NHXH 4x50 RM FE180 E90 MICA 3 90 minutes no failure / interruption 47 2 cables NHXCH 4x1,5/1,5 RE FE180 MICA 01 3 90 minutes no failure / interruption 48 2 cables NHXH 4x1,5 RE FE180 MICA 01 3 90 minutes no failure / interruption 49 2 cables NHXH 4x1,5 RE FE180 E90 MICA 3 90 minutes no failure / interruption 50 2 cables NHXCH 4x1,5/1,5 RE FE180 E90 MICA 4 90 minutes no failure / interruption 51 2 cables NHXH 4x1,5 RE FE180 E90 MICA 4 90 minutes no failure / interruption

[1] The fire test was discontinued in 92nd minute at the request of sponsor.

Specimens S1 – S51 were tested by three-phase voltage supply 3 x 230/400V with bulbs 240V / 60 W.

Circuit breakers with rating 3 A and performance characteristics B(gL) were used.

4. CLASSIFICATION AND FIELD OF APPLICATION 4.1 REFERENCE OF CLASSIFICATION

This classification has been carried out in accordance with clause 3.2 of DIN 4102 – 12:1998-11.

4.2 CLASSIFICATION ACCORDING TO DIN 4102-12: 1998-11

The element, cable bearing system BAKS – cable trays KCOD and KCOJ, cable ladders DGOD, cable holders OZO, ceiling ledges SDOC with clips UKO1, clips UDF, UEF and accessories (consoles WPCO, booms WMCO and WWSO, supports CWOP, holders UPWO, WPPOVE, threaded rods, dowels etc.) with power and communication non-halogen cables business Celina Bitner Zaklady Kablowe BITNER, type NHXH, (N)HXH, NHXCH, (N)HXCH is classified according to the following combinations of performance parameters and classes as appropriate.

(7)

FIRES-JR-086-15-NURE

FIRES 149/S-10/08/2015-E Page: 6/8

Used cables by test are classified as follows:

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

NHXCH FE180 E90

MICA

NHXCH 4x1,5/1,5 RE FE180 E90 MICA Cable trays KCOJ 400H60/3E.

Consoles WPCO 900E fixed to ceiling by two dowels

PSRO M10x80E.

Booms WMCO 400E with holders UPWOE and threaded rods PGM10E

with holders USOVE.

Consoles in spacing of 1500 mm.

Loading 10 kg.m-1. Track No. 1 and 3.

E 90 n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 E90 MICA E 90

NHXH FE180 E90

MICA

NHXH 4x1,5 RE FE180 E90 MICA E 90 n x ≥1,5 mm2

n ≥ 2 E 90

NHXH 4x50 RM FE180 E90 MICA E 90

NHXCH FE180 E90

MICA

NHXCH 4x1,5/1,5 RE FE180 E90 MICA Cable ladders DGOD 400H60/3E.

Consoles WPCO 900E fixed to ceiling by two dowels

PSRO M10x80E.

Booms WMCO 400E with holders UPWOE and threaded rods PGM10E

with holders USOVE.

Consoles in spacing of 1500 mm.

Loading 20 kg.m-1. Track No. 2.

E 90 n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 E90 MICA E 90

NHXH FE180 E90

MICA

NHXH 4x1,5 RE FE180 E90 MICA E 30 n x ≥1,5 mm2

n ≥ 2 E 30

NHXH 4x50 RM FE180 E90 MICA E 90

NHXCH FE180 E90

MICA

NHXCH 4x1,5/1,5 RE FE180 E90 MICA Cable trays KCOJ 400H60/3E.

Consoles combined of supporting profiles CWP/CWOP40H40/05E and two threaded rods PGM10E

with hangers WPPOVE and dowels PSRO M10x80E.

Consoles in spacing of 1500 mm.

Loading 10 kg.m-1. Track No. 9 and 13.

E 90 n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 E90 MICA E 90

NHXH FE180 E90

MICA

NHXH 4x1,5 RE FE180 E90 MICA E 90 n x ≥1,5 mm2

n ≥ 2 E 90

NHXH 4x50 RM FE180 E90 MICA E 90

NHXCH FE180 E90

MICA

NHXCH 4x1,5/1,5 RE FE180 E90 MICA Cable ladders DGOD 400H60/3E.

Consoles combined of supporting profiles CWP/CWOP40H40/05E and two threaded rods PGM10E

with hangers WPPOVE and dowels PSRO M10x80E.

Consoles in spacing of 1500 mm.

Loading 20 kg.m-1. Track No. 11.

E 90 n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 E90 MICA E 90

NHXH FE180 E90

MICA

NHXH 4x1,5 RE FE180 E90 MICA E 90 n x ≥1,5 mm2

n ≥ 2 E 90

NHXH 4x50 RM FE180 E90 MICA E 90

NHXCH FE180 E90

MICA

NHXCH 4x1,5/1,5 RE FE180 E90 MICA Cable trays KCOD 400H60/3N.

Consoles WPCO 900 fixed to ceiling by two dowels PSRO M10x80.

Booms WWSO 400 with holders UPWO and threaded rods PGM10E

with holders USOV.

Consoles in spacing of 1500 mm.

Loading 10 kg.m-1. Track No. 10 and 14.

E 90 n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 E90 MICA E 90

NHXH FE180 E90

MICA

NHXH 4x1,5 RE FE180 E90 MICA E 90 n x ≥1,5 mm2

n ≥ 2 E 90

NHXH 4x50 RM FE180 E90 MICA E 90

NHXCH FE180 E90

MICA

NHXCH 4x1,5/1,5 RE FE180 E90 MICA

Cable ladders DGOD 400H60/3N.

Consoles WPCO 900 fixed to ceiling by two dowels PSRO M10x80.

Booms WWSO 400 with holders UPWO and threaded rods PGM10E

with holders USOV.

Consoles in spacing of 1500 mm.

Loading 20 kg.m-1. Track No. 12.

E 90

n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 E90 MICA E 90

NHXH FE180 E90

MICA

NHXH 4x1,5 RE FE180 E90 MICA E 30

n x ≥1,5 mm2 n ≥ 2 E 30

NHXH 4x50 RM FE180 E90 MICA E 90

(8)

Cable Type of tested cable, single cross-

sections and number of conductors Arrangement

Classification for type of tested cable

(by cross-sections and number of

conductors)

Classification for cable

NHXCH FE180 E90

MICA

NHXCH 4x1,5/1,5 RE FE180 E90 MICA

Clips UDFE.

Clips fixed by dowels SRO M6x30E.

Clips in spacing of 600 mm.

Ceiling mounting.

Track No. 4.

E 90 n x = 1,5/1,5 - 10/10 mm2

n ≥ 2 E 90

NHXCH 4x10/10 RE FE180 E90 MICA E 90

NHXH FE180 E90

MICA

NHXH 4x1,5 RE FE180 E90 MICA E 90 n x = 1,5 - 10 mm2

n ≥ 2 E 90

NHXH 4x10 RE FE180 E90 MICA E 90

NHXCH FE180 E90

MICA

NHXCH 4x1,5/1,5 RE FE180 E90 MICA

Cable holders OZOE Holders fixed by dowels

SRO M6x30E.

Holders in spacing of 600 mm.

Ceiling mounting.

Track No. 5.

E 90 n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 E90 MICA E 90

NHXH FE180 E90

MICA

NHXH 4x1,5 RE FE180 E90 MICA E 90 n x ≥1,5 mm2

n ≥ 2 E 30

NHXH 4x50 RM FE180 E90 MICA E 30

NHXCH FE180 E90

MICA

NHXCH 4x1,5/1,5 RE FE180 E90 MICA

Clips UKO1E in the ledges SDOC 400E.

Ledges fixed by dowels SRO M6x30E.

Clips and ledges in spacing of 600 mm.

Ceiling mounting.

Track No. 6.

E 90 n x ≥1,5/1,5 mm2 n ≥ 2 E 90

NHXCH 4x50/25 RM FE180 E90 MICA E 90

NHXH FE180 E90

MICA

NHXH 4x1,5 RE FE180 E90 MICA E 90 n x ≥1,5 mm2

n ≥ 2 E 30

NHXH 4x50 RM FE180 E90 MICA E 30

NHXH FE180 E90

MICA

NHXH 4x10 RE FE180 E90 MICA Clips UDF.

Clips fixed by dowels SRO M6x30.

Clips in spacing of 300 mm.

Ceiling mounting.

Track No. 7.

E 60 Without

classification

(N)HXH FE180 E90

CERAMIC

(N)HXH 4x10 RE FE180 E90 CERAMIC E 90 Without

classification

NHXH FE180 E90

MICA

NHXH 4x10 RE FE180 E90 MICA Clips UEF.

Clips fixed by dowels SRO M6x30.

Clips in spacing of 300 mm.

Ceiling mounting.

Track No. 7.

E 90 Without

classification

(N)HXH FE180 E90

CERAMIC

(N)HXH 4x10 RE FE180 E90 CERAMIC E 90 Without

classification

The element, cable bearing system BAKS – cable trays KCOD and KCOJ, cable ladders DGOD, cable holders OZO, ceiling ledges SDOC with clips UKO1, clips UDF, UEF and accessories (consoles WPCO, booms WMCO and WWSO, supports CWOP, holders UPWO, WPPOVE, threaded rods, dowels etc.) with power and communication non-halogen cables business Celina Bitner Zaklady Kablowe BITNER, type NHXH, (N)HXH, NHXCH, (N)HXCH are classified to classes according to achieved test results of tested cables at tracks. Other classification is not allowed.

(9)

FIRES-JR-086-15-NURE

FIRES 149/S-10/08/2015-E Page: 8/8

4.3 FIELD OF APPLICATION

This classification is valid for the following end use applications:

§ throughout the period during which circuit integrity is to be maintained, neighbouring building components shall not have a negative effect on circuit integrity;

§ classification for type of cable (by cross-sections and number of conductors) is valid only for tested cable types, number and cross-sections of conductors;

§ classification for cable is valid for all numbers and cross-sections of tested cable type;

§ although testing is only carried out on cables arranged horizontally, test results also apply to cables arranged either diagonally or vertically (e.g. risers), as long as the cable system is supported in transitional areas (i.e. where it switches from a horizontal to a vertical arrangement) in such a manner that the cables will not slip or kink at corners;

§ test results of function in fire test of cables tested at standard supporting construction are also applicable for tested standard supporting construction of other producers;

§ test results of function in fire test of cables tested at standard supporting construction are also applicable for cables of other producers tested at standard supporting construction;

§ test results of function in fire test of cables at nonstandard supporting construction are valid only for tested construction with particular tested cable type and are also applicable for supporting construction with smaller spacing of consoles and smaller loading;

§ test results of cables tested in cable trays or ladders are applicable also for cable trays and ladders with particular construction with smaller width as tested with particular smaller loading;

§ test results of cables tested at cable trays or ladders are applicable also for another products trays and ladders (cross, elbow, T-bend, bends and etc.);

§ maximal length of increasing routing shall be 3500 mm with consistent horizontal placing of cable with minimal length of 300 mm (apart from cable bending) and with maximal spacing of clips of 300 mm, eventually the cables are stabilized by cable transmissions at floor or ceiling with particular fire resistance;

§ for vertical systems, the test results obtained for cables mounted singly on the ceiling using single clips apply. Brackets of proven suitability may also be used, as long as their spacing is equal to that of the single clips tested;

§ results of testing single cables on the ceiling apply also to cables mounted horizontally on walls;

§ results of testing bunched cables on a ladder or tray also apply to support construction attached to a wall. However, such constructions required proof of suitability by means of a test certificate or other document issued by an accredited testing laboratory;

§ test results are applicable only for systems without connection elements (e.g. junction box, branch bar).

5. LIMITATIONS

Load-bearing construction elements for fixing of cable systems must be proved for at least the same fire resistance compare to classified function in fire of cable system.

The construction contractor is solely responsible for proper preparation.

This classification document does not represent type approval or certification of the product.

The classification is valid until 10. 09. 2020 provided that the product, field of application and standards and regulations are not changed.

Approved: Signed:

Ing. Štefan Rástocký Miroslav Hudák

leader of the testing laboratory technician of the testing laboratory

Cytaty

Powiązane dokumenty

Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable clips with accessories (consoles, brackets, cable clamps, etc.) and power and communication

The element, Cable bearing system BAKS – cable trays, cable ladders, cable clips and clamps with accessories (consoles, brackets, supports, hangers, etc.) and

Product comprise of cable bearing system BAKS – cable trays, cable mesh trays, cable clips and clamps with accessories (consoles, brackets, assembling profiles, etc.) and

The element, Cable bearing system BAKS – cable trays, cable ladders, cable clips and clamps with accessories (consoles, brackets, supports, hangers, etc.) and

The element comprise of cable bearing system BAKS – cable trays KCOP, cable ladders DGOP, ceiling ledges SDOP with clips UKO1 and clips UDF with accessories (consoles, booms,

The element comprise of cable bearing system BAKS – cable trays KCOP, cable ladders DGOP, ceiling ledges SDOC with clips UKO1 and UKO2, clips UDF and UEF, cable holders

§ test results of function in fire test of cables at nonstandard supporting construction are valid only for tested construction with particular tested cable

The element comprise of cable bearing system BAKS – cable trays KCOP, cable mesh trays KDSO, cable ladders DGOP, DUOP, cable clips UDF, UEF, 1015 and accessories (consoles