FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-098-14-NURE
Cable bearing system BAKS with power and communication cables of ELKOND HHK, a.s.
This is an electronic version of a classification report which was made as a copy of classification report officially issued in a paper form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e.
FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor.
FIRES 004/S2-20/12/2012-E-el
FUNCTION IN FIRE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION IN ACCORDANCE WITH DIN 4102-12: 1998-11
FIRES-JR-098-14-NURE
FIRES 149/S-28/03/2014-E FIRES, s.r.o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk
Name of the product: Cable bearing system BAKS with power and communication cables of ELKOND HHK, a.s.
Sponsor: BAKS Kazimierz Sielski ul. Jagodne 5
05 - 480 Karczew Poland
Prepared by: FIRES, s.r.o.
Approved Body No. SK01 Osloboditeľov 282
059 35 Batizovce Slovak Republic
Task No.: PR-14-0438 Date of issue: 03. 02. 2015
Reports: 5
Copy No.: 2
Distribution list:
Copy No. 1 FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic (electronic version)
Copy No. 2 BAKS Kazimierz Sielski, ul. Jagodne 5, 05 - 480 Karczew, Poland (electronic version)
Copy No. 3 ELKOND HHK, a.s., Oravická 1228, Trstená 028 01, Slovak Republic (electronic version)
Copy No. 4 BAKS Kazimierz Sielski, ul. Jagodne 5, 05-480 Karczew, Poland
Copy No. 5 ELKOND HHK, a.s., Oravická 1228, Trstená 028 01, Slovak Republic
FIRES-JR-098-14-NURE
FIRES 149/S-28/03/2014-E Page: 2/9
1. INTRODUCTION
This expert judgement report with classification defines the function in fire classification assigned to element „Cable bearing system BAKS with power and communication cables of ELKOND HHK, a.s.” in accordance with the classes given in DIN 4102-12: 1998-11.
This test was carried out according to standard STN 92 0205: 2012 and meets requirements of DIN 4102-12: 1998-11. Basic deviation in process and carrying out of test between these standards is in measuring and in control of temperature in the test furnace. According to STN 92 0205: 2012, plate thermometers according to EN 1363-1 are used. According to DIN 4102-12: 1998-11, common thermocouples of construction which was used for this measurement till issue of EN 1363-1 are used.
Measurement by plate thermometers acc. to EN 1363-1 can be considered as stricter method of temperature control in test furnace in compare with thermocouples used till issue of EN 1363-1. Therefore, it is possible to use results of test according to STN 92 025: 2012 for classification of tested cables according to DIN 4102-12: 1998-11, but not conversely.
This expert judgement report defines field of application which is outside the field of direct application according test standard or outside the field of extended application according to relevant extended application standard. This expert judgement expresses the opinion of the FIRES and is based on the experience or internal rules of FIRES.
2. DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL
The element, Cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clips and clamps with accessories (consoles, brackets, assembling profiles, etc.) and power and communication halogen free cables of company ELKOND HHK, a.s. with circuit integrity maintenance classes.
2.2 PRODUCT DESCRIPTION
Product comprise of cable bearing system BAKS – cable trays, cable ladders, cable mesh trays, cable clips and clamps with accessories (consoles, brackets, assembling profiles, etc.) and power and communication halogen free cables of company ELKOND HHK, a.s. with circuit integrity maintenance classes.
Cable trays
Cable trays type KGJ/KGOJ…H60 are made from steel sheet thickness 0,9 mm.
Cable trays type KGL/KGOL…H60 are made from steel sheet thickness 0,7 mm.
Cable trays type KFL…H60 are made from steel sheet thickness 0,7 mm.
Trays are connected together and fixed by nut bolts (SGK M6x12). Trays are used as a bearing system for the cables.
Cable trays type KCP/KCOP…H60 are made from steel sheet thickness 1,5 mm. Trays are jointed together by two junctions (LPP/LPOPH60 - steel sheet 1,5 mm thick) on sides and by junction (BL/BLO…
- steel sheet 1,0 mm thick) on the bottom and with screws (SGK M6x12).
Cable mesh trays
Cable trays type KDS/KDSO…H60 are made from steel wire ∅ 4,0 – 4,5 mm. Mesh trays are jointed together by junctions (USSN/USSO).
Mesh trays are used as bearing system for the cables.
Cable ladders
Cable ladders type DGOP…H60N are made from steel sheet thickness 1,5 mm and spacing of transoms is 150 mm. Ladders are jointed together by two junctions (LDC/LDOCH60 - steel sheet 1,5 mm thick) on sides and by screws (SGK M8x14).
Cable ladders are used as bearing system for the cables.
Cable clips
Single cable clips UDF are made of steel sheet 1,2 mm thick.
Cable clips are used for fixing of cables directly to wall or ceiling.
Cable hangers
Cable hangers OZ/OZO are made of steel sheet thickness 1,5 mm.
Cable hangers OZS/OZSO and OZM/OZMO are made of steel sheet thickness 0,7 mm.
Cable hangers are used for fixing of cables to wall or ceiling.
Brackets
Brackets type WWS/WWSO… are made from steel sheet thickness 2,0 mm.
Brackets are used to gripping trays or ladders to ceiling or to wall.
Consoles
Consoles type WPCB… are made from steel sheet thickness 5,0 mm (base of console) and 2,0 mm (part for installation of brackets).
Accessories
Assembling profiles CWP40H22/… and CWP/CWOP40H40/… are made of steel sheet thickness 1,5 mm.
Trapezoidal hangers WT/WTO120 are made of steel sheet thickness 2,5 mm.
Used cables by test:
Power cables:
1-CXKH-V 4x1,5 RE P90-R B2
ca-s1,d0,a1 (36x) 1-CXKH-V 4x10 RE P90-R B2
ca-s1,d0,a1 (36x)
NHXH-J 4x1,5 RE FE180/E90 (4x)
NHXH-J 4x10 RE FE180/E90 (4x)
NHXH-J 4x1,5 RE FE180/E90 P (4x)
NHXH-J 4x10 RE FE180/E90 P (4x)
Communication cables:
SHXKFH-V180 1x2x0,8 Lg P90-R B2
ca-s1,d1,a1 (30x) JE-H(St)H 1x2x0,8 Bd FE180/PS90 B2
ca-s1,d1,a1 (14x) JE-H(St)H 1x2x0,8 Bd FE180/PS60 (4x)
The length of cables was 5,2 m and 4,0 m from that was exposed to fire.
More detailed information about product construction is shown in the drawings which form an integral part of test report [1]. Drawings were delivered by sponsor.
3. TEST REPORTS AND EXTENDED APPLICATION REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS AND EXTENDED APPLICATION REPORTS
No. Name of
laboratory Name of sponsor Test report No. Date of the
test Test method [1] FIRES, s.r.o.,
Batizovce, SR
BAKS Kazimierz Sielski, 05 - 480 Karczew, Poland
FIRES-FR-
225-14-AUNE 27. 11. 2014 STN 92 0205
FIRES-JR-098-14-NURE
FIRES 149/S-28/03/2014-E Page: 4/9
3.2 TEST RESULTS
No./
Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
[1]
STN 92 0205
1 2 cables NHXH-J 4x10 RE FE180/E90 P
16
41 minutes
2 2 cables NHXH-J 4x1,5 RE FE180/E90 P 48 minutes
3 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 4 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 5 2 cables NHXH-J 4x1,5 RE FE180/E90 P
15 71 minutes
6 2 cables NHXH-J 4x10 RE FE180/E90 P 64 minutes
7 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
21 90 minutes no failure / interruption 8 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 9 2 cables NHXH-J 4x1,5 RE FE180/E90
14
90 minutes no failure / interruption 10 2 cables NHXH-J 4x10 RE FE180/E90 90 minutes no failure / interruption 11 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 12 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 13 2 cables NHXH-J 4x1,5 RE FE180/E90
13
90 minutes no failure / interruption 14 2 cables NHXH-J 4x10 RE FE180/E90 90 minutes no failure / interruption 15 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 16 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 17 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
20 90 minutes no failure / interruption 18 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 19 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
12 90 minutes no failure / interruption 20 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 21 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
11 90 minutes no failure / interruption 22 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 23 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
10 90 minutes no failure / interruption 24 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 25 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
8 90 minutes no failure / interruption 26 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 27 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
6
90 minutes no failure / interruption 28 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 29 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
5
90 minutes no failure / interruption 30 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 31 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
19 90 minutes no failure / interruption 32 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 33 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
4 90 minutes no failure / interruption 34 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 35 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
3 90 minutes no failure / interruption 36 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 37 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
18 90 minutes no failure / interruption 38 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 39 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
2 90 minutes no failure / interruption 40 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 41 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1
1 90 minutes no failure / interruption 42 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption 43 2 cables 1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
17 85 minutes
44 2 cables 1-CXKH-V 4x10 RE P90-R B2ca-s1,d0,a1 90 minutes no failure / interruption
No./
Test method
Specimen
No. Cables Track
No.
Time to first failure / interruption of conductor
[1]
STN 92 0205
52 2 cables JE-H(St)H 1x2x0,8 Bd FE180/PS90 B2ca-s1,d1,a1 15
90 minutes no failure / interruption 53 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 90 minutes no failure / interruption 54 2 cables JE-H(St)H 1x2x0,8 Bd FE180/PS60 90 minutes no failure / interruption 55 2 cables JE-H(St)H 1x2x0,8 Bd FE180/PS60
14
47 minutes
56 2 cables JE-H(St)H 1x2x0,8 Bd FE180/PS90 B2ca-s1,d1,a1 90 minutes no failure / interruption 57 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 90 minutes no failure / interruption 58 2 cables JE-H(St)H 1x2x0,8 Bd FE180/PS90 B2ca-s1,d1,a1 13 66 minutes
59 2 cables JE-H(St)H 1x2x0,8 Bd FE180/PS90 B2ca-s1,d1,a1
20 75 minutes
60 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 90 minutes no failure / interruption 61 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 12 90 minutes no failure / interruption 62 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 11 90 minutes no failure / interruption 63 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 9 90 minutes no failure / interruption 64 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 7 90 minutes no failure / interruption 65 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 6 90 minutes no failure / interruption 66 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 5 90 minutes no failure / interruption 67 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 19 90 minutes no failure / interruption 68 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 4 90 minutes no failure / interruption 69 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 3 90 minutes no failure / interruption 70 2 cables JE-H(St)H 1x2x0,8 Bd FE180/PS90 B2ca-s1,d1,a1
18
83 minutes
71 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1 90 minutes no failure / interruption 72 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1
2
90 minutes no failure / interruption 73 2 cables JE-H(St)H 1x2x0,8 Bd FE180/PS90 B2ca-s1,d1,a1 31 minutes
74 2 cables SHXKFH-V180 1x2x0,8 Lg P90-R B2ca-s1,d1,a1
1 90 minutes no failure / interruption 75 2 cables JE-H(St)H 1x2x0,8 Bd FE180/PS90 B2ca-s1,d1,a1 90 minutes no failure / interruption
[1] The fire test was discontinued in 94
thminute at the request of test sponsor.
Specimens S1 – S44 were tested by three-phase voltage supply 3 x 230/400V with bulbs 240V / 60 W.
Specimens S52 – S75 were tested by one-phase voltage supply 1 x 110V with LED diodes 3V /0,03W.
Circuit breakers with rating 3 A were used.
FIRES-JR-098-14-NURE
FIRES 149/S-28/03/2014-E Page: 6/9
4. CLASSIFICATION AND FIELD OF APPLICATION 4.1 REFERENCE OF CLASSIFICATION
This classification has been carried out in accordance with clause 3.2 of DIN 4102 – 12:1998-11.
4.2 CLASSIFICATION ACCORDING TO STN 92 0205:2012
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Cable trays KGL/KGOL300H60.
Consoles WPCB1000 reinforced by spacer BR40, brackets WWS/WWSO300.
Loading 10kg.m-1. Consoles in spacing of 1500 mm.
Track No. 1.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 JE-H(St)H
FE180/PS90 B2ca-s1,d1,a1
JE-H(St)H 1x2x0,8 Bd FE180/PS90
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Cable mesh trays KDS/KDSO300H60.
Consoles WPCB1000 reinforced by spacer BR40, brackets WWS/WWSO300.
Loading 10kg.m-1. Consoles in spacing of 1500 mm.
Track No. 2.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 JE-H(St)H
FE180/PS90 B2ca-s1,d1,a1
JE-H(St)H 1x2x0,8 Bd FE180/PS90
B2ca-s1,d1,a1 E 30
n x 2 x ≥ 0,8 mm n ≥ 1 E 30
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Cable trays KGJ/KGOJ400H60.
Consoles WPCB100, brackets WWS/WWSO400,
holders UPW/UPWO, threaded rods PG M10.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Track No. 3.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Cable mesh trays KDS/KDSO400H60.
Consoles WPCB100, brackets WWS/WWSO400,
holders UPW/UPWO, threaded rods PG M10.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Track No. 4.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R
B2ca-s1,d0,a1 Cable trays KGL/KGOL300H60.
Consoles combined of assembling profiles CWP40H22/04 and
threaded rods PG M10.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Track No. 5.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Cable mesh trays KDS/KDSO300H60.
Consoles combined of assembling profiles CWP40H22/04 and
threaded rods PG M10.
Loading 20kg.m-1. Consoles in spacing of 1500 mm.
Track No. 6.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R
B2ca-s1,d0,a1 Cable trays KFL100H60 fixed to trapezoidal hanger WT/WTO120 on ceiling by threaded rods PG M6
and center hangers ZSW.
Loading 5kg.m-1. Hangers in spacing of 1500 mm.
Tracks No. 7 and 8.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Cable mesh trays KDS/KDSO100H60 fixed to trapezoidal hanger WT/WTO120 on ceiling by threaded rods PG M6
and center hangers ZSW.
Loading 5kg.m-1. Hangers in spacing of 1500 mm.
Tracks No. 9 and 10.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 1-CXKH-V
P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Cable trays KGL/KGOL300H60.
Consoles combined of assembling profiles CWP40H22/03 and threaded rods PG M10. Consoles fixed to trapezoidal steel sheet by trapezoidal hangers WT/WTO120.
Loading 10kg.m-1. Consoles in spacing of 1500 mm.
Track No. 11.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Cable mesh trays KDS/KDSO300H60.
Consoles combined of assembling profiles CWP40H22/03 and threaded rods PG M10. Consoles fixed to trapezoidal steel sheet by trapezoidal hangers WT/WTO120.
Loading 10kg.m-1. Consoles in spacing of 1500 mm.
Track No. 12.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Cable trays KCP/KCOP300H60.
Consoles WPCB1000, brackets WWS/WWSO400,
holders UPW/UPWO, threaded rods PG M10.
Loading 10kg.m-1. Consoles in spacing of 1200 mm.
Track No. 13.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
NHXH FE180/E90
NHXH-J 4x1,5 RE FE180/E90 E 90 n x ≥1,5 – 10 mm2
n ≥ 2 E 90
NHXH-J 4x10 RE FE180/E90 E 90
JE-H(St)H FE180/PS90 B2ca-s1,d1,a1
JE-H(St)H 1x2x0,8 Bd FE180/PS90
B2ca-s1,d1,a1 E 60
n x 2 x ≥ 0,8 mm n ≥ 1 E 60 1-CXKH-V
P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Cable ladders DGOP400H60.
Consoles WPCB1000, brackets WWS/WWSO400,
holders UPW/UPWO, threaded rods PG M10.
Loading 20kg.m-1. Consoles in spacing of 1200 mm.
Track No. 14.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
NHXH FE180/E90
NHXH-J 4x1,5 RE FE180/E90 E 90 n x ≥1,5 – 10 mm2
n ≥ 2 E 90
NHXH-J 4x10 RE FE180/E90 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 JE-H(St)H
FE180/PS90 B2ca-s1,d1,a1
JE-H(St)H 1x2x0,8 Bd FE180/PS90
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 JE-H(St)H
FE180/PS60 JE-H(St)H 1x2x0,8 Bd FE180/PS60 E 30
n x 2 x ≥ 0,8 mm n ≥ 1 E 30
FIRES-JR-098-14-NURE
FIRES 149/S-28/03/2014-E Page: 8/9
Cable Type of tested cable, single cross-
sections and number of conductors Arrangement
Classification for type of tested cable
(by cross-sections and number of
conductors)
Classification for cable
NHXH FE180/E90
P
NHXH-J 4x1,5 RE FE180/E90 P
Cable trays KCP/KCOP300H60.
Assembling profiles CWP/CWOP40H40 fixed to wall,
brackets WWS/WWSO400, holders UPWK/UPWKO, threaded rods PG M10 fixed to
profiles by hangers WKPO.
Loading 10kg.m-1. Consoles in spacing of 1200 mm.
Track No. 15.
E 60 n x ≥1,5 – 10 mm2 n ≥ 2 E 60
NHXH-J 4x10 RE FE180/E90 P E 60
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 JE-H(St)H
FE180/PS90 B2ca-s1,d1,a1
JE-H(St)H 1x2x0,8 Bd FE180/PS90
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 JE-H(St)H
FE180/PS60 JE-H(St)H 1x2x0,8 Bd FE180/PS60 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 1-CXKH-V
P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R
B2ca-s1,d0,a1 Cable ladders DGOP400H60.
Assembling profiles CWP/CWOP40H40 fixed to wall,
brackets WWS/WWSO400, holders UPWK/UPWKO, threaded rods PG M10 fixed to
profiles by hangers WKPO.
Loading 20kg.m-1. Consoles in spacing of 1200 mm.
Track No. 16.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
NHXH FE180/E90
P
NHXH-J 4x1,5 RE FE180/E90 P E 30 n x ≥1,5 – 10 mm2
n ≥ 2 E 30
NHXH-J 4x10 RE FE180/E90 P E 30
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Track is made of cable hangers (OZO) fixed to ceiling by expansion screws (MKR Ø6 x 30)
mm in spacing of 600 mm.
Track No. 17.
E 60 n x ≥1,5 – 10 mm2 n ≥ 2 E 60 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Track is made of single cable clips (UDF) fixed to ceiling by expansion screws (MKR Ø6 x 30)
mm in spacing of 600 mm.
Track No. 18.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 JE-H(St)H
FE180/PS90 B2ca-s1,d1,a1
JE-H(St)H 1x2x0,8 Bd FE180/PS90
B2ca-s1,d1,a1 E 60
n x 2 x ≥ 0,8 mm n ≥ 1 E 60
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Track is made of cable hangers (OZSO) fixed to ceiling by screws (SBSTM 7,5 x 52) mm in spacing
of 600 mm.
Track No. 19.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Track is made of single cable clips (UDF) fixed to trapezoidal steel sheet by steel self-drilling screws (SMD 4,8 x 16) mm in spacing of
600 mm.
Track No. 20.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90
SHXKFH-V180 P90-R B2ca-s1,d1,a1
SHXKFH-V180 1x2x0,8 Lg P90-R
B2ca-s1,d1,a1 E 90
n x 2 x ≥ 0,8 mm n ≥ 1 E 90 JE-H(St)H
FE180/PS90 B2ca-s1,d1,a1
JE-H(St)H 1x2x0,8 Bd FE180/PS90
B2ca-s1,d1,a1 E 60
n x 2 x ≥ 0,8 mm n ≥ 1 E 60
1-CXKH-V P90-R B2ca-s1,d0,a1
1-CXKH-V 4x1,5 RE P90-R B2ca-s1,d0,a1
Track is made of cable hangers (OZMO) fixed to ceiling by expansion screws (MKR Ø6 x 30)
mm in spacing of 600 mm.
Track No. 21.
E 90 n x ≥1,5 – 10 mm2 n ≥ 2 E 90 1-CXKH-V 4x10 RE P90-R
B2ca-s1,d0,a1 E 90